This is not possible because a 120v switch disconnects one conductor while a 240v application requires that both hot conductors be disconnected simultaneously. The proper solution is to use a double pole 240v switch of the correct size. It must have contacts which are rated to carry the appliance's starting and running currents (amps). A switch with under-sized contacts would be likely to get very warm - or even overheat - to such an extent that it might become a dangerous fire hazard. IF YOU ARE NOT ALREADY SURE YOU CAN DO THIS JOB
SAFELY AND COMPETENTLY
REFER THIS WORK TO QUALIFIED PROFESSIONALS.
If you do this work yourself, always turn off the power
at the breaker box/fuse panel BEFORE you attempt to do any work
AND
always use a meter or voltage indicator
to insure the circuit is, in fact, de-energized.
The equation you are looking for is Amps = Watts/Volts. To change kW to watts, multiply kW x 1000.
Pwer is volts times amperes. 120 volts times 10 amperes = 1.2 KW
The wiring regulations in your country must be followed and if you need to ask it means you should employ an electrician to do the work.
Yes water cycle use up earths supply. Water is evaporated from earth's surface.
If the supply is a 20 amp supply it cannot supply a 40 amp stove, you need a bigger supply or a smaller stove.
power supply
32 volts of course. But the real difference is the way the power company has "tapped" their supply step down transformers.
Your neutral May not be grounded good
Yes.
Check the back of the charger, if it says "100-240volts" than yes.
1 d0nt kn0w but have fun
120volt
The equation you are looking for is Amps = Watts/Volts. To change kW to watts, multiply kW x 1000.
yes
Supply voltages are simply 'nominal', or 'named' voltages, and they are allowed to vary in value within statutory limits. In the UK, for example, the nominal supply voltage is 230 V but is allowed to vary within the range +10% to -6%. 240 V is well within this range and, so, yes, there is absolutely nothing wrong with using a 240-V load with a 230- V supply or vice versa.
240Volts in the USA.
Work it out for yourself. The equation is: Z = E/I, where Z is the impedance, E is the supply voltage, and I is the load current.