The neutral.
That's because the neutral is a grounded conductor.AnswerThe line (not 'phase'!) conductor has a potential of 230 V (Europe) or 120 V (North America) with respect to the neutral, which is earthed (grounded) at the supply panel.As you are more than likely 'earthed' (or 'grounded') by virtue of standing on it, this means that if you come into contact with a line conductor you will experience a potential difference of 230 V (or 120 V) between your point of contact with that line conductor and your point of contact with the earth, and you will receive a shock.However, as the neutral conductor is already at, or close to, earth potential, should you come into contact with the neutral conductor, you will experience no (or very little) potential difference, and receive no shock.
A ground, or earth, conductor is never included in the conductor count. So, a three-phase, three-wire, system has three line conductors, whereas a three-phase, four-wire system, has three line conductors and a neutral conductor.
The (ideal) voltage is 480V line to line. The line to neutral voltage (if it is a grounded system - 4 wires) is 480 / 1.732 = 277 volts. The actual measured voltage may be slightly higher or lower than this.
If a load were only 240 volt on a single phase 240v system with a center tapped transformer the neutral conductor would carry no current.
400 volt three phase on a grounded system is 230 volt single phase, with each phase 120 degrees apart. So, if you have a 400 volt, three phase four wire service (grounded service), you can pull one phase off and reference to the neutral for 230 volt service. Note this may not allow 115 volt service, unless there is also a center tap for each phase.
There is no such thing as a 'phase conductor'; the correct term is 'line conductor'. In a single-phase system, the line conductor is the energised conductor; in a three-phase system, there are three (energised) line conductors.
A 'grounded-wye' connection describes a wye-connected supply, whose star-point (or common point) is grounded. This is essential in order to ensure stable phase voltages. I'm not sure what you mean by a 'grounded-phase' connection; if you mean a 'grounded-line' connection, then this is a short-circuit to ground from a line conductor.
That's because the neutral is a grounded conductor.AnswerThe line (not 'phase'!) conductor has a potential of 230 V (Europe) or 120 V (North America) with respect to the neutral, which is earthed (grounded) at the supply panel.As you are more than likely 'earthed' (or 'grounded') by virtue of standing on it, this means that if you come into contact with a line conductor you will experience a potential difference of 230 V (or 120 V) between your point of contact with that line conductor and your point of contact with the earth, and you will receive a shock.However, as the neutral conductor is already at, or close to, earth potential, should you come into contact with the neutral conductor, you will experience no (or very little) potential difference, and receive no shock.
A ground, or earth, conductor is never included in the conductor count. So, a three-phase, three-wire, system has three line conductors, whereas a three-phase, four-wire system, has three line conductors and a neutral conductor.
no
In residential 120 VAC, single-phase electrical wiring, there are three main types of electrical wires: 1. Ungrounded conductor (Hot, and sometimes called "Line" or "Phase") 2. Grounded conductor (Neutral), and 3. Grounding conductor (Safety Ground or Protective Earth) The groundED conductor is the power return, intended as a current return path from the load back to the source to complete the "circuit." Its insulation is White, gray or a non-green color with white stripes. The National Electric Code requires it be connected to earth ("groundED ") at the service entrance and usually only there. The groundING conductor is usually the safety ground which serves as an emergency current return path in the event of a circuit fault or overvoltage. Like the groundED conductor, it too is grounded at the service entrance, but is also connected to metal surfaces and parts along the circuit, groundING them. It conducts current only if the current "seeks" to return to the service entrance along a path other than the Neutral (like through your chest, should a Hot wire becomes loose and contact metal in the circuit that you may touch). Since the grounding conductor doesn't normally carry current, its cross-section is sometimes smaller than the groundED conductor's. The grounding conductor's insulation is green (no other conductors can have green insulation) though sometimes it is bare copper. Sometimes the steel metal conduit enclosing the Hot and Neutral acts as the grounding conductor.
It's highly probably that the '240 V' refers to the machine's phase voltage. In which case, its line voltage will be 1.732 times larger -i.e. 415 V. Phase voltages are measured between any line conductor and the neutral conductor, whereas line voltages are measured between any pair of the three line conductors.
The (ideal) voltage is 480V line to line. The line to neutral voltage (if it is a grounded system - 4 wires) is 480 / 1.732 = 277 volts. The actual measured voltage may be slightly higher or lower than this.
There is no such thing as a 'phase conductor'. The correct term is 'line conductor'. Line conductors are the three energised conductors that supply a three-phase load.
All current is the passage of electric charges from one terminal to another through a conductor so there is no real difference in the type of current that flows in a 3 phase system compared to a single phase system.
If a load were only 240 volt on a single phase 240v system with a center tapped transformer the neutral conductor would carry no current.
Phase is just like as +ve terminal & neutral is just like -ve terminal in equivalent dc circuit. In AC, lines the higher voltage terminal is called phase & lower voltage terminal is known as neutral.