answersLogoWhite

0

If one phase really is missing, then you have an unbalanced load.

User Avatar

Wiki User

13y ago

What else can I help you with?

Continue Learning about Natural Sciences

How does neutral missing protection work in single phase energy meter?

Neutral missing protection in a single-phase energy meter detects the absence of the neutral wire in the electrical circuit. When the neutral wire is missing, it can result in overvoltage on the load side. The energy meter typically shuts off to prevent damage to the connected equipment in such a situation.


Why is the amperage in single phase double than of 3 phase?

If I have 1 KW In 3 Phase it will give 1.54 A and In single phase it will give 4.6 AFor cosF 0.9V 415 3 phV 240 1 phIt seems the reason is because the current is carried on more wires. Also, remember that if wattage stays constant, then as voltage increases, current decreases.AnswerIt really depends on the load. Are you assumining the three-phase load to be the same as the single-phase load or, as it is likely to be in practice, three times the value of the single-phase load?But, in either case, the single-phase current will not be double the the three-phase (line) current!The equation for the load current supplying a single-phase is: I = P / (E x power factor)The equation for the line current supplying a balanced three-phase system is: IL = P / (1.732 x E x power factor)If you insert real figures into these equations, (240 V for the single-phase voltage and 415 V for the three-phase line voltage) then you will find that, when the three-phase load is threetimes that of the single-phase load, the supply currents will be exactly the same. On the other hand, if you assume that the three-phase load is exactly the same as the single-phase load, then you will find that the three-phase line current will be one-third that of the single-phase current.


Can 3phase source supplies single phase load?

For a three-phase, four-wire, system, single-phase loads can be connected between any pair of line conductors. For a three-phase, four-wire, system, single-phase loads can be connected between any pair of line conductors, or between any line conductor and the neutral conductor. The choice depends on the voltage requirements of the load.


How many wires are used for a 460 volt circuit breaker?

If the load is single phase and the load requires 460 volts to operate, then two conductors will be needed and they will connect to a two pole breaker. If the load is three phase and the load requires 460 volts to operate, then three conductors will be needed and they will connected to a three pole breaker. The sizing of the wires will depend upon the current that is drawn by the loads.


Can 1 phase be used with 3 phase?

If you have a 208Y/120 volt 3 phase system, you can use any one of the three phases (hot or ungrounded conductor) with the neutral for 120 volt load or you can use any two phases of the three phase for a single phase 208 volt load. If you have a 120/240 volt 3 phase system, you can use any two phases of the three phase for a single phase 240 volt load or you can use either the A phase or C phase with the neutral for a 120 volt load. You can not use the B phase with a neutral (you would have 208 Volts!).

Related Questions

How do you balance the unbalanced load in 3 phase?

If the load is connected in wye (star) and it has a neutral, then the vectorial-difference of the phase currents will flow in the neutral and there will be no problem. On the other hand, if there is no neutral, then an unbalanced load would cause unbalanced phase voltages.


How does neutral missing protection work in single phase energy meter?

Neutral missing protection in a single-phase energy meter detects the absence of the neutral wire in the electrical circuit. When the neutral wire is missing, it can result in overvoltage on the load side. The energy meter typically shuts off to prevent damage to the connected equipment in such a situation.


What will happen if 2 phase load is connected to generator?

There is no such thing as a two phase load any more. Any two legs from a three phase system are classed as single phase. If this single phase load is connected across the generator it will induce an imbalance in the output voltages of the generator. This is one reason that single phase loads on a three phase generator should be shifted around to find the best possible balance.


Do you need only a watt-meter in a three phase power?

To measure the power of a three-phase load, you need to use one less wattmeter than there are conductors supplying that load.


What happen when only one phase of three phase generator is fully loaded?

any more load will add to that phase ,over current protection will trip the generator.


What is three-phase unbalanced load?

A balanced three phase load is where the current flowing in all three phases of the load are reasonably close to each other.Another answerWhen the voltage and measured current draw do not deviate by more than 2 percent under load.AnswerA balanced three-phase load is one in which each of the three loads is identical in all respects (magnitude and phase). Further to the first answer, the three line currents must not all be 'reasonably close', they must be identical -i.e. the same value and phase relationship.


How do you meter a 208v load meter only 1 phase add the two?

The voltage 208 is a three phase voltage. Single phase is classed as the voltage obtained from any two legs of the three phase voltage system. The voltage between L1 to L2 = 208. L2 to L3 = 208 volts and L3 to L1 = 208 volts. To measure the load of the 208 volt device just clamp an amp meter around one of the legs coming from the load. This will give you the amperage that the load draws.


Why is the amperage in single phase double than of 3 phase?

If I have 1 KW In 3 Phase it will give 1.54 A and In single phase it will give 4.6 AFor cosF 0.9V 415 3 phV 240 1 phIt seems the reason is because the current is carried on more wires. Also, remember that if wattage stays constant, then as voltage increases, current decreases.AnswerIt really depends on the load. Are you assumining the three-phase load to be the same as the single-phase load or, as it is likely to be in practice, three times the value of the single-phase load?But, in either case, the single-phase current will not be double the the three-phase (line) current!The equation for the load current supplying a single-phase is: I = P / (E x power factor)The equation for the line current supplying a balanced three-phase system is: IL = P / (1.732 x E x power factor)If you insert real figures into these equations, (240 V for the single-phase voltage and 415 V for the three-phase line voltage) then you will find that, when the three-phase load is threetimes that of the single-phase load, the supply currents will be exactly the same. On the other hand, if you assume that the three-phase load is exactly the same as the single-phase load, then you will find that the three-phase line current will be one-third that of the single-phase current.


How do you wire a three phase four wire generator for single phase output?

In a three phase four wire system - voltage between any one phase and the neutral is single phase. Hence the single phase equipment or load between any one phase and the neutral.Another AnswerA single-phase load can be connected either between any line conductor and the neutral conductor, or between any pair of line conductors. The choice is dependent on the voltage rating of the load, which must match either the phase voltage (line-to-neutral) or line voltage (line-to-line) -these values will be indicated on the machine's nameplate.


What are then line and phase voltage for a 415v 50Hz balanced delta connected system which has a load consisting of 100 resistance and 200mH inductance?

If it has one load, it isn't balanced.AnswerThe voltages are determined by the supply, not by the load -so they would remain at 415 V (line voltage) and 240 V (phase voltage) regardless of your load. But, assuming your load specification is per phase, then you have a balanced load and the phase and line currents are easily calculated.The first step is to determine the impedance per phase, which is the vector sum of the resistance and reactance -the reactance can be calculated from the inductance value (63 ohms) -this works out at 118 ohms.Next, we find the phase current, which is the phase voltage (240 V) divided by the phase impedance, 240/118 = 2 A. Finally, we calculate the line current, which is 1.732 times the phase current = 3.5 A.


If an industrial customer of an electrical power company connects a large single phase load to a three phase power line then every user on that power line will have unbalanced power explain why?

A 'balanced' three-phase load, by definition, is one in which the load connected in each phase (either line-to-line or line-to-neutral) is identical in all respects. A single load, clearly, doesn't comply with this definition.


How many feeder you can use for chiller?

One feeder will do the job. The definition of a feeder in the electrical trade is a set of conductors that supply a source to a load. The sizing of the feeders will depend on what the load current is. The wire count of the feeder will be dependant upon whether the load is single phase or three phase.