answersLogoWhite

0

If the load requires a single circuit breaker, as most three phase loads do, you need a separate neutral for each. This allows you to check the balance between each phase and the other phases as well as neutral, in order to detect a ground fault.

It depends on the purpose of the three phase circuits - if this were CT cables, then yes, unless you intentionally over sized the ground wire. Otherwise this would cause unusually high voltage rise in the secondary of the CT during ground faults, which could lead to saturation (unless CT ratio is intentionally set high). As noted above, having separate neutrals helps to determine balance, although you can measure 3I0 from the phase currents for a similar relationship without actually looking at the neutral at all (some relays doe this for ground protection instead of directly measuring neutral current, see SEL's 351 for an example relay). No matter what, this would be highly irregular, and I wouldn't recommend scrimping on a neutral. In my experience, the more you move away from accepted practices (not to dampen ingenuity...), the more trouble you create for the future.

If the loads were strictly three phase then there would not be any neutral needed. If from a three phase distribution panel the loads were three single phase loads then you can use one neutral for the three phase wires. This is a code rule that has to be adhered to. A same N, B same N, C same N and only in this combination. Conduit fill 4 wires, two three phase four wire circuits, conduit fill 8 wires.

User Avatar

Wiki User

15y ago

What else can I help you with?

Continue Learning about Engineering

How many single phase can you run on a 100amp 3 phase?

You can divide a three phase service into (3) single phase circuits providing you have a 4th neutral wire.


What is meaning for TPN isolator and SPN isolator?

TPN (Triple Pole and Neutral) isolator is an electrical switch used to disconnect three-phase electrical circuits, ensuring that all three phases and the neutral are isolated for safety during maintenance or servicing. SPN (Single Pole and Neutral) isolator, on the other hand, is used for single-phase circuits, allowing isolation of the live wire and the neutral wire. Both types of isolators are crucial for ensuring safety by preventing accidental energization of circuits during work.


Condition of three phase in which there is no need of neutral?

A delta-connected system is described as being a three-phase, three-wire, system, and doesn't have a neutral. But a balanced star (wye) connected load (e.g. a three-phase induction motor) doesn't actually require a neutral.


Can the star point of a 400 volt three phase generator be grounded to produce 240 volts?

A 400/230-V three-phase generator hase three line terminals, together with a neutral terminal. The line voltage (i.e. the voltage between any pair of line terminals) is 400 V, while the phase voltage (i.e. the voltage between any line terminal and the neutral terminal) is 230 V.


Why neutral is not requied in 3 phase?

As far as I understand, you don't need neutral line for connecting appliances that is 3-phase compilant. You only need the neutral line to connect a single phase appliance, which you connect along with one of the three lines.

Related Questions

What is the code ruling in the US on 3 phase branch circuits and the neutral?

A three phase system will have 3 phase branch circuits and no neutral.


How many neutrals for three-phase multi circiuts?

For a three phase distribution system there is one neutral. In North America the electrical code allows three individual branch circuits to connect with one neutral as long as the three circuits each use an individual phase leg. This differs from 120/240 volt single phase wiring where only two legs can be used with one neutral.


Can a three phase circuit be installed in the same conduit or in different conduits?

The conductors of any three phase circuit must be run in the same conduit. If the circuit requires a neutral, it must also run with the conductors in the same conduit. (If they were to be run in more than one conduit or raceway, the circuit would not operate properly.)


How many single phase can you run on a 100amp 3 phase?

You can divide a three phase service into (3) single phase circuits providing you have a 4th neutral wire.


What is meaning for TPN isolator and SPN isolator?

TPN (Triple Pole and Neutral) isolator is an electrical switch used to disconnect three-phase electrical circuits, ensuring that all three phases and the neutral are isolated for safety during maintenance or servicing. SPN (Single Pole and Neutral) isolator, on the other hand, is used for single-phase circuits, allowing isolation of the live wire and the neutral wire. Both types of isolators are crucial for ensuring safety by preventing accidental energization of circuits during work.


How many circuits can share one neutral?

Multiple circuits can typically share one neutral as long as the currents do not exceed the capacity of the neutral wire. This practice is common in residential electrical installations, especially in split-phase systems where two circuits share a neutral. It is important to follow local electrical codes and regulations when combining circuits on a shared neutral.


Single phase and three phase circuit?

Yes, there is a difference between single phase and three phase circuits.


Condition of three phase in which there is no need of neutral?

A delta-connected system is described as being a three-phase, three-wire, system, and doesn't have a neutral. But a balanced star (wye) connected load (e.g. a three-phase induction motor) doesn't actually require a neutral.


Why neutral cross section is half the phase in three phase cable while it has to carry current of summation of all phase..?

The current carried by the neutral of a three phase four wire system is the un balanced current. If the three phase system was completely balanced on all three phases there would be no need for a neutral, eg a three phase motor. This neutral current will be less that the phase current so a reduction in the neutral size is allowed.


What is a single circuit?

is the measured voltage,generated between a line voltage and the starting point of a three phase transformer, which is the neutral point. Answer: it is an ac circuit in which the supply has a live and neutral wire, usually at one of the standard voltages 110/120v or 220/240 v. A three-phase circuit is a combination of three single-phase circuits with the phases of the voltages 120 degrees apart so that they peak in a regular sequence.


Can the star point of a 400 volt three phase generator be grounded to produce 240 volts?

A 400/230-V three-phase generator hase three line terminals, together with a neutral terminal. The line voltage (i.e. the voltage between any pair of line terminals) is 400 V, while the phase voltage (i.e. the voltage between any line terminal and the neutral terminal) is 230 V.


Why neutral is not requied in 3 phase?

As far as I understand, you don't need neutral line for connecting appliances that is 3-phase compilant. You only need the neutral line to connect a single phase appliance, which you connect along with one of the three lines.