Yes. The basic components of the refrigeration system are the refrigerant, compressor, condenser and receiver, expansion device and the evaporator. One cycle: Refrigerant travels to Compressor (A) to Condenser (B) to Expansion device (C) to evaporator (D). The refrigerant gas at low pressure and temperature is drawn into the compressor. The gas is compressed to a higher pressure, which causes an increase in the temperature. The refrigerant gas at a high pressure and temperature passes to the condenser (point B), where it is cooled (the refrigerant gives up its latent heat) and then condenses to a liquid. The high pressure, low temperature liquid is collected in the receiver. The high pressure liquid is routed through an expansion valve (point C), where it undergoes an abrupt reduction in pressure. That pressure reduction causes part of the liquid to immediately vaporize or flash. The vapor and remaining liquid are cooled to the saturation temperature (boiling point) of the liquid at the reduced pressure. At this point most of the refrigerant is a liquid. The boiling point of the liquid is low, due to the low pressure. When the liquid refrigerant enters the evaporator (point D), it absorbs heat from the process and boils. The refrigerant gas is now at low pressure and temperature, and enters the suction side of the compressor, completing the cycle.

User Avatar

Wiki User

17y ago

What else can I help you with?

Continue Learning about Natural Sciences

What is the state of refrigerant in the liquid line?

Refrigerant in the liquid line is in a liquid state. It has condensed from its vapor form into a liquid due to the pressure and temperature conditions in the line. This liquid refrigerant is ready to enter the evaporator coil to absorb heat and undergo the phase change process again.


Should only liquid refrigerant enter the meter device?

Yes, only liquid refrigerant should enter the metering device to ensure optimal performance and efficiency. The metering device is designed to reduce the refrigerant pressure and control its flow into the evaporator, where it absorbs heat. If vapor refrigerant enters the metering device, it can lead to improper cooling, reduced efficiency, and potential damage to the system. Proper refrigerant management is crucial for maintaining the system's reliability and effectiveness.


Does refrigerant enter evaporator as a liquid in a direct expansion evaporator?

It will, in basically all cases be a mixture of liquid and vapor, which means the refrigerant is saturated but with a few bubbles entering the evaporator. In a properly operating system though entering the metering device should be solid liquid and some sub-cooling (sub-cooled means cooler then saturation and therefore= no vapor) but then through the metering device (TXV, cap tube, orifice) some of the liquid will boil off, which is called flash gas, in order to cool the refrigerant down as saturated temperature goes down (the pressure to boiling point relation, as pressure is reduced boiling point is lowed). The amount of flash gas is directly related to the specific heat of the refigernt (BTUs/lb), the number of degrees you are cooling the refrigerant (eg. 95 to 45), and the latent heat of vaporization (BTUs/lb for change of state. liquid to vapor)


What is a T and P valve for electric water heater?

The T and P valve is the temperature and pressure valve that is used on hot water tanks as a safety device. The temperature rating is up to 210 degrees F and a water pressure up to 150 psig. (pound-force per square inch gauge) before the safety valve trips to relieve water and lower the pressure inside the tank. When the safety valve trips it allows cooler water to enter the tank to cool off the hot water that tripped the valve in the first place. The valve is usually located on the outflow of the tank as the temperature probe has to be located within 6 inches from the top of the tank where the water temperature will be the hottest.


How do you reset the temperature and pressure valve for electric water heaters?

The T and P valve is the temperature and pressure valve that is used on hot water tanks as a safety device. The temperature rating is up to 210 degrees F and a water pressure up to 150 psig. (pound force per square inch gauge) before the safety valve trips to relieve water and lower the pressure inside the tank. When the safety valve trips it allows cooler water to enter the tank to cool off the hot water that tripped the valve in the first place. The valve is usually located on the outflow of the tank as the temperature probe has to be located within 6 inches from the top of the tank where the water temperature will be the hottest. The valve is self resetting as soon as the pressure is reduced or the temperature lowers to below the set point of the valve.

Related Questions

What is the state of refrigerant in the liquid line?

