I would suggest a 20 amp breaker.
* Added - I would suggest a 25 amp breaker. A slight surge, depending upon what equipment is the source of the 17.3 amp load, should not result in circuit breaker opening.
<<>>
In North America, the electrical code only allows circuit loading up to 80% on a continuous load. A 20 amp breaker can be legally loaded to 16 amps. A 25 amp breaker can be legally loaded to 20 amps.
A #10 wire has the capacity for 30 amps. No breaker larger than 30 amps should be used to protect the circuit.
Breaker sizing is dependant on what the load amperage is that the breaker is connected to. If the amperage is not given but just the wattage, use this equation I = W/E. Amps = Watts/Volts. This air conditioner unit should be on a dedicated circuit receptacle. On these types of loads the conductor can only be loaded to 80% of the conductors rating. So a 15 amp breaker times 80% = 12 amps or Watts = Amps x Volts, 12 x 120 = 1440 watts. A 20 amp breaker times 80% = 16 amps or Watts = Amps x Volts, 16 x 120 = 1920. Once the breaker is sized remember to use the correct wire size to correspond with the amperage of the breaker.
For typical residential house wiring 12 AWG wire is required for a 20 Amp breaker. If you change out the breaker for a 25 A breaker you would have to rewire the circuit with 10 AWG. In that case you could up the breaker to 30 Amps. All outlets and switches should be rated at the same voltage and current as the breaker.
3000 / 240 = Amps. You de-rate a breaker by 20 % for continuous load like an oven. You could get by with a 20 Amp breaker and 12 AWG wire. However, I would recommend 30 Amps and 10 AWG for an oven for the long run.
No, it is not safe to use a #8 conductor on a 50 amp breaker. A #8 conductor is only rated at 45 amps capacity. By connecting it to a 50 amp breaker, which would trip at 50 amps on an overload, would overload the conductor by an extra 5 amps. This would be a conflict against the electrical code.
A double breaker is a breaker that has 2 switches on it. One of the switches is 20 amps and the other is 30 amps.
KA stands for kilo-amps, or thousands of amps. Thus a 2KA breaker means it will trip when the load exceeds 2,000 amps.
It's the amps that are controlled by the breaker not the volts. You can have a 600 volt 15 amp breaker, you can have a 347 volt 15 amp breaker. The breaker will trip when you exceed 15 AMPS.
Look on the heater and see what amps it is pulling. That will determine the wire size and breaker size. It must be on a dedicated circuit. 15 amps = AWG # 14 wire with 15 amp breaker 20 amps = AWG # 12 wire with 20 amp breaker 30 amps = AWG # 10 wire with 30 amp breaker 40 amps = AWG # 8 wire with 40 amp breaker
The number that is on a breaker is the amount of amperage that the breaker can deliver before it trips. This is the same regardless of how many poles the breaker is.
61 nano-amps is 0.061 milliamps or 0.000061 amps
Depends on what you have connected to the circuit. It is less than 10 amps or the breaker would trip. A rule of thumb is you design for about 80% load related to the breaker. For 20 amps that would equal 16 amps.
15 amp breaker.
Not a whole lot. Assuming that is 120 volt power, 1200 watts would be 10 amps. A standard breaker is 15 amps.
A #10 wire has the capacity for 30 amps. No breaker larger than 30 amps should be used to protect the circuit.
If the current safety requirement is 30 amps, you can;t run if off of a larger circuit breaker. It violates NEC and is very unsafe. If the current requirement is 40 amps , it will continuously trip a 30 amp breaker because it is too small of a breaker in electrical requirement.
Add up your amps to calculate your breaker size. Add up your loads (amps), divide by 0.8, and choose that size breaker. If that number does not correspond to a standard size breaker you go to the next higher standard size breaker.