answersLogoWhite

0


Best Answer

== == == == It is true. Damage will most likely result somewhere, maybe not everything. When a neutral on a multi-wire circuit is opened (open-circuited) (removed) (cut) while things are under load, the voltage will change at the loads. Some loads will get more than normal, some will get less. The damage usually occurs on the side that gets MORE voltage. For example: your TV may be on a circuit that goes from 120volts to 50 volts, while your light bulb goes from 120volts to 180volts and blows. It all depends on how "balanced" the circuit is. In theory, if the loads are perfectly balanced then the neutral is not needed. In reality loads vary constantly, therefore, the voltage will vary if the neutral is open-circuited. That means running with an open neutral is something that anyone with any smarts at all will not do. It is absolutely possible to damage equipment by opening the neutral in some circumstances. <><><>

As always, if you are in doubt about what to do, the best advice anyone should give you is to call a licensed electrician to advise what work is needed.

If you do this work yourself, always turn off the power

at the breaker box/fuse panel BEFORE you attempt to do any work AND

always use an electrician's test meter having metal-tipped probes

(not a simple proximity voltage indicator)

to insure the circuit is, in fact, de-energized.

IF YOU ARE NOT ALREADY SURE YOU CAN DO THIS JOB

SAFELY AND COMPETENTLY

REFER THIS WORK TO QUALIFIED PROFESSIONALS.

User Avatar

Wiki User

14y ago
This answer is:
User Avatar
More answers
User Avatar

Wiki User

10y ago

You will open or break the circuit to any single phase circuits being supplied by the panel.

Three phase panels which are supplied with a neutral typically supply a variety of circuits, power, lighting and motor circuits such as air conditioning. A 3 phase motor circuit will have three pole circuit breakers, one breaker occupying three spaces in the panel and buss bar. The single pole circuit breakers are supplying single phase power via the single "hot" phase off the breaker and the neutral Also, many three phase circuits may employ the neutral for low voltage control.

In a low voltage (208-240V) three phase panel, the three pole breakers are supplying 208-240 volt power. The single pole breakers are supplying 110 volt. (with the neutral as the "return" to complete the circuit.)

In a high voltage (480V) three phase panel, the three pole breakers are supplying 480 volt power and the single pole breakers are supplying 277 volts with the neutral as the return. 277 volt power is used almost exclusively for commercial lighting loads.

The bottom line here is you don't want to disconnect the neutral from any panel. It's there for a good reason!

Another AnswerFor an unbalanced load, the removal of the source's neutral connection will result in unbalanced phase voltages
This answer is:
User Avatar

Add your answer:

Earn +20 pts
Q: What happens when you disconnect a neutral at source in a three phase system?
Write your answer...
Submit
Still have questions?
magnify glass
imp
Continue Learning about Engineering

Do you need a neutral in your 3 phase disconnect to pump control?

Not usually, if the three phase pump is a three wire pump then the disconnect does not need a neutral. The pump control may or may not need a neutral depending on the voltage system that the control panel needs.


Can a 3 wire system create neutral voltages due to Harmonic distortion?

Yes, a 3 wire system can create neutral voltages due to harmonic distortion. Neutral voltages can also be caused by load imbalance between the two hots. It is normal for neutral to have a voltage differential relative to ground. Neutral is, after all, a current carrying conductor. In a well balanced system, however, there is little (theoretically zero) current in neutral.


How emergency generators onboard taking load automatically?

There is usually a reserve switching device or scheme which is activated when the power coming from the main grid disappears. When such an outage happens, the scheme will sense it and disconnect the circuitry from the main source of power (grid) and start up the emergency generators. When the main power is restored, the system will connect you back to it and turn off the emergency generator.


Can the neutral conductor be downsized in a 3 phase electrical system?

Yes, you can reduce the neutral in a three phase system. you must figure the unbalanced current the neutral will carry and also make allowances for any harmonics that may be present.


How do you identify that in the system the neutral is floating or not?

do a continuity test between the neutral and the metal enclosure of the equipment containing the neutral. infinity reading [ open line ] indicates floating neutral. Steve sorensen jr

Related questions

Do you need a neutral in your 3 phase disconnect to pump control?

Not usually, if the three phase pump is a three wire pump then the disconnect does not need a neutral. The pump control may or may not need a neutral depending on the voltage system that the control panel needs.


What is gndt reading?

GNDT reading stands for Grounded Neutral Disconnect Time. It refers to the time delay set in some electrical protection devices to disconnect a grounded neutral system from the mains in case of faults to protect against electrical hazards.


What happens when you remove heat from a system?

what happens to a product when removed from the heat source?


What happens when your Wii system does not power on?

Nothing it might be disconnected or it might be something else. It happens to me too so what i do is disconnect it for a while about 5 to 8 minutes and then connect it again.


What happens if the source of 220 Volts originates from two legs of a 3-phase circuit?

Nothing happens. This is a normal way to obtain a single phase system from a three phase system.


How do you disconnect a theft deterrent system?

First, disarm the theft deterrent system. Then you can power off and disconnect it.


How can you disconnect alarm system Nissan quest 2005?

How car i disconnect the alarm system of Nissan quest 2005. Disturbing the neighbours


How do I disconnect the airbag system for a radiator change in 1997 Chevy Cavaliar?

easiest way to disconnect is to remove airbag fuse from vehicle. why you need to disconnect to remove a radiator is beyond me, the radiator has nothing to do with the airbags


What is role of neutral in three phase system?

In a three phase system, connected wye, neutral is the common return, and it is grounded. In a delta connection, there is no neutral.


How do you disconnect security system?

By disconnecting the battery.


Can you tow a 2002 blazer?

If you have a manual transmission, you can put the transmission in neutral and flat tow it that way, whether it's a 2WD or 4WD model. If you have an automatic transmission but either a manual transfer case or the electronic transfer case with the four button system (NOT with the three button system), you can put the transfer case in neutral and tow it that way. Otherwise, you'll have to disconnect the driveshaft(s) before you flat tow it.


What is the difference between neutral point and earthing?

Earthing point is where conductor is directly connected to ground and its potential is always zero. Neutral is a return path in single phase system and in three phase system Neutral point will have zero potential if all the loads are balanced in the system. In un balanced three phase system even neutral point will have some potential