Inrush is due to the saturation of the core of the transformer.

When the highside device closes to energize the transformer, it does not always do so right at a voltage peak. The transformer core B (magnetic field) will be 90 degrees out of phase with the applied voltage, so a peak voltage close is ideal. Once it is closed, the B will continue up and down 90 degrees out of phase with the voltage. Assuming there is no residual magnetic field (B starts at zero), it will be offset by the initial non - peak close. This offset in magnetic field will cause the core to go into saturation; depending on the core design it may be further or less into saturation on different Transformers.

When the core saturates, large currents flow, and these currents (normally) have a high 2nd harmonic component which is used in protective relaying to restrain for inrush.

User Avatar

Wiki User

15y ago

What else can I help you with?

Continue Learning about Engineering

What is the difference between the inrush current and the fault current?

Magnetizing inrush current has bigger 2nd harmonics compare to short circuit current. the second harmonics content is about >60% of fundamental harmonic. magnetizing inrush current happened when we energised the transformer, and short circuit current happened if there is a short circuit between different alive phase.


Does a transformer draw a lot of current when first connected to a source?

Yes it does as it is an Inductor and an Inductor needs to build up a magnetic field. It is called INRUSH current.


What is magnetic inrush?

Magnetic inrush refers to the sudden surge of current that occurs when an inductive device, such as a transformer or motor, is energized. This phenomenon happens because the magnetic core of the device initially presents low impedance, leading to a high initial current flow until the magnetic field stabilizes. The inrush current can be several times greater than the normal operating current, potentially causing equipment damage or tripping circuit breakers if not properly managed. To mitigate this, various techniques, such as using inrush current limiters or soft starters, are often employed.


What does the term VA mean when applied to a control transformer?

VA refers to the effective load that is placed upon the Control Transformer (also known as Selection Inrush VA).


Why inrush current has a positive peak?

Inrush current has a positive peak because it represents the initial surge of electrical current when a device, such as a motor or transformer, is first energized. This peak occurs as the system attempts to rapidly establish the magnetic field necessary for operation, resulting in a brief but substantial increase in current. The positive peak reflects the instantaneous demand for power to overcome inertia and other resistive forces, before settling down to the normal operating current once the device stabilizes.

Related Questions

Magnetic inrush current in power transformer with waveforms?

The mgnetic inrush current is the current drawn by the transformer when power is applied to the primary winding


Magnetic inrush current in power transformer?

When a transformer is initially connected to a source of AC voltage, there may be a substantial surge of current through the primary winding called inrush current. Inrush current can be up to ten times higher than the continuously needed current because there is low initial resistance.


What happens to a transformer when it is first connected to a power line?

When a transformer is first connected to a power line, it experiences an inrush current, which is a high initial current that occurs as the magnetic core saturates. This inrush can be several times greater than the transformer's normal operating current and lasts for a short duration. The transformer begins to establish its magnetic field, and the secondary winding produces an induced voltage based on the primary voltage applied. Proper protective measures are often needed to manage this inrush and prevent damage to the transformer and connected equipment.


What is the difference between the inrush current and the fault current?

Magnetizing inrush current has bigger 2nd harmonics compare to short circuit current. the second harmonics content is about >60% of fundamental harmonic. magnetizing inrush current happened when we energised the transformer, and short circuit current happened if there is a short circuit between different alive phase.


Does a transformer draw a lot of current when first connected to a source?

Yes it does as it is an Inductor and an Inductor needs to build up a magnetic field. It is called INRUSH current.


What are the factors affect the magnitizing inrush current in power transformer?

1- residual flux existing before enegizing the transformer . 2- size of transformer . 3- size of power system. 4- type of magnetic material of the core. 5- the method of energizing the transformer.


What is magnetic inrush?

Magnetic inrush refers to the sudden surge of current that occurs when an inductive device, such as a transformer or motor, is energized. This phenomenon happens because the magnetic core of the device initially presents low impedance, leading to a high initial current flow until the magnetic field stabilizes. The inrush current can be several times greater than the normal operating current, potentially causing equipment damage or tripping circuit breakers if not properly managed. To mitigate this, various techniques, such as using inrush current limiters or soft starters, are often employed.


What does the term VA mean when applied to a control transformer?

VA refers to the effective load that is placed upon the Control Transformer (also known as Selection Inrush VA).


Why inrush current has a positive peak?

Inrush current has a positive peak because it represents the initial surge of electrical current when a device, such as a motor or transformer, is first energized. This peak occurs as the system attempts to rapidly establish the magnetic field necessary for operation, resulting in a brief but substantial increase in current. The positive peak reflects the instantaneous demand for power to overcome inertia and other resistive forces, before settling down to the normal operating current once the device stabilizes.


What is meant by transformer charging?

Most likely this is referring to the initial inrush that occurs when a transformer is energized. The core of a transformer is designed for a specific magnetic field strength; When a transformer is switched into a circuit, it usually will not be switched at exactly a voltage peak. When the voltage is at its' peak, the induced magnetic field will be at zero. If the switching occurs at a voltage zero, the magnetic field strength will attempt to climb to double the designed value; since the transformer core is not generally oversized to this degree, it will saturate. This causes large inflows of current to the transformer, and shows up as even harmonics (mainly second harmonics) in the current waveform. This settles out within a few seconds (generally) to a small energizing current, usually less than 1% of the transformer's rated current.


Why does a three phase transformer not short itself out when the phases are connected through the transformer?

I asked this very question to my professor in electronics 101 in college! He explained to me the load side of the transformer if not connected to any load is open. This is a great resistance to completing the circuit. This is transferred to the primary side of the transformer as a great resistance thus no current flow.