Estimated Insulation Resistance of a cable:

IR = K log (D/d)

K = specific insulation resistance in megohs - 1000 feet at 60 Deg. F (K = 2000 for PVC; 50,000 for EPR; 100,000 for XLP)

D = diameter over insulation

d = diameter under insulation

IR = insulation resistance in megohms - 1000 feet. Note that IR is inversely proportional to the cable length. So don't forget to divide the calculated IR for 1000 ft. by your Cable Length (L) then multiplied by 1000.

Be advised that in the real world, the measured IR may not be anywhere close to the calculated IR due to extraneous influences such as humidity, temperature, dirt, etc.

User Avatar

Wiki User

14y ago

What else can I help you with?

Related Questions

How do you test leakage on equipment?

by measuring the insulation resistance then by usig the formula for finding leakage current leakage current =voltage applied /resistance measured by megger.


What is the formula for calulating the volume and the area of a sphere?

r is the radius of the sphereSurface Area: S = 4Πr2Volume: V = 4/3Πr3Π=pi or 3.14


What is LV cable insulation resistance acceptance value?

The minimum acceptable insulation resistance value is calculated using the following formula: Rinsulation= (Vrated + 1 ) x (304.8 / L ) Where: Rinsulation is the minimum acceptable insulation resistance value, in mega-ohms; Vrated is the rated voltage of the cable (typically printed on the cable), in kilovolts; and L is the length of the cable, in meters (if the cable length is in feet, replace the number 304.8 with 1000).


How the heat losses through insulation can be calculated?

Heat losses through insulation can be calculated using the formula Q = (T1 - T2) / R, where Q is the heat loss, T1 and T2 are the temperatures on the two sides of the material, and R is the thermal resistance of the insulation material. Thermal resistance can be determined using the formula R = L / (k * A), where L is the thickness of the material, k is the thermal conductivity, and A is the cross-sectional area. By calculating the thermal resistance and temperature difference, the heat loss through insulation can be estimated.


What is the formula for calulating the volume and the area of a triangular prism?

Surface area = 2A + PdwhereA = area of the base shapeP = perimeter of base shaped = height of prismVolume = Ad


What is the formula for calculating the resistance in an electrical circuit?

The formula for calculating resistance in an electrical circuit is R V/I, where R is the resistance, V is the voltage, and I is the current.


How do you calculate contact resistance?

Resistance is resistance , no matter if it is contact resistance or any other resistance. And formula is R = V / I.


What is the formula for electrical resistance?

Resistance(Ohms)= Voltage(volts)/Current (Ampheres) -X


What is the Dimensional formula of thermal resistance?

no


What is the dimensional formula of Resistance?

Resistance = V/I Dimensional formula for V ML2T -3A -1 Dimensional formula for I A Dimensional formula for R= ML2T -3A -1 / A = ML2T -3A -2


What is dimensional formula of resistance?

Resistance = V/I Dimensional formula for V ML2T -3A -1 Dimensional formula for I A Dimensional formula for R= ML2T -3A -1 / A = ML2T -3A -2


Formula to calculate min insulation resistance?

insulation resistance = (2 * operating voltage +1000V) at operating temperature if you define what you mean by minimum insulation resistance maybe i could help 132,000V on the towers is usually happy with 6' of air some insulation is far better than air dry air 500v/mill thermoplastics 6000v/mill your power drill has 1/8" - 1/4" of plastic on the cord and perhaps .001" on the wire in the coils the cord gets rougher handling anything practical insulation resistance (2 * operating voltage +1000V) witch means a 1500Vdc megger is ok for 120V appliances should be safe to handle if its more than 10megohms the 1500V will bridge any pinholes or airgaps NEVER use a vom the 9v battery wont find a pinhole or an air gap ceramic on heaters and toasters has a way of letting metals diffuse in it lowering the resistance over time also it usually lowers with temperature so the resistance reading will be a lot lower while its hot