At 600 volts the rule of thumb is one amp per horsepower. So a 20 HP motor would need 20 amp wire. The code book states that a 20 HP motor at 575 volts draws 22 amps. The conductor for a motor has to be 125% rating of the motors FLA (full load amps). 22 x 125% = 27.5 amps. A #10 copper conductor with a insulation factor of 60,75 or 90 degrees C is rated at 30 amps.
If the motor wire numbers are L1, L2 and L3, it is not a single phase motor. It is a three phase motor. Also for future reference, a 220 volt single phase motor does not use a neutral.
5000 volt
The electrical code states that a 7.5 HP 460 volt three phase motor draws 11 amps. For fuse sizes, non time delay - 30 amps, time delay type D - 20 amps and if using a breaker it will be 30 amps. Minimum wire size is #12 and the maximum setting of overload devices will be 13.75 amps
Depends on the motor and the load on that motor. If the motor is loaded to its capacity, it will draw the same amount of power as it would on 690 volts - which will result in ( 690/480 = ) 144% of normal current, which will thermally damage the motor, or will trip overload protection.
No. If the motor runs backwards, swap any two phases to reverse the rotation, like this: Old wiring: phase A - brown wire - motor lead T1 phase B - yellow wire - motor lead T2 phase C - orange wire - motor lead T3 New wiring: phase A - brown wire - motor lead T2 phase B - yellow wire - motor lead T1 phase C - orange wire - motor lead T3
If the motor wire numbers are L1, L2 and L3, it is not a single phase motor. It is a three phase motor. Also for future reference, a 220 volt single phase motor does not use a neutral.
5000 volt
A motor can be reckoned at 1.6 kVA per horse-power, so on a 415 v 3-phase suppy the current for 20 HP would be 45 amps. For continuous use the wire size should be 25 mm2
no
The recommended wire size for a 220 volt circuit according to the 220 volt wire size chart is typically 10 gauge wire for a circuit with a maximum of 30 amps.
The electrical code book states that a 40 HP 230 volt three phase motor draws 104 amps. For that motor the wire must be rated for 131 amps, Non time delay fuses at 300 amps, time delay fuses at 175 amps or a 250 amp circuit breaker. When calculating wire sizes and motor protection the motor's full load amperage should be taken from the motor's nameplate.
208 volts is not a common single phase voltage but you could just size your breaker to the capabilities of the conductor. 208 is normally a phase to phase voltage <<>> Many 230 volt motors can be connected to lower voltage supplies. These motors can be connected to supplies of 208 and 200 volts. The code requirement is that the 230 volt full load amperage of the motor be increased by 10% and 15% respectively for wire sizing and breaker selection. To answer the question you will need a two pole 15 amp breaker.
The size of conductor needed will be a #14. It should be copper and have an insulation factor of 90 degrees C. The fact that it is a three phase load does not enter into the calculation of the wire size.
For a 3 wire 240-volt single-phase motor, typically one overload unit would be required. The overload unit would protect the motor from overheating due to excessive current draw. It is important to select the correct size overload unit based on the motor's full load amperage.
The electrical code states that a 7.5 HP 460 volt three phase motor draws 11 amps. For fuse sizes, non time delay - 30 amps, time delay type D - 20 amps and if using a breaker it will be 30 amps. Minimum wire size is #12 and the maximum setting of overload devices will be 13.75 amps
A 10 mm cable is most commonly used for a 500 KVA transformer, 240 volt, 3 phrase. The size of the wire that is used in a transformer is based on the voltage.
The motor would take 10-12 amps which would need wire of 1.5 mm2 or larger. For a permanent installation use the next size, 2.5 mm2 cross section.