answersLogoWhite

0

The formula you are looking for is I = W/E.

User Avatar

Wiki User

15y ago

What else can I help you with?

Related Questions

What size wire and breaker for a 240 volt single phase 20 kw electric furnace rated at 83.3 amps?

AWG #3 copper.


What is the Equipment Demand Load for a 12 kW kitchen range line and neutral?

The demand load would be 12 kW. When you talk about line and neutral you are referring to the voltage that the equipment operates on. In North America, an electric kitchen range operates on two voltages 120/240 volts. The 240 volts is obtained across two breakers in the distribution panel and the 120 volts is obtained between either 240 volt leg and the neutral. On a range of this size the 120 volts is usually used for the clock and controls for the range. The range at maximum would draw 50 amps, fed by a two pole 50 amp breaker using a #6 copper conductor with an insulation factor of 90 degrees C. The range will have an internal breaker or fuse to protect the 120 volt circuit.


What size of wire do you need for 5 kw heat strip?

120 15 amp service ? 210 7 amp service ?


What size wire for 10kw 240 volt?

10 mm2 cross section should be sufficient (#6 wire?)


What is breaker size for 62.19 KW 3 phase?

A breaker protects the wire size of the feeder that is connected to it. The amperage of the load must be found. Without a voltage stated the amperage from the wattage given can not be calculated. The equation for amperage when the kw is given is A = kW x 1000/1.73 x volts x pf. The pf constant to use is .9.


How many amps in1 KW for a 240v sistem?

1KW is 1000w. one watt is equals to product of volt and current. current=watt/volt =1000/240 =4.1667 amps


What size wire and breaker for 8 kw heater?

If your power source is 120 V then 8000/120 = 66.7 Amps. If operated at 240 V then it is 33.3 Amps. In the first case you would need 3 AWG and in the second 8 AWG.


How do you calculate the dc circuit breaker rating for a given kw?

the given kw Divide by the your voltage


What breaker size do you use for a 270 Kw power rated equipment and power supply of 380 vac 3 phase?

I=270000/380/1.732 I=410A USE: 500A CIRCUIT BREAKER


What size breaker should be used for a 3.6 kW oven?

3000 / 240 = Amps. You de-rate a breaker by 20 % for continuous load like an oven. You could get by with a 20 Amp breaker and 12 AWG wire. However, I would recommend 30 Amps and 10 AWG for an oven for the long run.


How many watts can 14-2 wire run?

14 AWG wire normally supplies 15 amps. Watts = Volts x Amps x Power Factor. Power Factor has a maximum value of one. If you have a 120 volt circuit that would be 15 x 120 = 1800 watts or 1.8 KW. For a 240 volt circuit 3.6 KW.


What size breaker do you need for 9000W at 440V 3phase?

This formula will give you the amperage I = kw x 1000/1.73 x E x pf (pf = power factor). Take the amperage and multiply it by 125%. This will give you the breaker size that you need.