Yes you can. You did not say how many amps were required.
Answer for USA, Canada and countries running a 60 Hertz supply service.Underground or using triplex, a new ground has to be established at the new distribution's sub panel. It must be in the form of a ground plate or ground rods with the ground wire being connected to the neutral point in the sub panel.
The guy wire forms a right triangle with the pole and the ground. Using the Pythagorean theorem (a^2 + b^2 = c^2), we can calculate the length of the guy wire. In this case, a = 10 ft, b = 15 ft, so the length of the guy wire (c) is √(10^2 + 15^2) = √(100 + 225) = √325 ≈ 18.03 ft.
it is about 100 feet away
This is a voltage drop question and a voltage needs to be stated.
A 400 MCM copper conductor will limit the voltage drop to 3% or less when supplying 100 amps for 700 feet on a 240 volt system. This size will allow the conductor to be loaded to 80 amps. 100 x 80% = 80 amps. Conductors are only allowed to be loaded to 80% or their rated capacity. If you need the full 100 amps then you would need to use a wire with a rating of 125 amps. 125 x 80% = 100 amps. A 600 MCM copper conductor will limit the voltage drop to 3% or less when supplying 125 amps for 700 feet on a 240 volt system.
For a 60 amp sub panel located 100 feet away, it is recommended to use a 6-gauge wire size to ensure proper electrical conductivity and safety.
Answer for USA, Canada and countries running a 60 Hertz supply service.Underground or using triplex, a new ground has to be established at the new distribution's sub panel. It must be in the form of a ground plate or ground rods with the ground wire being connected to the neutral point in the sub panel.
Most people get hung up on the diameter of the earth. The diameter of the earth is actually of no consequence since the question asks for how much longer the wire is as a result of moving it 100 feet away from the surface of the earth. What's critical here is that the radius has increased 100 feet. So the change in radius is 100ft since it moved 100 feet further away from the center of the earth. Base don the simple formula circumference = 2 * pi * radius, the wire 100 feet above the earth is about 628 feet (628 = 3.14 * 2 * 100) longer than the wire on the surface of the earth.
100 feet into the ground
The recommended ground wire size for a 100 amp sub panel installation is typically 8 copper wire.
A 100 foot fish tape and wire lubrication will be needed to make this wire pull.
This is a voltage drop question. A voltage must be stated to answer this question.
For a 100 amp service over a distance of 100 feet, the recommended wire size is typically 2 AWG copper or 1/0 AWG aluminum.
it is about 100 feet away
I'll say about 100 feet away. Or more then 100 to get away from the sun to not get burned.
100 Ft.
a dead centipede