you would want to use a meg-ohmeter (to measure high values of resistance)

you would test from each phase wire to the motor housing frame (to check for unwanted ground faults)

if the windings are isolated, you would also check between each set of windings (if the winding are internally connected as part of the manufacturing process, you will read low resistance between the windings because they are in essence spliced to each other and therefore this test would be meaningless)

<<>>

Megger test

On the whole megger testing is non destructive. What happens is a DC voltage is applied to the device or winding under test. It is an insulation test to see is the insulation has been injured in any way to cause a short circuit when normal power is applied to it. On my megger there are 3 ranges 300V, 750V, and 1000 volts. Applying the proper voltage is essential to not damaging the device you are testing. Working voltages up to 240 volts should use the 300 range. Working voltages up to 600 volts use the 750 volt range and working voltages above 600 use the 1000 volt range. As you can see if you used the 1000 volt range on a device that had a working voltage of say 24 volts you could damage the insulation just by testing it. So meggering a device is non destructive if you use the tester as its instructions tell you to.

User Avatar

Wiki User

14y ago

What else can I help you with?

Continue Learning about Engineering

How do you measure insulation resistance between windings for 120KVA alternator?

Use a megger or a insulation tester. Place one lead on any of the phases nd other lead the alternator boy. Observe the indicator. In megger it s good with infinity or it must be minimum 100M OHM, IF IT SHOWs 50 it could be coz of moisture in winding by heating the alternator the insulation resistance value may improve


Can you check capacitor by megger?

Yes, you can check a capacitor using a megger (insulation resistance tester) by measuring the insulation resistance between the capacitor terminals and the casing or ground. However, it’s important to note that a megger primarily tests insulation quality and not the capacitor's capacitance or performance under operational conditions. Before testing, ensure the capacitor is fully discharged to prevent damage to the megger or inaccurate readings. Always follow safety precautions when working with electrical components.


How do you perform a 'Residual Loop Test' in domestic installation?

To perform a Residual Loop Test in a domestic installation, first ensure that all electrical appliances are disconnected. Use a suitable insulation resistance tester to measure the resistance between the live conductors and earth, and then check the loop impedance by connecting the tester to the live and neutral conductors. Record the readings, ensuring they comply with the relevant electrical standards. Finally, analyze the results to confirm that the installation is safe and effective, addressing any issues that may arise.


How do you identify a burnt out motor without meggering?

If the motor is still connected to its electrical supply and it is safe to do so switch it on and check for an odour of burning insulation and or the presence of smoke. A burnt out winding can cause a motor to run very slowly and make a unusual humming noise, if this cannot be achieved safely then make sure the motor main switch is isolated and sniff around any ventilated area of the motor to check for the smell of burning insulation. If you have a circuit tester that will check for continuity then use this after firstly completely isolating the motor from its electrical supply and disconnecting the wiring to the input terminals. You may see and open circuit reading between the live and neutral terminals or a short circuit between one or the other terminal when the tester is connected between the terminals and the metal case of the motor, remember that a circuit tester will read resistance so try the test on the appropriate setting, example; RX10K


When are megger testers used?

On the whole megger testing is a non destructive test. What happens is a DC voltage is applied to the device or winding under test. It is an insulation test to see is the insulation has been injured in any way to cause a short circuit when normal power is applied to it. On my megger there are 3 ranges 300V, 750V, and 1000 volts. Applying the proper voltage is essential to not damaging the device you are testing. Working voltages up to 240 volts should use the 300 range. Working voltages up to 600 volts use the 750 volt range and working voltages above 600 use the 1000 volt range. As you can see if you used the 1000 volt range on a device that had a working voltage of say 24 volts you could damage the insulation just by testing it. So meggering a device is non destructive if you use the tester as its instructions tell you to.

Related Questions

How do you measure insulation resistance between windings for 120KVA alternator?

Use a megger or a insulation tester. Place one lead on any of the phases nd other lead the alternator boy. Observe the indicator. In megger it s good with infinity or it must be minimum 100M OHM, IF IT SHOWs 50 it could be coz of moisture in winding by heating the alternator the insulation resistance value may improve


Can you check capacitor by megger?

Yes, you can check a capacitor using a megger (insulation resistance tester) by measuring the insulation resistance between the capacitor terminals and the casing or ground. However, it’s important to note that a megger primarily tests insulation quality and not the capacitor's capacitance or performance under operational conditions. Before testing, ensure the capacitor is fully discharged to prevent damage to the megger or inaccurate readings. Always follow safety precautions when working with electrical components.


How accurate are the readings of a megger test?

While using megger we only have to see whether resistance breaksdown at the upper value mentioned. Since megger generates high voltage we can check whether breakdown takes place or not.Megger has a range from o to infinity.So it is not possible to find accurate resistance,hence it is used as an insulation tester


How can you know that power cable need to be replaced?

you check the insulation and it is degraded,hole in it or it does not have a very high ohms of resistance,which means the insulation is bad.


Can insulation resistance of cable be checked with a volt meter?

No. A volt-ohmmeter will not check insulation. To check cable insulation you need a special device (called a megger) made for the purpose that imposes a high voltage and measures current leaks.


How do you perform a 'Residual Loop Test' in domestic installation?

To perform a Residual Loop Test in a domestic installation, first ensure that all electrical appliances are disconnected. Use a suitable insulation resistance tester to measure the resistance between the live conductors and earth, and then check the loop impedance by connecting the tester to the live and neutral conductors. Record the readings, ensuring they comply with the relevant electrical standards. Finally, analyze the results to confirm that the installation is safe and effective, addressing any issues that may arise.


Why you do insulation resistance test?

in order to avoid unwanted short circuit break downs.... short circuit can burn the transformer and motor winding.... Megger is the device used to check the insulation .


What is the function of a insulation tester?

An insulation tester is s meter used by electricians and cabling technicians to check the quality of the electrical installation. The insulating materials coating the copper conductors can be nicked, chafed or nibbled by rats either during installation or during it's lifetime. The tester generates a high DC voltage of around 500V to 1000 V. This high voltage is applied in series with a sensitive ammeter to one conductor to electrical earth or between two open circuit conductors. Any current flowing through the meter wiil be effectively via the insulation or perhaps through a water ingress fault. Any value of leakage current above a recommended threshold has to be investigated,repaired and tested again. The unit is also used to check the quality of the copper terminations and resistance of the conductors. Again,any high resistance reading will need to be checked to ensure tight terminations otherwise a fire may ensue during periods of heavy current load on the cable.


How to check for an ungrounded wire?

You can use a wire tester to check for a ungrounded wire. Attached the wire tester to the battery posts. The tester will show you if the ground is weak or strong.


Solid layer test method on insulator?

One common method to test the solid layer on an insulator is the Megger test, where a high voltage is applied across the insulation to measure its resistance. Another method is the insulation resistance test, which measures the resistance of the insulation to detect any defects. Additionally, visual inspection can also be used to check for any visible damage or contamination on the insulator's surface layer.


What is a land tester?

land tester is use for check a utp cable..if is worth


Why 5KV voltage is applied to Megger for insulation resistance measurement?

It is a easy voltage to obtain and can check for breakover in the insulation. The voltage is higher then what would be put through most wire and shows any weakness.