A circuit breaker is dual function. The only time it will trip is if it senses a fault current that is rated higher than the breaker rating (short circuit). The other trip condition is if the circuit is overloaded and is drawing a current higher than the breaker rating. On breakers that protect motor feeders the breaker has to be rated 250% higher than the motors full load amperage. If the breaker has lots of use and is used for a switch being manually turned off and on will weaken the trip value of the breaker.
If you have access to, or know an electrician, a clamp on amp meter on the conductor that the breaker feeds will tell you what is happening. Clamp the line and turn on the load to see exactly what the current is. If, like you say, the breaker is properly rated and the current is within the breaker limits then change out the breaker for a new one.
Joey Breaker - 1993 is rated/received certificates of: USA:R
The 80% ideal is from the NEC. Let's say you have a standard 15A circuit. This circuit is rated to carry a maximum of 15A, no more. If you try to draw more than 15A, the breaker will pop. Now, you can put 15A worth of appliances on this circuit, but then you are running it at its maximum all the time. If you add anything else to this circuit, you will pop the breaker. If you have something that draws surge current, it can opo the breaker under normal use. You have no "wiggle room" when you load it at its maximum. Also, as touched on above, if you run your circuit at the maximum you cannot add anything else. This is generally a sign that you need to upgrade your wiring. Furthermore, the breaker can handle 15A indefinitly under standard test conditions, which are close to ideal. Your breaker box may not be ideal. Breakers are thermal devices, so self heating and heating from other breakers can be a problem. If your breaker is hot, it will pop sooner than if it is cold. The more current that flows through it, the hotter it will get. If you are overloading circuits the easiest thing to do is to break the circuit up into multiple circuits. The exact implementation will depend on the situation.
Short circuit ratio is the ratio of field current required for the rated voltage at open circuit to the field current required for the rated armature current at short circuit
The number that is on a breaker is the amount of amperage that the breaker can deliver before it trips. This is the same regardless of how many poles the breaker is.
60898 is an IEC standard; there are two parts. 1 is for AC, 2 is for DC. IEC 60898-1 "applies to a.c. air-break circuit-breakers for operation at 50 Hz or 60 Hz, having a rated voltage not exceeding 440 V (between phases), a rated current not exceeding 125 A and a rated short-circuit capacity not exceeding 25000 A." IEC 60898-2 "gives additional requirements for single- and two-pole circuit-breakers suitable for operation with direct current, having a rated d.c. voltage not exceeding 220 V for single-pole and 440 V for two-pole circuit-breakers, a rated current not exceeding 125 A and a rated d.c. short-circuit capacity not exceeding 10000 A. This Part 2 is to be used in conjunction with IEC 60898-1." (quotes taken from IEC abstracts)
You need a breaker rated for 10 amps and 250 volts. The breaker must also fit properly in your panel.
You don't calculate the rated kV.A of a circuit breaker; it's determined by the manufacturer. It's important that a circuit breaker's rated kV.A exceeds the fault level kV.A at the point where the circuit breaker is located, otherwise it may fail to interrupt a fault current and, possibly, self destruct.
Typically yes because that is what makes sense. However, the subpanel could have the same size breaker as long as the panel were rated for that amperage and the wire sizes were appropriate.
Not if it's functioning properly. The purpose of a circuit breaker is to shut off power if the circuit exceeds the rated power capacity of the wires. Don't plan to exceed the 30 Amp capacity of your house wiring; the results will be destructive.
A 15 amp circuit breaker will handle this situation very well. The smallest home breaker is rated at 15 amp.
Tripping is caused by excessive current, which is usually the result of a fault in cable or equipment. The circuit breaker is there for safety and it trips to prevent a possible fire starting.
Hard to define... A four year old child has the strength to physically "make" a typical household circuit breaker, while a teen would be able to "make" a typical industrial circuit breaker. (The latter breaker being physically much larger than the former.) Circuit breakers have their "breaking capacity" rated in AMPS. A typical household breaker is rated at 20, 30 or 50 Amps. Industrial breakers might be rated at 500 amps or a thousand or even more. Hope this helps but if it didn't answer your question, please rephrase it and ask again.
Quite simply, so you don't put too much current on the wires than they can handle. They also provide protection from 'ground faults', which is when the 'hot' and neutral wires touch. This causes a spike of current (because the resistance drops to near zero) and the breaker senses that too, or it should when it functions properly.
Branch circuits are protected by the circuit breaker found in the electrical panel. Each circuit should have its one breaker. The breaker should be rated to protect the insulation of the wire, so you can determine the breaker size based on the circuit conductor size Example #14-2 should be protected by a 15 amp breaker
A circuit breaker is an overcurrent protection device. As well as being able to open and close a circuit supplying its rated load, a circuit breaker must also be capable of interrupting and closing onto an overcurrent, including a short-circuit fault, without damaging itself.
The previous answer is incorrect, and I would advise that user to not give out information if they are going to give completely misguided information. The interrupting rating of a breaker is the maximum current that the breaker is designed to handle, at the breaker's rated voltage, before damage will occur to the breaker. A breaker will trip at FAR LESS than the interrupting rating, but it is extremely dangerous to expose the breaker to any situation where it will have more than the rated interruption current. the breaker is designed for. The reason some breakers are rated at 22kA instead of 10kA is because they typically have far larger conductors hooked up to them, so with the lowered impedance on the circuit there is more of a chance for the breaker to experience a higher fault current at the breaker. So electricians install 22kA breakers to handle the higher "available fault current."
Yes. But,circuit breaker are usually rated in terms of current they can interrupt,not the voltage.