Corona Fields arround a transmission line is the high electric field caused by the transmission line causing the surrounding air to ionise and conduct electricity. As this ionisation requires a current to maintain, this causes a loss associated with the corona.
It is very effectively descirbe in the contagion movie. Actually it shows how it spread and danger of it. I saw a video of this movie and real situation compared video. i share it with this .
youtubecom/watch?v=UmUykwjg6ic&t=3s
Line current = 10MW / 500kV = 20A Assuming the 1000 ohms is the resistance of the entire transmission line, end to end. Power loss = line current ^ 2 * line resistance = 20A ^ 2 * 1000 ohms = 400 KW
Line loss equations are complicated by transmission environment and temperature?Transmission env. - Include wire type, bus impedance in switching fields, etc.Temperature - Temperature can change the wire resistance and thus line loss.Electric energy is transported across the countryside with high-voltage lines because the line losses are much smaller than with low-voltage lines.All wires currently used have some resistance (the development of high-temperature superconductors will probably change this some day). Let's call the total resistance of the transmission line leading from a power station to your local substation R. Let's also say the local community demands a power P=IV from that substation. This means the current drawn by the substation is I=P/V and the higher the transmission line voltage, the smaller the current. The line loss is given by Ploss=I²R, or, substituting for I,Ploss = P²R/V²Since P is fixed by community demand, and R is as small as you can make it (using big fat copper cable, for example), line loss decreases strongly with increasing voltage. The reason is simply that you want the smallest amount of current that you can use to deliver the power P. Another important note: the loss fractionPloss/P = PR/V²increases with increasing load P: power transmission is less efficient at times of higher demand. Again, this is because power is proportional to current but line loss is proportional to current squared. Line loss can be quite large over long distances, up to 30% or so. By the way, line loss power goes into heating the transmission line cable which, per meter length, isn't very much heat.
Energy loss is I^2*R losses. Calculate the transmission line resistance, and multiply by the current squared per unit time (seconds if in watt/seconds, for example).
Power = voltage times current, and the power loss is the loss in the line, I^2 * R. At 11,000 volts, the current will be (11,000 / 415 = ) 3.77% of what it is at 415 volts. So the power loss in the line at 11,000 volts will be (3.77% ^2 = ) .14% of what it is at 415 volts.
From the Generator station, the voltage is sent to a step up transformer. Transmission at higher voltages is used to over come line loss over the miles of transmission.
A: Transmission lines while there is ceramic insulators providing separation to the phases will have a corona if the insulators are dirty providing small current leakage ionizing the air around it therefore corona effect.
Line current = 10MW / 500kV = 20A Assuming the 1000 ohms is the resistance of the entire transmission line, end to end. Power loss = line current ^ 2 * line resistance = 20A ^ 2 * 1000 ohms = 400 KW
Actually surge impedance is present in a transmission line due to the capacitance of transmission line. Now this capacitor attends the reactive power of the transmission line to energise its magnetic flux. now due to the flux the impedance will increase and the power is reactive too. due to the impedance loss is more.
Transmission line efficiency is power at the recieving-end of the line compared to the power at the sending-end of the line and is expressed as a percentage, so this can be formulated. % efficiency = load power (output) / source power (input) x 100 In the line, there are power losses. to calculate this we use the formula: power loss = 3.I2.R where I is current and R is resistance. Now that we have the losses, we know the difference between the input and the output. So, for example, if one had the output value known, then to get the input we just add the loss to the output or if had the input known, just subtract the loss from it to get the output. hope that helps
frequency is directly propotional to corona loss... so higher the freq the corona also high..
there are some distortion in transmission line : copper loss,dielectric loss,skin effect
The Insertion Loss of a line is the ratio of the power received at the end of the line to the power transmitted into the line.
The term, 'power loss', describes the rate of energy losses caused by the load current in the transmission lines
Reactance certainly causes loss in a transmission system, but I^2R or resistance losses are greater.
Line loss equations are complicated by transmission environment and temperature?Transmission env. - Include wire type, bus impedance in switching fields, etc.Temperature - Temperature can change the wire resistance and thus line loss.Electric energy is transported across the countryside with high-voltage lines because the line losses are much smaller than with low-voltage lines.All wires currently used have some resistance (the development of high-temperature superconductors will probably change this some day). Let's call the total resistance of the transmission line leading from a power station to your local substation R. Let's also say the local community demands a power P=IV from that substation. This means the current drawn by the substation is I=P/V and the higher the transmission line voltage, the smaller the current. The line loss is given by Ploss=I²R, or, substituting for I,Ploss = P²R/V²Since P is fixed by community demand, and R is as small as you can make it (using big fat copper cable, for example), line loss decreases strongly with increasing voltage. The reason is simply that you want the smallest amount of current that you can use to deliver the power P. Another important note: the loss fractionPloss/P = PR/V²increases with increasing load P: power transmission is less efficient at times of higher demand. Again, this is because power is proportional to current but line loss is proportional to current squared. Line loss can be quite large over long distances, up to 30% or so. By the way, line loss power goes into heating the transmission line cable which, per meter length, isn't very much heat.
Energy loss is I^2*R losses. Calculate the transmission line resistance, and multiply by the current squared per unit time (seconds if in watt/seconds, for example).
Power loss.