Three phase Delta motors can continue to operate when one phase has an earth (ground) fault, when the motors are powered from an ungrounded Delta or Wye (star) service. This feature can be helpful in agricultural and oil rig pumping because it allows the operation to continue until the affected motor can be replaced. Motors on a grounded service will trip and the pumping will stop immediately after one phase goes to ground.
The ground ('earth'), because of its mass, is a reasonably-good conductor and is used as a 'reference' for a distribution transformer's neutral terminal. A ground fault ('earth fault') occurs when the line conductor from the distribution transformer makes accidental contact directly with the ground ('earth'). The resulting low-resistance earth path back to the transformer's neutral is such that the resulting ground-fault current('earth-fault current') will operate the transformer's overcurrent protection device (e.g. fuse).
A "GFCI" is a ground fault circuit interrupter. For more information see the link below.
Neutral Ground Resistor is using for minimizing the fault current of system. It is a resistor which connected between ground and neutral and increase the resisting path for fault current.
An earth or ground conductor that is used for continuity throughout the home is the ground conductor that is found in cable wire sets. What it is used for is to bring everything that it is connected to down to the same potential which is zero. The grounding circuit is a low impedance circuit. If a fault occurs on any equipment and shorts out to ground, this conductor being directly connected to the distribution panel, carries the fault and trips the breaker feeding the faulted circuit.
I am sure that the anwser is the San Andreas fault.
They mean the same thing, a current to ground/earth that shouldn't exist in the circuit.
a fault is a large crack in the earth. a fold is when the ground gets bent.
The ground ('earth'), because of its mass, is a reasonably-good conductor and is used as a 'reference' for a distribution transformer's neutral terminal. A ground fault ('earth fault') occurs when the line conductor from the distribution transformer makes accidental contact directly with the ground ('earth'). The resulting low-resistance earth path back to the transformer's neutral is such that the resulting ground-fault current('earth-fault current') will operate the transformer's overcurrent protection device (e.g. fuse).
if your on a fault it will shake and shift ground above
earthquakes
an earthquake
Grounding?AnswerIf a line conductor is unintentionally connected to earth, then it is an earth fault.
If you connected neutral and earth (ground) to each lead in an LED and it glowed then this would be evidence of a ground fault.
There is such a thing as a three phase to earth fault, so maybe this is what you mean by a "balanced earth fault". I don't believe any earth or ground currents would flow in this case. A restricted earth fault is a typical phase to earth fault, where the zone of protection is restricted to a specific area, such as around a transformer. "Restricted" is referring to the protection method, not what is actually going on with the currents and voltages.
The ground shakes, and the earth is displaced along a section of the earthquake fault.
The function of a neutral earth resistor is to limit any fault current resulting from fault between a line conductor and earth.
If one terminal of a battery is earthed (and, by this, we normally mean a 'chassis earth'), then an earth fault within the circuit supplied by the opposite terminal will result in the battery being discharged. The rate of discharge depends on the resistance of the earth fault.