In Pakistan, Transformers are commonly used to step down high transmission voltages, such as 11,000 volts, to lower distribution voltages appropriate for consumer use. The voltage reduction is determined by the turns ratio of the transformer, which is designed to provide a specific output voltage. For instance, a transformer with a turns ratio that steps down 11,000 volts to 415 volts is typically designed for three-phase systems, where 415 volts is the standard voltage for industrial and commercial applications. This process allows for safe and efficient power distribution to end-users.
11000
That type of transformer normally has about 99% efficiency so the full-load loss would be 1% or 6 kW.
To connect a 1000 kVA electric generator to a 1000 kVA transformer for stepping up to 11,000 volts, first ensure that the generator's output voltage matches the transformer's primary voltage rating. Connect the generator's output terminals to the primary side of the transformer, ensuring proper phase alignment. The secondary side of the transformer will then output the stepped-up voltage of 11,000 volts. It's crucial to follow safety protocols and check all connections for compliance with electrical standards.
The standard three-phase distribution transformer in the UK is a delta/star connection with a rated primary line voltage of 11 kV, and a nominal secondary line voltage of 400 V, giving a secondary phase voltage of 230 V.So, the secondary provides a three-phase, four-wire, system comprising three line conductors and a neutral conductor. The line-to-line (line voltage) voltage is 400 V and the line-to-neutral (phase voltage) voltage is 230 V.There are not 'three types' of supply obtained from this arrangement.
since at no load only excitation current(responsible for core loss ie iron loss) flow on the primary side so core loss current will be 1A and core loss = v1*i1*powerfactor. core loss = 1*11000*0.24= 2640watt.
Impedance (Z) voltage is the amount of voltage applied to the primary side to produce full load current in the secondary side. It is usually listed on the transformer nameplate, expressed as a percent, and measured by conducting a short circuit test.
Only Pakistan International Airlines operates from Multan to Karachi. Air fare varies from time to time. Average air fare from Karachi to Multan is 11000 Pakistani Rupees.
You really do need to use the correct symbols for electrical units! '2mva' indicates that you are describing '2 millivolt amperes', whereas I think you intend to mean 'megavolt amperes'? In which case the correct symbol is MV.A! (m = milli, M = mega) Note that the volt and ampere symbols are also capitalised.You can determine the primary current by dividing the MV.A rating of the transformer by its primary voltage rating:Ip = (2 x 106) / (11 x 103) = 182 A
12 percent of 11000 = 132012% of 11000= 12% * 11000= 0.12 * 11000= 1320
4 percent of 11000 dollars = $440 4% of $11000 = 4% * $11000 = 4%/100% * $11000 = 0.04 * $11000 = $440
11000
11000