answersLogoWhite

0


Best Answer

we are looking to wire up diagram for a 45kw transformer from 220 volts to 440 volts 3 phase 60 Hz

<<>>

The formula you are looking for is KVA = Amps x Volts x 1.73/1000 = 118 x 380 x 1.73 = 77573/1000 = 77.5 KVA transformer.

Your primary amperage will be 205 amps and the secondary amperage will be 118 amps.

User Avatar

Wiki User

11y ago
This answer is:
User Avatar

Add your answer:

Earn +20 pts
Q: What capacity of transformer required for step up from 220 to 380 3 phase 45 kw air compressor?
Write your answer...
Submit
Still have questions?
magnify glass
imp
Continue Learning about Natural Sciences

Is there a neutral on a three phase transformer?

It depends on whether you are wye or delta connected. A transformer is a transformer, and a three phase transformer is simply three transformers. The key is in how you hook them up.AnswerIt depends on how the transformer is connected. If one set of windings is connected in star (or wye), then the star point is/canbe earthed and becomes the neutral for that particular connection; this is the standard connection for the secondary (low-voltage) of European distribution transformers. In North American three-phase distribution transformers, the secondary windings are connected in delta, and one phase is centre tapped, earthed, and that becomes the neutral point for a 240/120-V split-phase supply to a residence.This answer applies to both three-phase transformers, and to single-phase transformers which have been connected to form a three-phase transformer bank. (It is incorrect to say that a three-phase transformer is simply three single-phase transformers!)


What is the purpose of conducting sc and oc test of single phase transformer?

to determine the transformer characteristics...


Where are three phase transformer systems used?

Any where that a three phase supply distribution is needed to operate three phase equipment.


How do you connect 480 vac three phase power to a 480 vac single phase transformer?

If the primary and the secondary windings of the three phase transformer are connected in delta, you cannot get a healthy neutral from it but why bother? You simply drive a rod into earth and use it as a neutral. Alternatively either the primary or the secondary windings must be connected as star and you use the common point as neutral.


Does the formula used to calculate the turns ratio uses the phase voltages and phase current?

For a transformer, the turns ratio always applies between its primary and secondary windings. So the turns ratio for a three-phase transformer is the ratio of primary to secondary phase voltages, not between line voltages.

Related questions

What is the maximum capacity of 11kv transformer?

It depends on the design of the transformer but 1 MVA is a common size for an 11 kV / 415 v three-phase transformer.


Would you install three-phase transformer or bank of three single phase transformer in a large power station and justify by comparing the two schemes?

A three-phase transformer bank is often used in power stations because it is easier to construct and transport very large single-phase transformers, compared with constructing and transforming an equivalent-capacity three-phase transformer.


What is the 3-phase step-down transformer capacity in kVA 380V-220V for 4.5kW motor?

5 kva


Can 3 single phase transformers can replace 1 three phase transformer?

Yes, you can use three single phase transformers on three phase applications and interconnect them to serve as a single transformer or you could use one single phase transformer fed from two of the three lines in a step down application.


What is the current of 1MVA transformer?

This depends on the voltage, and whether it is a three phase or single phase transformer.


When three single phase tronsformer is conneted to star what will be the phase shift between each phases?

When 3ph transformer of required capacity is unavailable in that place 3 single phase bank is used. More over this bank works well in conditions where there's unbalance of loads. When there's quite small 3ph load you can isolate one transformer to create open delta connection. In bank nd single 3ph transfo's there wont be any change in maintaining phase shift


Why vector group is required?

There are various ways in which you can connect a three-phase transformer's primary and secondary windings, or in which you can connect three single-phase transformers to create a three-phase transformer bank. For example: wye-wye, wye-delta, delta-delta, delta-wye, etc.For each connection, there is a natural phase shift between the primary and secondary line voltages. This is called the angular displacement (or 'phase displacement') of the transformer connection.If you wish to parallel two three-phase transformers, or two three-phase transformer banks, then their angular displacements must be the same (there are also other requirements not relevant to this answer).A vector group is a method of specifying a three-phase transformer (or transformer bank) method of connection and its angular displacement. Transformer connections from the same group can be paralleled. Those in different groups cannot


What are the condition for transformer parallel operation?

CONDITIONS REQUIRED FOR TRANSFORMER PARALLEL operation are.. 1. Voltage turn ratio. 2. phase sequence 3. Impedence should be same 4. polarity Hitesh


Is there a basic difference between a three phase power transformer and a three phase distribution transformer?

The basic difference is the secondary voltages. On a distribution transformer the secondary voltage is very high. This is to overcome line loss for transmission of electricity over long distances. A three phase power transformer is used at the consumers three phase services end to manipulate voltages that consumers need to operate their equipment. The transformer that feeds your house is considered to be a single phase power transformer.


Why would you use a three phase transformer in place of a single phase transformer?

the necesscity of two three phase transformers operating in parallel are as follows...if the one transformer fails to give supply,then another transformer can be used in parallel and hance,continuity of supply can be maintained.one transformer can be easily take out from the supply for repair & maintanance.if the load on the substation increases beyond the rated values of transformer, then another transformer can be used to share rhe load of the substation.


How do you design a transformer with three phase 400v input and single phase 2000v output?

By design are you going to wind the transformer yourself? In your design you need a 5:1 ratio. On the output side of the transformer any two legs of a three phase transformer is considered single phase voltage. Good luck on your project.


Phase imbalance on three phase compressor Can a phase imbalance cause a compressor to lock up mechanically even if power restored to unit?

yes