If a step-up transformer has 200 turns on the primary coil and 3000 turns on the secondary coil, with a primary coil voltage of 90 volts and current of 30 amps, then the turns ratio is 200:3000, so the secondary voltage is 1350 voltage and the available current is 2 amps. (This ignores losses through the transformer.)
It depends on the design objectives of the transformer.
Assuming a lossless transformer, it will be 300 times the secondary current, or 1500A.
150 amperes
When the secondary of a transformer is opened, there is no longer any load on the transformer. There will be some current flowing in the primary winding, which is needed to induce the voltage in the secondary. This primary current is referred to as the "no load" current, and is indicative of the core losses in the transformer.
The current flowing in the primary generates a magnetic field which induces a current in the secondary winding.AnswerNo current is induced into the secondary winding of a transformer. What is induced is voltage. Current will only flow in the secondary winding if it is connected to the load, and it is the load that determines the current, not the primary current.
The primary current of a transformer depends upon the secondary current which, in turn, depends upon the load supplied by the transformer. There is not enough information in the question to determine the rated primary and secondary currents of the transformer.
If the number of turns in the primary is the same as the secondary, this would be an isolation transformer. Primary and secondary voltages should match (minus the inherent transformer losses), as should the current.
If I am not wrong then you have asked about a transformer. And its a current transformer. By theory of voltage transformer we know that Vs/Vp = Ns/Np So for answering your question we need the value of number of turns in primary and secondary coil. But you can use this equation to find your answer if you have other values. By using ohmic law you can convert voltage to current.
When the secondary of a transformer is opened, there is no longer any load on the transformer. There will be some current flowing in the primary winding, which is needed to induce the voltage in the secondary. This primary current is referred to as the "no load" current, and is indicative of the core losses in the transformer.
The current flowing in the primary generates a magnetic field which induces a current in the secondary winding.AnswerNo current is induced into the secondary winding of a transformer. What is induced is voltage. Current will only flow in the secondary winding if it is connected to the load, and it is the load that determines the current, not the primary current.
150 amperesAnswerYour transformer's primary current will be:Is = Ip (Ns/Np) = 5 (90 000/300) = 5 x 300 = 1500 A
A current transformer doesn't 'measure current'. It merely reduces a large current flowing through its primary to a smaller current which can be read by an ammeter connected to its secondary. At the same time, it electrically isolates the secondary circuit from the primary circuit, which is essential if the primary circuit is part of a high-voltage system.
The current in the secondary winding of a transformer is not determined by the current flowing in the primary winding; rather, it is the other way around.The current flowing through the secondary winding of a transformer is determined by the load to which it is connected. The primary current can then be determined from the turns ratio.
You never ever ever ever under any condition open the secondary when primary current is flowing.
1500A. You probably have pri / secondary confused. primary is usually used to denote the higher voltage winding, which will have more turns than the secondary. The secondary will have lower voltage, less turns, but will carry more current.
The primary current is determined by the secondary current, not the other way around. For example, a step up transformer will step up the primary voltage in proportion to the turns ratio of the transformer. Any secondary current is then determined by the secondary voltage and the load, NOT by the primary current. The primary current is then determined by the secondary current in proportion to the reciprocal of the turns ratio.
The basic principle of current transformer is same as that of the power transformer. Like the power transformer current transformer also contains a primary and a secondary winding. Whenever an alternating current flows through the primary winding alternating magnetic flux is produced, which then induces alternating current in the secondary winding. In case of current transformers the load impedance or "burden" is very small. Therefore the current transformer operates under short circuit conditions. Also the current in the secondary winding does not depend load impedance but depends on the current flowing in the primary winding.
There is no disadvantage with a current transformer -it does exactly what it's supposed to do, that is:reduce the current flowing in the primary circuit to a value that can be handled by its burden (ammeter or protective relay).electrically-isolate its secondary circuit from the primary circuit.
To limit the current flowing through the primary circuit.
It depends on the turns ratio between the primary and the secondary. If the ratio were 10:1, a step-down transformer, for instance, the current in the secondary would be about 50A. If it were 1:10, a step-up transformer, however, the current in the secondary would be about 0.5A.AnswerThe primary current doesn't determine the secondary current. The secondary current is entirely-dependent on the secondary voltage and the impedance of the load. It is this secondary current that the determines the primary current. So you should be asking, "What value of secondary current would result in a primary current of 5.0 A?"