answersLogoWhite

0

Yes you can. You did not say how many amps were required.

User Avatar

Wiki User

10y ago

What else can I help you with?

Continue Learning about Natural Sciences

To run a 200 amp disconnect box from a 200 amp disconnect box about a 100 feet away to run a corn dryer do you have to run a ground wire from the first disconnect box or can you just run triplex?

Answer for USA, Canada and countries running a 60 Hertz supply service.Underground or using triplex, a new ground has to be established at the new distribution's sub panel. It must be in the form of a ground plate or ground rods with the ground wire being connected to the neutral point in the sub panel.


How long is a guy wire that reaches from the top of a 15-ft pole to a point on the ground 10 feet from the bottom of the pole?

The guy wire forms a right triangle with the pole and the ground. Using the Pythagorean theorem (a^2 + b^2 = c^2), we can calculate the length of the guy wire. In this case, a = 10 ft, b = 15 ft, so the length of the guy wire (c) is √(10^2 + 15^2) = √(100 + 225) = √325 ≈ 18.03 ft.


What is the distance from the sun and the moon?

it is about 100 feet away


What gauge wire 800 watts in 100 feet?

This is a voltage drop question and a voltage needs to be stated.


What size wire needed for 100 amp service 700 feet away?

A 400 MCM copper conductor will limit the voltage drop to 3% or less when supplying 100 amps for 700 feet on a 240 volt system. This size will allow the conductor to be loaded to 80 amps. 100 x 80% = 80 amps. Conductors are only allowed to be loaded to 80% or their rated capacity. If you need the full 100 amps then you would need to use a wire with a rating of 125 amps. 125 x 80% = 100 amps. A 600 MCM copper conductor will limit the voltage drop to 3% or less when supplying 125 amps for 700 feet on a 240 volt system.

Related Questions

What is the recommended wire size for a 60 amp sub panel located 100 feet away?

For a 60 amp sub panel located 100 feet away, it is recommended to use a 6-gauge wire size to ensure proper electrical conductivity and safety.


To run a 200 amp disconnect box from a 200 amp disconnect box about a 100 feet away to run a corn dryer do you have to run a ground wire from the first disconnect box or can you just run triplex?

Answer for USA, Canada and countries running a 60 Hertz supply service.Underground or using triplex, a new ground has to be established at the new distribution's sub panel. It must be in the form of a ground plate or ground rods with the ground wire being connected to the neutral point in the sub panel.


Suppose it were possible to string a wire around the earth's equator at a constant 100 feet above the earth How much wire would be needed?

Most people get hung up on the diameter of the earth. The diameter of the earth is actually of no consequence since the question asks for how much longer the wire is as a result of moving it 100 feet away from the surface of the earth. What's critical here is that the radius has increased 100 feet. So the change in radius is 100ft since it moved 100 feet further away from the center of the earth. Base don the simple formula circumference = 2 * pi * radius, the wire 100 feet above the earth is about 628 feet (628 = 3.14 * 2 * 100) longer than the wire on the surface of the earth.


How many feet did the twin towers go into the ground?

100 feet into the ground


What is the recommended ground wire size for a 100 amp sub panel installation?

The recommended ground wire size for a 100 amp sub panel installation is typically 8 copper wire.


How is wire pulled into a conduit of 100 feet?

A 100 foot fish tape and wire lubrication will be needed to make this wire pull.


What size wire for a 200 amp 3phase service 100 feet away?

This is a voltage drop question. A voltage must be stated to answer this question.


What is the recommended wire size for a 100 amp service over a distance of 100 feet?

For a 100 amp service over a distance of 100 feet, the recommended wire size is typically 2 AWG copper or 1/0 AWG aluminum.


What is the from the moon and the sun?

it is about 100 feet away


How far away do you have to be to not get burned by the sun?

I'll say about 100 feet away. Or more then 100 to get away from the sun to not get burned.


Ground vehicle operators will yield the right-of-way to all aircraft and Will remain at least feet away from any helicopter with its rotors in motion?

100 Ft.


What is 100 feet in the air but its back is on the ground?

a dead centipede