answersLogoWhite

0

What else can I help you with?

Continue Learning about Engineering

What is defrential protection relay?

I am going to assume that you are asking about a differential relay. It is basically just that- it compare two different sources and will trip at a set value value of the difference. These can be directional as well. A couple of examples are transformer protective relays and bus differential. A transformer relay will measure the amount of current coming into the transformer and the amount of current going out. If there is a disparity due to an internal fault the relay will trip the supply source and deenergize the transformer. Same for the Bus differential.


Why differential relay is not used for 11kv transformers?

It depends what you mean by an '11-kV transformer'; do you mean a primary transformer (33/11-kV transformer) or a distribution transformer (11-kV/400-230-V transformer). Differential protection IS offered on primary transformers.


What is differential transformer protection?

The current input (primary) to a transformer is proportional to the output (secondary) current. Differential protection relays monitor these via current transformers (CT). The percentage of difference between primary and secondary can be adjusted. If it is over the seting the relay will trip the primaryand secondary feeder breakers. Thus indicating an inbalance between internal phasewindings and or shorts to earth.


What is the function of capacitor voltage transformer at the switch yard?

function of capacitive voltage transformer is measure high transmission voltage with low range voltmeter and oprate the relay circuit to oprate CBs.


What factor cause spill current on external fault in case of transformer differential protection?

Spill current during an external fault in transformer differential protection is primarily caused by the unequal impedance in the transformer windings and the connected power system. When an external fault occurs, the fault current flowing through the transformer can create a differential current between the primary and secondary windings due to their differing voltage drops and phase shifts. Additionally, the presence of harmonics and the effects of CT (current transformer) saturation can further contribute to this spill current, complicating the differential relay's ability to distinguish between internal and external faults.

Related Questions

What is the definition of differential relay and how does it function?

In power transformer, a differential relay is a relay that verifies the balance of current between the primary and the secondary face of a transformer. It is also employed in other components of the power system like in protecting cables. Differential relay is also called a unit protection.


Where you can see differential protective relay?

Power Transformer


What is defrential protection relay?

I am going to assume that you are asking about a differential relay. It is basically just that- it compare two different sources and will trip at a set value value of the difference. These can be directional as well. A couple of examples are transformer protective relays and bus differential. A transformer relay will measure the amount of current coming into the transformer and the amount of current going out. If there is a disparity due to an internal fault the relay will trip the supply source and deenergize the transformer. Same for the Bus differential.


Why differential relay is not used for 11kv transformers?

It depends what you mean by an '11-kV transformer'; do you mean a primary transformer (33/11-kV transformer) or a distribution transformer (11-kV/400-230-V transformer). Differential protection IS offered on primary transformers.


Dear all what direct consequences can be from Current transformer on generator with respect to differential protection relay?

CT's are used as inputs to the differential. If the CT is bad, or it is not wired to the differential correctly, it will cause differential current to be seen by the relay, resulting in a trip.


What is a function of a Buchholz relay?

A Buchholz relay is designed to detect a failing oil-filled power transformer. It will automatically disconnect the transformer and produce an alarm signal.


What is differential transformer protection?

The current input (primary) to a transformer is proportional to the output (secondary) current. Differential protection relays monitor these via current transformers (CT). The percentage of difference between primary and secondary can be adjusted. If it is over the seting the relay will trip the primaryand secondary feeder breakers. Thus indicating an inbalance between internal phasewindings and or shorts to earth.


How you using ref relay in transformer?

an REF relay (restricted earth fault) is used to provide ground fault protection for a transformer. Its' operation is limited by CTs starred towards the transformer (usually on the transformer bushings or in breakers used to isolate the transformer), so it will only operate for transformer related faults. Because of this, it can be set to operate very quickly.


What is the function of capacitor voltage transformer at the switch yard?

function of capacitive voltage transformer is measure high transmission voltage with low range voltmeter and oprate the relay circuit to oprate CBs.


Why percentage differential protection is preferred over differential protectionfor internal faults?

if we are seeking for internal protection of transformer only, then if any external fault occurs then it will show the fault though it should not. what a percentage differential protection will do means, it will include a restraining coil which is excited by the current in the transformer itself. Also the percentage differential relay ha taps. So it is easy to avoid the external fault. for reference check 'theory and applications of transformer differential protection' by GEORGE W.McKENNA, AIEE transactions 1950,volume 69


What factor cause spill current on external fault in case of transformer differential protection?

Spill current during an external fault in transformer differential protection is primarily caused by the unequal impedance in the transformer windings and the connected power system. When an external fault occurs, the fault current flowing through the transformer can create a differential current between the primary and secondary windings due to their differing voltage drops and phase shifts. Additionally, the presence of harmonics and the effects of CT (current transformer) saturation can further contribute to this spill current, complicating the differential relay's ability to distinguish between internal and external faults.


What is the angle of buchholz relay?

To enable any gases generated within the transformer to bubble along the pipe towards the expansion tank. The Buchholz relay itself isn't angled; it's the pipe in which its fitted.