The neutral size is typically 50 percent of the phase conductors in a cable to ensure proper current-carrying capacity and safety in unbalanced load conditions. In three-phase systems, if the loads are balanced, the neutral current is minimal; however, in cases of unbalanced loads, the neutral needs to handle the return current effectively. Sizing the neutral at 50 percent of the phase conductors provides a margin for safety and accounts for potential unbalances in the system. This approach also helps prevent overheating and ensures compliance with electrical codes.
As normally load distribution is done equally in all three phases, almost balanced current is drawn by load and current flow though neutral is very small when compared to the phase and hence difference in cable size is observed
To answer this question a voltage is needed.
The Neutral wire should be the same gauge and size of the phase wires. Only the Earth or Equipment wire can be smaller than the phase(hot) wires. <<>> On a three phase four wire distribution system the neutral can be reduced in size. The neutral only carries the unbalanced load current and should be sized to that current. The highest current load to neutral of the three legs is used to calculate the neutral sizing. There is no reduced neutral allowed on discharge lighting and non linear loads. A demand factor of 70% shall be permitted to be applied to that portion of the unbalanced load in excess of 200 A.
The neutral wire should be the same size as your conducters
due to unbalance load 1. Due to negetive phase sequence components in current generator and transformers suppling the load will be over heated 2. The opposite torque on the shaft will damage, rotors are more likely to damage. 3. High current through neutral of the system, normally neutral cable conductor is of lesser size then phase and hence it may be damaged.
As normally load distribution is done equally in all three phases, almost balanced current is drawn by load and current flow though neutral is very small when compared to the phase and hence difference in cable size is observed
In a 3.5 core cable, the neutral conductor carries less current compared to the phase conductors. By reducing the size of the neutral conductor to half, it helps balance the voltage drop and prevents overheating in the cable. This helps ensure the safety and efficiency of the electrical system.
The current carried by the neutral of a three phase four wire system is the un balanced current. If the three phase system was completely balanced on all three phases there would be no need for a neutral, eg a three phase motor. This neutral current will be less that the phase current so a reduction in the neutral size is allowed.
Sir, what is the cable size for 1.5kw 3phase induction motor 400v?
it means 3conductors(ie RYB) and half neutral ie size of neutral would be half size of other conductors...
70mm 4core copper cable
To answer this question a voltage is needed.
On three phase services over 200 amps the electrical code allows the electrical contractor to reduce the size of the neutral wire . This saves the customer money. There are conditions as to how much the neutral can be reduced but it is not as low as half the supply conductors. The reason that the neutral can be reduced is that it only carries the unbalanced current on the three phase four wire system.
The Neutral wire should be the same gauge and size of the phase wires. Only the Earth or Equipment wire can be smaller than the phase(hot) wires. <<>> On a three phase four wire distribution system the neutral can be reduced in size. The neutral only carries the unbalanced load current and should be sized to that current. The highest current load to neutral of the three legs is used to calculate the neutral sizing. There is no reduced neutral allowed on discharge lighting and non linear loads. A demand factor of 70% shall be permitted to be applied to that portion of the unbalanced load in excess of 200 A.
The neutral wire should be the same size as your conducters
due to unbalance load 1. Due to negetive phase sequence components in current generator and transformers suppling the load will be over heated 2. The opposite torque on the shaft will damage, rotors are more likely to damage. 3. High current through neutral of the system, normally neutral cable conductor is of lesser size then phase and hence it may be damaged.
To determine the appropriate cable size for a 320 kW three-phase system with a current of 444 amps per phase, you must consider factors such as the type of insulation, installation method, and ambient temperature. Generally, for a typical installation using copper conductors, a cable size of 95 mm² would be suitable for this current rating, ensuring it can handle the load with a margin for safety. Additionally, it's crucial to consult local electrical codes and standards, as they may dictate specific requirements for cable sizing and installation practices. Always consider factors like voltage drop and derating due to temperature or bundling when selecting the final cable size.