Refrigerant in the liquid line is in a liquid state. It has condensed from its vapor form into a liquid due to the pressure and temperature conditions in the line. This liquid refrigerant is ready to enter the evaporator coil to absorb heat and undergo the phase change process again.


What is would happen if liquid refrigerant were to enter the compressor cylinder while it was running?

If liquid refrigerant enters the compressor cylinder while it's running, it can damage the compressor. Liquid refrigerant is not compressible like gas, causing hydraulic lock and putting excessive strain on the compressor motor. This can lead to mechanical failure and decreased efficiency of the refrigeration system.


What side is the charging liquid added to in a compressor?

The charging liquid is typically added to the low-pressure side of a compressor. This allows the liquid to enter the compressor, where it is compressed and then discharged as a high-pressure gas.


What is liquid slugging of the compressor?

Liquid slugging of a compressor occurs when liquid refrigerant enters the compressor cylinders instead of vapor. This can lead to mechanical damage, decreased efficiency, and potential system failure. Measures to prevent liquid slugging include proper system design, control of liquid refrigerant flow, and maintaining proper superheat.


What is meant by restricting liquid refrigerant added to a refrigeration system when charging?

Restricting liquid refrigerant during charging helps prevent the compressor from being flooded with liquid, which could cause damage. It allows the refrigerant to enter the system as a vapor, which is more efficient for the compressor to handle. Properly charging the system with vapor also ensures that the refrigerant circulates effectively throughout the system.


When do you put the freon or refrigerant in 2004 Chrysler intrepid 2.7L?

Freon or refrigerant is put in a 2004 Chrysler Intrepid 2.7L by locating the low pressure inlet near the rear of the engine compartment. A can of refrigerant is then connected to the line and allowed to enter the system until the desired pressure is reached.


What is the discharge line on an air conditioner?

Discharge line is the line in which the refrigerant passes through after being discharged by the compressor. Liquid line is the line located after the condenser, following refrigeration cycle. Suction line is the one that the referigerant is sucked :) in, to enter the compressor.


What three effects does the condenser have on the refrigerant vapor entering the coil?

The condenser helps to condense the refrigerant vapor into a liquid state by removing heat. It also increases the pressure of the refrigerant, preparing it to enter the coil as a high-pressure liquid. Additionally, the condenser helps to release any remaining heat energy from the refrigerant before it enters the coil to complete the cooling process.


Should only liquid refrigerant enter the meter device?

Yes, only liquid refrigerant should enter the metering device to ensure optimal performance and efficiency. The metering device is designed to reduce the refrigerant pressure and control its flow into the evaporator, where it absorbs heat. If vapor refrigerant enters the metering device, it can lead to improper cooling, reduced efficiency, and potential damage to the system. Proper refrigerant management is crucial for maintaining the system's reliability and effectiveness.


Ac high pressure switch on a 97 Ford Taurus?

before you enter compressor it is "t"'d to pipe has 4 harness wires


How does the vapor pressure of a substance change with temperature?

The vapor pressure of a substance increases with temperature. As the temperature rises, more molecules have enough energy to escape from the liquid phase and enter the gas phase, leading to an increase in vapor pressure.


Where is the sensor located to restart the AC compressor on your 1995 Lincoln Town Car it is low on freon and when you try to add a can of R134 the compressor shuts off and will not accept the freon?

I really don't know waht you mean by a sensor to restart the system. There isn't any such thing. The clutch cycling switch is a pressure switch that cuts off the compressor as the pressure on the low-side of the sytem cycles low during normal operation, or when the sytem has a low charge. But this switch is not something you reset. It automatically closes itself, when the system pressure comes up enough to trip it, usually about 20 or 25 pounds of pressure. If you cant it to take a charge, you have another problem. Make sure your cahrhging hose is actually depressing the shrader vavle(looks like a tire valve) in the charging port to allow refrgerant to enter the system. Or you may have a problem with the tool you are using to charge up the system, or you may have a restriction in the system. Also, is charging the system really the issue? Is refrigerant getting in, but the compreesor dosent engage? Could it be that the system has refrigerant, but an electrical problem is causing the compressor to not turn on?