Contact your power provider or power company. 3 phase sometimes is not available in certain areas (mostly rural). They have to run extra wires from the power pole or grid to your place where you want 3 phase.
Answer for USA, Canada and countries running a 60 Hz supply service.
A three phase service can be tested for voltage. This test lets you know if the fuses or breaker has an open circuit through them. Use a voltmeter set to one scale above the working voltage of the circuit. Place the test leads from L1 to L2 and check for voltage. Next place the leads from L2 to L3 and check for voltage and finally place the leads from L3 to L1. If a voltage is read between all of the phases the service should be operational. If the service is a three phase four wire system a safer way to check for voltage is each phase line to ground or neutral should produce a voltage.
As always, if you are in doubt about what to do, the best advice anyone should give you is to call a licensed electrician to advise what work is needed.
Before you do any work yourself,
on electrical circuits, equipment or appliances
always use a test meter to ensure the circuit is, in fact, de-energized.
IF YOU ARE NOT ALREADY SURE YOU CAN DO THIS JOB
SAFELY AND COMPETENTLY
REFER THIS WORK TO QUALIFIED PROFESSIONALS.
If the three phase service has a neutral (or 4th wire), then it can be done just by using the 4th neutral and ONE of the legs (l1-l2-l3). If there is no 4th wire that is neutral, then it cannot be done without a transformer.
Three-phase supplies are obtained from three-phase alternators.
A three-phase alternator has three separate stator windings, physically displaced from each other by 120 degrees. As the rotor spins, the field winding induces a separate voltage into each of the stator windings, with each voltage displaced from each other by 120 electrical degrees. The stator windings are then connected together internally, providing three external line conductors, A, B, and C. The potential of each line conductor is displaced from each other by 120 electrical degrees -in other words, each line conductor reaches its peak value of potential 120 electrical degrees apart and in the sequence A, B, C (called its 'phase sequence').
The cheapest service to construct is a single phase service. A three phase service requires more equipment and materials to complete a service.
No. Three phase service is something that you would need to request from your power company. You'd need to not only have service, you also need to have an electrician run 3 phase service into your home.
You can divide a three phase service into (3) single phase circuits providing you have a 4th neutral wire.
You can do that in one of three ways: 1- current on each phase, 2- phase to gnd voltage, 3- phase to phase voltage, preferably with multiple meters, the three lines has to be balanced within ~ 3%
Yes the minimum voltage of an 115vac 400 Hz 3 phase motor will run. You can run a single phase motor on a three service but you cannot be run on a single phase.
The cheapest service to construct is a single phase service. A three phase service requires more equipment and materials to complete a service.
If single phase - 2 wire service > two wires If single phase - 3 wire service > three wires If three phase - 3 wire service > three wires If three phase - 4 wire service > four wires US residential service is usually single phase 3 wire service: Two hots and neutral.
When you do a load test on a 3-phase induction motor you are checking the power factor, viz slip, and efficiency of the motor. You can test various loads with this test.
No. Three phase service is something that you would need to request from your power company. You'd need to not only have service, you also need to have an electrician run 3 phase service into your home.
You can divide a three phase service into (3) single phase circuits providing you have a 4th neutral wire.
If you have single phase now, you have two options. One, is to install a three phase service or Two, install a roto phase device.
If the 240V 3-phase service is 240V phase-to-phase, then you can get 240V single-phase by simply picking two phases (poles, as used in the question) and connecting the load across them. This is simply one third of a standard delta connection. If you need 120V/240V split phase, i.e. with a neutral, as used in residential services, you will need a transformer. If the service is actually a four wire "quadraplex" service, however, you will probably already have that 120V/240V with neutral connection phase available. In this case, you will need to pick the two phases correctly in order to get the proper 120V service half.
You can do that in one of three ways: 1- current on each phase, 2- phase to gnd voltage, 3- phase to phase voltage, preferably with multiple meters, the three lines has to be balanced within ~ 3%
4/0 copper phases and neutral
Yes the minimum voltage of an 115vac 400 Hz 3 phase motor will run. You can run a single phase motor on a three service but you cannot be run on a single phase.
You lose one third the service so the motor overheats and runs slow if at all.
How do you zero phase current transformer test