Want this question answered?
Neutral current is the vector sum of the phase currents. You should be able to add up the phase currents from their polar quantities.
You can't have a three phase earth fault, you can have a phase to phase or a phase to earth fault. If you want the potential phase to earth fault current it will be your voltage times your impedance. If you want the phase to phase potential fault current then you should just double the above result.
A 7.5 kW three phase load will be balanced by the manufacturer. When connected to a three phase source the line current on each phase will be equal.
380V ÷ √3 = 219.4
In a balanced 3-phase system, if the three loads are star connected, the line current is equal to the load current. If the loads are delta connected, the line current is less than the load current by a factor of 1/sqrt(3).
Current is always flowing in the phase due to the continuous voltage application. the current in phase can be used when it is given a - ve terminal or earth the current would complete the circuit.
power=work/time=fd/t=watt This is how you would figure out your power or wattage. i hope i could be of help to you!
Add them upAnswerThere is no 'total' current in a three-phase system. The current flowing in each line (not 'phase') is considered separately. And you most definitely don't 'add them up'!
You will need to determine the power per phase, and add them up to give the total power of the three-phase load. To do this, you will need to multiply the phase-voltage by the phase current by the power factor -for each phase.
You check on the ends of the immersion heater elements. The wattage will be stamped on it. The other thing you can do is look at the instruction manual and find the specs. for the tank. Watts = amps x volts. Amps = Watts/240 volts.
Neutral current is the vector sum of the phase currents. You should be able to add up the phase currents from their polar quantities.
4/4+4*4=20 is it correct by any means or not ? No this garbage has got nothing to do with negative phase sequence current in 3 phase electrical systems.
You can't have a three phase earth fault, you can have a phase to phase or a phase to earth fault. If you want the potential phase to earth fault current it will be your voltage times your impedance. If you want the phase to phase potential fault current then you should just double the above result.
Measuring the current in each phase (or do you mean 'line'?) will not give you sufficient information to work out what you are asking for.
DC Current divided by 1.225
By knowing the voltage you could use calculate the wattage. Power equals volts times amps. Divide by 1000 to get kilowatts.
You can't. Measure the amperes simply tells you what the current is.