It depends upon the Generator system voltage. For 3 Phase, 600 Volt system, it will be 73 Amps For 3 Phase, 480 Volt system, it will be 90 Amps For 3 Phase, 208 Volt system, it will be 208 Amps
Full load amps for a three phase, 375KVA generator is 375 / (voltage in kV) / sqrt(3).
To calculate the kVA rating of the transformer, you can use the formula: kVA = (Voltage × Current) / 1000. In this case, the secondary winding delivers 10 amps at 480 volts. Therefore, the kVA rating is (480 V × 10 A) / 1000 = 4.8 kVA.
635kva
To convert amps to kilovolt-amperes (kVA), you can use the formula: kVA = (Amps × Voltage) / 1000. The voltage level is essential for the calculation, as kVA is a function of both current (in amps) and voltage (in volts). For example, at a voltage of 400V, 350 amps would be approximately 140 kVA (350 × 400 / 1000). Without the voltage value, the kVA cannot be accurately determined.
62.5 amps
To answer this question the voltage of the generator must be given.
The formula you are looking for is , A = kva x 1000/Volts.
To calculate the output amps of a 600kVA generator at 240V, you would use the formula Amps = kVA / Volts. In this case, it would be 600kVA / 240V = 2500 amps.
The amps you can get from a 500 kVA transformer would depend on the voltage of the transformer's output. To calculate amperage, you can use the formula: Amps = Power (kVA) / Voltage. For example, if the output voltage is 480V, you would get approximately 1041 amps (500 kVA / 480V).
It depends upon the Generator system voltage. For 3 Phase, 600 Volt system, it will be 73 Amps For 3 Phase, 480 Volt system, it will be 90 Amps For 3 Phase, 208 Volt system, it will be 208 Amps
I=Kva*1000/v*1.732 =500*1000/415*1.732 =500,000/718.78 =695.62 Amps. So max.load of 500kva DG is 695.62 Amps
500 KVA how many amps? almost 650 Amps according to formula.
Full load amps for a three phase, 375KVA generator is 375 / (voltage in kV) / sqrt(3).
A 15 KVA - Generator operating at 380 Volts can cater to only 22.79 Amps. It cannot cater to a 60 Amps breaker
4core*240mm square..
To calculate the amperage of a 40 kVA load, you will need to know the voltage. The formula is: Amps = kVA / Volts. Assuming a standard line voltage of 120V, the amperage for a 40 kVA load would be approximately 333 amps.