i have 200 hp motor what i need cable size in 100 feet distance
For a 240-volt single-phase induction motor, a two-pole motor starter is typically required, as it connects to the two live conductors of the single-phase supply. For a 440-volt three-phase induction motor, a three-pole motor starter is needed, as it connects to the three phases of the three-phase supply.
The formula you are looking for is Amps = kW x 1000/1.73 x E x pf. Use .84 for a power factor value.
The equation that you are looking for is Amps = Watts/Volts. There are 6000 watts in 6kW.
It is not recommended to supply a 240 volt single phase motor with only one phase until the other phase is closed. This can cause imbalanced current flow, leading to motor overheating and potential damage. It is best to provide both phases simultaneously to ensure proper operation of the motor.
Assuming the power factor is 1, a 10 hp motor operating at 600 volts in a three-phase system would draw approximately 13.33 amps.
A single phase 10 HP motor will draw aproximately 50 amps. A three phase 10 HP motor will draw aproximately 28 amps.
read the name plate on the motor
20 HP Three phase 360 volt what is the amps
The electrical code states that a 7.5 HP 460 volt three phase motor draws 11 amps. For fuse sizes, non time delay - 30 amps, time delay type D - 20 amps and if using a breaker it will be 30 amps. Minimum wire size is #12 and the maximum setting of overload devices will be 13.75 amps
88 amps
The electrical code book states that a 40 HP 230 volt three phase motor draws 104 amps. For that motor the wire must be rated for 131 amps, Non time delay fuses at 300 amps, time delay fuses at 175 amps or a 250 amp circuit breaker. When calculating wire sizes and motor protection the motor's full load amperage should be taken from the motor's nameplate.
a 3 phase 415 volts 50 HZ 15 HP motor draws: 1. On no load 3.6 amp after a starting kick of around 18AMP 2. On a full load : a starting kick of 108 amp for few seconds and then18.3 amp. 3. On rated load(this means the motor is selected such that the load is 80% of the motor capacity) 14.64 amp with a starting kick of 88Amp.
The wiring should allow for 115 amps.
Then you are trying to get more HP out of the motor that it can supply. Back off on the load that the motor is driving or put a bigger motor onto the load.
For a 240-volt single-phase induction motor, a two-pole motor starter is typically required, as it connects to the two live conductors of the single-phase supply. For a 440-volt three-phase induction motor, a three-pole motor starter is needed, as it connects to the three phases of the three-phase supply.
62.5 amps
Yes, but the motor's horsepower rating will not be reached.