In its simplest form, a single-phase a.c. system comprises two conductors: a line ('hot') conductor and a neutral conductor. In North America, however, it is usual for a single-phase residential supply to have three conductors: the two 'hot' conductors are connected across opposite ends of a single-phase transformer winding, while the neutral conductor is connected to the centre (tap) of that winding. This provides a combination of 240 V and 120 V, and is known as a 'split phase' single-phase system.
A two-phase a.c. system is very rare, these days, and you are unlikely to come across one. It is an archaic system that has long since been replaced by the three-phase system. Essentially, this system was provided by an a.c. generator whose armature windings were physically displaced from each other by 90 degrees, thus providing two phase voltages that are 90 electrical degrees apart. Usually, a two-phase system was a three-wire system, providing two line conductors and a neutral. The resulting line voltage (measured between the two lines) would then be 1.42 times either of the phase voltages (measured between one of the lines and the neutral).
Two phase is technically a system that became obsolete about 100 years ago when three-phase came in. In two-phase there were two supplies with 90 degrees of phase between them.
However split-phase systems are in common use on North America where a 240 v single-phase supply is supplied with a centre-tapped neutral wire and two live wires with the voltages in opposite phase.
Split-phase allows two separate single-phase 120 v circuits to be taken between neutral and either live wire, while a single-phase 240 v supply is available across the two live wires for high-power appliances.
Split-phase is also used in Europe to supply remote communities with 480 v across the transformer and 240 v between the neutral and each live wire. If the loads are ideally balanced on each side, the current in the neutral is zero, which saves power losses in the wire resistance.
oil and water
On a three phase system you have incorporated into it a potential of three single phase systems. A-B, B-C, C-A. Any two legs of a three phase system can be used as a single phase load. On a three phase system, be it a motor or a service, if one of the legs drops out for what ever reason, the remaining two legs are known as single phase. This is how the terminology became single phasing. As a side note a motor will run in a single phase condition, it just will not start. In motor control, a single phase condition is prevented by the use of overload heaters on all three voltage legs.
The number of Volts in a residential service drop in the US is either 120V 2 Wire, 120V-208V Network, or 120-240V 3 Wire. A 120-208V Network service is not single phase, but its 120V portion is.
In a two-phase connection, the phases are displaced by 90 degrees. Two lines (not 'phases') of a three-phase system will provide a single-phase supply, not a two-phase supply.
A one gang switch is like an ordinary switch box in your home. When there is more than one box, the electrical terminology used is ganging the boxes together. Two switches side by side in a single box is expressed as a two gang box. Three switches side by side in a single box is a three gang box. A single phase circuit is a circuit that gets is supply voltage from a single phase supply system. In North America the single phase supply voltages are 120/240 volts. A single phase circuit can also be supplied from any two legs of a three phase system. The most common voltages in North America from a three phase system are 120/208 volts.
A two-phase a.c. system is an archaic system, in which two phase voltages are generated 90 electrical degrees apart. It has nothing whatsoever to do with the US 'split phase' system that supplies North American homes. A two-phase system can be a four-wire system, or a three-wire system, and was useful because, unlike a single-phase system, it could create naturally rotating magnetic fields in induction motors. It has long been superseded by the three-phase system.
Any load that needs three legs from a three phase system can not be considered single phase. Single phase from a three phase system only needs a connection to two legs.
This is a rubbish questionTwo single phase transformers can be combined together to make a three phase system. It does not become a two phase system. Look up information of an open delta wired distribution system to see how they are tied together.See related links below.
The US system is not a two-phase system; it's a split-phase system. But, to answer your question, probably not without damaging the Japanese device.
On a three phase system you have incorporated into it a potential of three single phase systems. A-B, B-C, C-A. Any two legs of a three phase system can be used as a single phase load. On a three phase system, be it a motor or a service, if one of the legs drops out for what ever reason, the remaining two legs are known as single phase. This is how the terminology became single phasing. As a side note a motor will run in a single phase condition, it just will not start. In motor control, a single phase condition is prevented by the use of overload heaters on all three voltage legs.
In star connection when two phase is short,it work as single phase system. In delta when one phase is open ,it work as a single phase.
There is no such thing as a two phase instrument. There is only single phase and three phase. You can only have: single phase/ one pole single phase/ two pole three phase/ three pole
Nothing happens. This is a normal way to obtain a single phase system from a three phase system.
The number of Volts in a residential service drop in the US is either 120V 2 Wire, 120V-208V Network, or 120-240V 3 Wire. A 120-208V Network service is not single phase, but its 120V portion is.
Any two legs of a three phase system can be classed as a single phase supply.Alternative AnswerAs the above answer points out, connecting a load between any two line conductors of a three-phase supply will give you a single-phase load. But you must, of course, take into account the voltage rating of the load you wish to connect.In Europe, three-phase low-voltage distribution is normally by means of a four-wire system, comprising three line conductors and a neutral conductor, operating at 400 V (line-to-line) and 230 V (line-to-neutral).Your single-phase load's voltage rating must, of course, match either the single-phase supply's line-to-line or line-to-neutral voltages. In Europe, most single-phase loads are rated at 230 V so, for a residential three-phase, four-wire system, it is usual to obtain a single-phase supply by connecting the load between any one of the line conductors and the neutral conductor.But, if you have a non-standard, 400-V single-phase load, then connecting that load between any two line conductors will also give you a single-phase supply.
In a two-phase connection, the phases are displaced by 90 degrees. Two lines (not 'phases') of a three-phase system will provide a single-phase supply, not a two-phase supply.
A one gang switch is like an ordinary switch box in your home. When there is more than one box, the electrical terminology used is ganging the boxes together. Two switches side by side in a single box is expressed as a two gang box. Three switches side by side in a single box is a three gang box. A single phase circuit is a circuit that gets is supply voltage from a single phase supply system. In North America the single phase supply voltages are 120/240 volts. A single phase circuit can also be supplied from any two legs of a three phase system. The most common voltages in North America from a three phase system are 120/208 volts.
Two phase is single phase for today's purposes. We generally do not call 240v single phase "two phase" anymore, although technically that's what it is. 240v two phase has power to both lines to the motor versus 120v single phase has one power line and a neutral. Fortunately most single phase motors today are dual voltage. So check your nameplate data of the motor for guidance. The use of proper motor protection will prevent any damage to motors if wrong voltages are inadvertantly applied.CommentA two-phase system is an archic system, in which two phase voltages are displaced from each other by 90 electrical degrees. Like three-phase, it had the advantage of producing a naturally-rotating magnetic field, so could drive induction motors without any need for a starting capacitor.