The 230v breaker is 2-pole,

The 115v is only single-pole so YES you need a new breaker. DON'T use 2 single-pole breakers instead.

The well pump will run to the pressure setting of the pressure switch controlling it, regardless of HP. The difference might be in the size of the pump in flow rating, I.E. a 1/2 HP pump rated at 10gpm @ 70 psi won't perform the same as a 3/4 HP pump rated at 20 gpm @ 50 psi. Check the pump curve and pressure switch setting.

The pressure switch for the new pump will need both power leads connected to the switch (1 lead per contact set), not 1 wire as the 115v motor was.

User Avatar

Wiki User

14y ago
This answer is:
User Avatar

Add your answer:

Earn +20 pts
Q: Do i need to switch circuit breaker since i went from 115V well pump to 230V well pump it is also a higher HP pump but pressure is lower than before?
Write your answer...
Submit
Still have questions?
magnify glass
imp
Continue Learning about Electrical Engineering

What is the higher voltage at the electrode before the arc is struck called what is it's advantages to welding?

Open circuit voltage is the voltage at the electrode before striking an arc (with no current being drawn). The higher the open circuit voltage, the easier it is to strike an arc because of the initial higher voltage pressure.


What causes electrical overloads?

Electrical overloads are caused by the load amperage increasing above what it should normally be. On a motor load this could be a request for the motor to do more work than the motor is capable of, working outside of its HP rating. In a house circuit an overload is created by plugging more devices into the circuit than the circuit breaker can handle. Again the load current will be higher than the circuit will allow and the circuit will open by the tripping of the breaker.


Why would plugging in an Air Conditioning unit in a wall receptacle blow a fuse?

The fuse (or circuit breaker) rating has been exceeded. I'm assuming you do NOT have the AC unit connected to a dedicated circuit. Lets say you have a 15 amp circuit breaker and the AC unit draws 12 amps and other items on the same circuit draw an additional 5 amps. The total amp draw of 17 amps exceeds the circuit design capacity; so the breaker trips to prevent an electrical fire. If you have old style fuses, NEVER EVER replace a fuse with a higher rated one! I'm sure you'd have problems with your homeowners insurance paying out when your house burns down. Have an electrician run a new dedicated circuit for the AC unit and you should be good to go.


How does a circuit breaker protect you?

A circuit breaker limits the amps that a circuit can carry. If the amperage draw on a circuit exceeds that limit, the circuit breaker turns off the circuit. If the current through a wire exceeds the rated amperage, the wire will overheat and eventually cause a fire, or at a minimum, destroy the wire behind inside the wall. Obviously, people don't want a house fire caused by an electrical overload, so circuit breakers are used to prevent damage and potential loss of life.


Is a 60 amp breaker correct for a 10 kw 220 heat strip?

10 kW at 220v will use 45.45 Amps. I'd recommend a 60A circuit, with a 60A breaker, but the heater or electric furnace should have "maximum fuse amps" rated on its nameplate. Above all, neverconnect wiring to a breaker that is rated higher than the maximum current capacity of the wire. In the case of 60A, use #6 AWG wire.The HVAC Veteran

Related questions

Will a circuit breaker give off less amperage?

A circuit breaker does not give off amperage. A circuit breaker allows a flow of current up to the rating of the breaker. Any current higher than that of the breaker's rating will open the breaker's contacts and stop the flow of current.


High voltage will trip a circuit breaker?

A higher voltage means that a higher current will flow in the same load. It is the current that causes the breaker to trip.


What is a difference between 10KA and 22KA circuit breakers?

The previous answer is incorrect, and I would advise that user to not give out information if they are going to give completely misguided information. The interrupting rating of a breaker is the maximum current that the breaker is designed to handle, at the breaker's rated voltage, before damage will occur to the breaker. A breaker will trip at FAR LESS than the interrupting rating, but it is extremely dangerous to expose the breaker to any situation where it will have more than the rated interruption current. the breaker is designed for. The reason some breakers are rated at 22kA instead of 10kA is because they typically have far larger conductors hooked up to them, so with the lowered impedance on the circuit there is more of a chance for the breaker to experience a higher fault current at the breaker. So electricians install 22kA breakers to handle the higher "available fault current."


Do air conditioners need there own circuit breaker?

Yes. Due to their higher current requirements it is recommended that air conditioners be connected to their own dedicated circuit and thus have their own circuit breaker.


How does a circuit breaker operate?

A circuit breaker can be magnetic; the higher the current is the stronger the magnetic field will be, if the magnetic field gets strong enough it will pull open the circuit. A circuit breaker can also be thermal; as current travels through the circuit heat is generated (higher current = more heat), in the breaker there is two different kinds of metal bonded together, each will expand and contract at different rates, since they are bonded together they will bend and trip the circuit open. A circuit breaker can be a combination of magnetic and thermal.


Is it possible that a circuit breaker can explode?

The definition of the word explosion is, a rapid expansion of gases. It may occur from physical or mechanical change. As there in no gases involved in a common circuit breaker the answer has to be a definite no. If a circuit breaker short circuits internally across the line the only thing that will happen is the safety protection up stream from the breaker will trip and take the faulted breaker off line.


How does a solid state circuit breaker works?

Recently a new technology "solid state' are applied to traditional circuit breaker. This technology has resulted in freeing circuit breaker from arcing and switch bounce, also offering higher reliability and longer lifetimes and a faster switching time.


What causes circuit breaker to trip even when it's properly rated?

A circuit breaker is dual function. The only time it will trip is if it senses a fault current that is rated higher than the breaker rating (short circuit). The other trip condition is if the circuit is overloaded and is drawing a current higher than the breaker rating. On breakers that protect motor feeders the breaker has to be rated 250% higher than the motors full load amperage. If the breaker has lots of use and is used for a switch being manually turned off and on will weaken the trip value of the breaker. If you have access to, or know an electrician, a clamp on amp meter on the conductor that the breaker feeds will tell you what is happening. Clamp the line and turn on the load to see exactly what the current is. If, like you say, the breaker is properly rated and the current is within the breaker limits then change out the breaker for a new one.


Why would a higher amp breaker trip before a lower amp breaker?

Need more information. It doesn't seem rationale that they are protecting the same circuit unless you are substituting one for the other for a test. A unit like an air conditioner may have multiple breakers and a higher value breaker may trip because the load it is connected to is drawing current in excess of the rating of breaker.


What is the standard to select circuit breaker?

Add up your amps to calculate your breaker size. Add up your loads (amps), divide by 0.8, and choose that size breaker. If that number does not correspond to a standard size breaker you go to the next higher standard size breaker.


What is the capacity in amperes 20 amp circuit breaker supplying a continuous load?

For a continuous load the circuit breaker is set 25% higher than the load current. So a 20-amp breaker is used with a continuous 16-amp load.


What is the higher voltage at the electrode before the arc is struck called what is it's advantages to welding?

Open circuit voltage is the voltage at the electrode before striking an arc (with no current being drawn). The higher the open circuit voltage, the easier it is to strike an arc because of the initial higher voltage pressure.