The safest andeasiest way is to get a good ammeter (make sure it is rated for the correct application with at least a CAT IV rating) and then take the hot wire and only the hot wire and put it into the clamp of the ammeter while the wire is under load. Then all you have to do is read the meter.
Note: when using an ammeter you can only test one side of the circuit at once either the hot side or the neutral side not both at once. If you try to put both wires under the clamps at the same time your readings will be wrong. The same goes for a 240v circuit you are only able to read one line at a time.
For a continuous load the circuit breaker is set 25% higher than the load current. So a 20-amp breaker is used with a continuous 16-amp load.
If you consider a tandem breaker as one breaker then the answer is yes. As for adding two separate circuits under one breaker terminal tab then the answer is no. Circuits are designed to have a specific amount of load to be applied to it. This circuit it designed to be connected to a single breaker. Adding two of these designed circuits to a single breaker will double the designed load and will probably cause nuisance tripping of the breaker. It is this scenario that tandem breakers were designed for, as smaller distribution panel become full, as new appliances and their circuits are added to the system.
No, a 2 pole breaker is designed for a 240-volt circuit or for two separate 120-volt circuits that are out of phase with each other. For a 120-volt single-phase circuit, you would typically use a single-pole breaker.
A common type of circuit breaker used in a load center is a miniature circuit breaker (MCB) or a molded case circuit breaker (MCCB). These circuit breakers protect the electrical system from overload and short circuits by interrupting the flow of current when necessary. They come in various sizes and ratings to suit different applications within the load center.
For a circuit with a load of 10 amps, a breaker of 15 amps should be used for adequate protection. It is important to choose a breaker size that is slightly higher than the load to prevent frequent tripping and ensure safety.
The breaker may be tripping with no load due to a short circuit, ground fault, or overheating. These issues can cause the breaker to trip as a safety measure to prevent damage or fire.
A fuse or circuit breaker used in a circuit is usually inserted in series with the load.
A circuit breaker may trip with no load due to a short circuit, ground fault, or overheating. These issues can cause excessive current flow, triggering the circuit breaker to protect the electrical system from damage or fire.
Answer for countries in Europe and other world areas running a 50 Hz supply service.Depending on the load of your lighting circuit. I would measure the current with an inductive amp meter. once you know the current required for your lighting circuit, you then install a circuit breaker which is 15% higher than your load. eg, load is 10A. 10A load + 15 % = 12A breaker (15 A is ok as the breaker is used to protect the wiring and should be rated in consequence of your wiring by 25% less or its current rating, or less, not the load)The humming of your lighting circuit breaker indicates that your breaker is either faulty, or having a difficult time keeping a closed circuit. Or simply that the manufacturer produced a breaker that hums by nature of its construction.
For a continuous load the circuit breaker is set 25% higher than the load current. So a 20-amp breaker is used with a continuous 16-amp load.
The circuit breaker may trip with no load due to a short circuit or a ground fault in the electrical system, which can cause an excessive flow of electricity and trigger the breaker to shut off for safety reasons.
If you consider a tandem breaker as one breaker then the answer is yes. As for adding two separate circuits under one breaker terminal tab then the answer is no. Circuits are designed to have a specific amount of load to be applied to it. This circuit it designed to be connected to a single breaker. Adding two of these designed circuits to a single breaker will double the designed load and will probably cause nuisance tripping of the breaker. It is this scenario that tandem breakers were designed for, as smaller distribution panel become full, as new appliances and their circuits are added to the system.
The maximum current rating for the circuit breaker required for a 125 amp load is 125 amps.
The maximum current rating for the circuit breaker that can handle a load of 40 amps is 40 amps.
A 200 amp circuit breaker can support a maximum electrical load capacity of 200 amps.
The recommended amperage for a circuit breaker to safely handle a 50 amp load is 60 amps.
the circuit breaker used will be miniature circuit breaker(MCB) maily used in homes.Answer for USA, Canada and countries running a 60 Hertz supply service.A two pole circuit breaker is used for a load of 240 volts. It is sized, according to the load amps of the device, to protect the wires that supply the load current.