No. All a tap changer (whether 'off-load' or 'on-load') does is to make minor changes to the turns-ratio of a transformer.
depending on the amount of the load of transformer as well as the power factor of it, there is a transformer specific voltage drop at its terminals, due to the internal impedances. The on-load tap changer can / will be used to compensate this voltage drop or rise.
What?... Tell me what a tap changer is, and I may be able to help.
Tap changer is a device that is used to change the secondary voltage on transformers. It is normally on the HV winding of the transformer. Off load tap changer is designed to change the taps only when the transformer is not charged, while on load tap changer is capable of changing the tap on load too.
automatic tap changing transformers can change their tap setting on their own, manual tap means a person has to manually go out and change the tap setting
An on-load tap-changer must not break the supply to the transformer's windings while the transformer is on load. So it has a 'make-before-break' arrangement with its contacts -i.e. one contact moves to the second tap setting, before the second contact moves away from the first tap setting, while a reactor balances the load currents when the contacts are on different tap settings. An on-load tap changer is motor-driven, and can be operated automatically or manually.An off-load tap-changer does not require a make-before-break arrangement, because it is designed to be operated when the transformer is disconnected.
A tap changer is used to vary the turns ration between the windings of a transformer to make minor changes to the secondary voltage. An on-load tap changer enables the turns ratio to be altered without disconnecting the transformer. An off-load tap changer requires the transformer to be temporarily diconnected. On-load tap changers are installed on the high-voltage side of the transformer, where the current is lower.
It is a type of resistor called a potentiometer, which is a resistor with a movable center tap. The full volume signal is applied across the full resistor and the variable volume signal is taken off the movable center tap.
So that tap-changing can't be done any more, or maybe the tap changer was faulty.
Follow the related link, below, for detailed in information.
On-load tap-changers are operated by an electric motor, often by driving a flywheel mechanism. The operation of the tap-changer is controlled by an AVR (automatic voltage regulator) which monitors the transformer's secondary voltage.
First isolate the transformer
A Tap Position Indicator (TPI) is utilized in power transformers to monitor the position of the tap changer, which is responsible for adjusting the transformer winding to control voltage levels.