The motor would draw about 24 kVA which is 35 amps. For this you would need 10 mm2 cable.
you need the current of motor or the KW/HP rating
yes . A change of motor would be required. The motor windings would have to be totally different. three hot leads instead of two. And three phase would have to come from your provider.
Need to know the horsepower of the motor.
If the motor is connected to an ungrounded delta supply service there will be no effect on the operation of the motor. If the motor is connected to a wye system supply service and the B phase grounds out, the motor's overload protection would take the motor off line from the electrical supply.
Assuming it is a 400 V three-phase motor, the phase current is 11 amps, or more if the power factor is less than 1.0 (or the supply voltage is different). If it is a 400 V motor the cable should be capable of carrying 16 amps, so a 2.5 mm-sq 4-core cable is needed.
The motor would draw about 24 kVA which is 35 amps. For this you would need 10 mm2 cable.
We can convert a 3 phase ac motor into generator by changing phase sequence of the ac input cable of that motor
Sir, what is the cable size for 1.5kw 3phase induction motor 400v?
No. That would be a single phase motor.
you need the current of motor or the KW/HP rating
70mm 4core copper cable
The winding design of the motor will not economically allow this to work. You would have to drive a 3 phase generator to supply it.
yes, It would run as long as the motor was not coupled to a load. Coupled to a load the motor would have no torque and would stall.
To use a single/one phase motor instead of a three phase motor is possible if you have a three phase power supply as you will only need to tap one of the three phases together with neutral and an earthwire, however to use a three phase motor instead of a single phase will require the provision of three phase power supply.
yes . A change of motor would be required. The motor windings would have to be totally different. three hot leads instead of two. And three phase would have to come from your provider.
You still need the same horsepower. The advantage of the three-phase motor is that it will draw lower current.
Need to know the horsepower of the motor.