answersLogoWhite

0


Best Answer

Probably not, in the case of a three-phase transformer as it has been pre-connected, enclosed in a metal tank, fitted with the appropriate bushings, etc.. However, it is a relatively straightforward job in the case of a three-phase transformer bank that comprises three separate, single-phase, Transformers.

Whether you'll obtain your desired secondary voltage is another matter.

User Avatar

Wiki User

11y ago
This answer is:
User Avatar

Add your answer:

Earn +20 pts
Q: Can you connect 480 volt 3 phase WYE POWER to a 3 phase 480 volt delta primary transformer?
Write your answer...
Submit
Still have questions?
magnify glass
imp
Related questions

How do you connect an earthing transformer with delta connected secondary?

You have to connect each phase (R,Y & B respectively) of earthing transformer zig zag winding to each phase of power transformer delta secondary respectively. Then the zig zag winding of earthing transformer star point to be earthed.


What is phase shift in three phase transformer?

The phase shift in three-phase transformer from winding of Transformer and determine by vectorgroup of transformer such as YNd1 High voltage connect to wye Low Voltage connect to delta so L.V. lag H.V 30 degree.Answer'Phase shift' or, more accurately, 'angular displacement', is the angle between the secondary line voltages and primary line voltages of a three-phase transformer.


Why vector group is required?

There are various ways in which you can connect a three-phase transformer's primary and secondary windings, or in which you can connect three single-phase transformers to create a three-phase transformer bank. For example: wye-wye, wye-delta, delta-delta, delta-wye, etc.For each connection, there is a natural phase shift between the primary and secondary line voltages. This is called the angular displacement (or 'phase displacement') of the transformer connection.If you wish to parallel two three-phase transformers, or two three-phase transformer banks, then their angular displacements must be the same (there are also other requirements not relevant to this answer).A vector group is a method of specifying a three-phase transformer (or transformer bank) method of connection and its angular displacement. Transformer connections from the same group can be paralleled. Those in different groups cannot


Is 3 phase star transformer has more winding than delta?

The # of windings in a transformer are based on the primary and secondary voltages the transformer is rated for not the way the windings are connected.


Can you hook up a delta to delta transformer to be a delta to wye transformer?

The open Delta or V-Connection transformer is an improvement of the 1 three-phase transformer. The open Delta transformer can restore power in a Delta-Delta three-phase bank when one of the three single-phase transformers, which can be individually disconnected and replaced in case of failure, breaks down. The open Delta transformer then allows functionality to be restored, but at a reduced power of 57.7 of the original power.


What is the voltage phase shift between primary and secondary line voltages in star-delta transformer connection?

The voltage phase shift between primary and secondary connections in a transformer is 180 electrical degrees.


How do you connect 480 vac three phase power to a 480 vac single phase transformer?

If the primary and the secondary windings of the three phase transformer are connected in delta, you cannot get a healthy neutral from it but why bother? You simply drive a rod into earth and use it as a neutral. Alternatively either the primary or the secondary windings must be connected as star and you use the common point as neutral.


Why doesn't the primary winding on a transformer have a neutral?

In a three phase transformer, the primary winding is often configured in a Delta. The delta winding configuration does not use a neutral. The secondary winding is often in a Wye configuration, which does have a neutral. The Delta configuration is typically used for transmitting power to various locations, and thee phase loads where a neutral is not needed. The Wye configuration is typically used to distribute power in a facility where there are single phase loads that need a neutral. There are other reasons to use either Wye or Delta, such as grounding issues, but I think the short answer is probably what you're looking for (I hope). Hope this helps! Dave


If one transformer of a delta transformer bank fails the bank can be reconnected open delta and operate at reduced efficiency?

yes open all fuses close the primary neutral tap,remove secondary leads off of bad traansformer,tell customer to reduce his load until bad transformer can be replced.


What is the function of a grounding transformer in a dc electric locomotive and what would make it heat up?

A grounding transformer provides a place to connect the distribution system ground where a delta system provides the AC supply.


How tertiary winding of power transformer acts as stabilizing winding?

in star-star neutral transformer at unbalanced load condition zerosequnce current will be flows in secondary side but this current can not be balanced by primary side because its not having neutral to circulate zerosequence current.due to this unbalance voltage will appeared in primary side but the tertiary delta winding allows circulate the zerosequence current so the primary voltage will get stabilized.


How do you find angular displacement of transformer?

Angular displacement (sometimes called phase displacement) applies to three-phase transformers, whether a single three-phase transformer, or three single-phase transformers connected as three phase transformer bank. It is, to a three-phase transformer what additive/subtractive polarities are to a single-phase transformer.Angular displacement is one of a number of conditions that must be the same before two three-phase transformers (or transformer banks) are paralleled.'Angular displacement' is the angle by which the secondary line-to-line voltage lags the primary line-to-line voltage.Angular displacements for common connections are as follows:delta/delta transformers have an angular displacement of 0o or 180owye/wye transformers have an angular displacement of 0o or 180odelta/wye transformers have an angular displacement of 30o or 210owye/delta transformers have an angular displacement of 30o or 210oSo, for example, it is impossible to parallel a delta/delta or wye/wye transformer with a delta/wye or wye/delta transformer, as their angular displacements are different.Determining the angular displacement of a particular transformer configuration (wye-delta, etc.) can be done by drawing the phasor diagram for the complete transformer as follows:draw the primary phase voltagesdraw the primary line voltagesdraw the secondary phase voltagesdraw the secondary line voltagesmeasure the (angular displacement) between a secondary line voltage and its corresponding primary line voltage