answersLogoWhite

0


Best Answer

Yes, you can reduce the neutral in a three phase system. you must figure the unbalanced current the neutral will carry and also make allowances for any harmonics that may be present.

User Avatar

Wiki User

12y ago
This answer is:
User Avatar

Add your answer:

Earn +20 pts
Q: Can the neutral conductor be downsized in a 3 phase electrical system?
Write your answer...
Submit
Still have questions?
magnify glass
imp
Continue Learning about Engineering

What is an AC single phase 2 wire system?

two wires coming off the secondary of the transformer ex. residential voltage of 120 volts each line, and one neutral wire, L1 to neutral is 120 volts, L2 to neutral is 120 volts, L1 to L2 is 240 volts.AnswerA single-phase, two-wire, system comprises a line conductor and a neutral conductor. In European countries, the line conductor for a residential supply is at a nominal potential of 230 V with respect to the neutral.In North America, a 'split phase' system is used for residential supplies; this is a single-phase, three-wire, system comprising two line conductors which and a neutral conductor. The nominal potential difference between the line conductor is 240 V, while the potential of each line conductor with respect to the neutral is 120 V.


Can a 3 wire system create neutral voltages due to Harmonic distortion?

Yes, a 3 wire system can create neutral voltages due to harmonic distortion. Neutral voltages can also be caused by load imbalance between the two hots. It is normal for neutral to have a voltage differential relative to ground. Neutral is, after all, a current carrying conductor. In a well balanced system, however, there is little (theoretically zero) current in neutral.


Why link is provided as neutral in an ac circuit?

link is provided in neutral path of ac supply because it should provide a path for unbalanced currents , if we use fuse ,fuse may blow of and damage the entire system and also unbalanced currents may be more than the fuse rating


Is it possible to use brick-wall for earthing?

A brick wall is not a sufficiently good electrical conductor to act as part of an earthing system. There is no substitute for a proper system.


Is a neutral considered a current carrying conductor?

No, in a three phase balance load, there should not be any current through Neutral conductor. If it is a 2 wire, single phase system, the Neutral will carry the same current as live conductor if the system has no Earth fault, leak.

Related questions

Define earth voltage and neutral voltage?

As the neutral point of an electrical supply system is often connected to earth ground, ground and neutral are closely related. Under certain conditions, a conductor used to connect to a system neutral is also used for grounding (earthing) of equipment and structures. Current carried on a grounding conductor can result in objectionable or dangerous voltages appearing on equipment enclosures, so the installation of grounding conductors and neutral conductors is carefully defined in electrical regulations. Where a neutral conductor is used also to connect equipment enclosures to earth, care must be taken that the neutral conductor never rises to a high voltage with respect to local ground.


What is meant by PEN conductor when referring to earthing of supply system?

Conductor combining the functions of both a protective earthing conductor and a neutral conductor


What is the meaning of ecc in electrical?

ECC stands for Earth Continuity Conductor. It is a grounding component of the electrical system. An ECC can be a bare conductor, a single conductor or a part of a multi-conductor cable.


Why you required neutral explain in detail?

The neutral conductor (also referred to as the grounded conductor) is used in order to establish a ground reference in an electrical system. Without this reference, circuit breakers would not reliably trip (most likely, they would not trip at all) in response to an overcurrent condition. This is a dangerous situation which would lead to destruction of equipment and loss of life. The other primary reason to include a neutral conductor is to stabilize the voltage in a single phase or three phase distribution system. Without a neutral conductor the voltage on ungrounded (hot) conductors would raise or lower due to varying load conditions. This erratically fluctuating voltage would cause damage to equipment and potentially harm people as well. The neutral conductor is very important to ensure safety in electrical circuits.


Is there a neutral conductor in a 3 phase 4 wire wye system?

no


Is the brown cable live in electrical wiring?

all electrical wire but green and white are hot wires in electrical wiring according to the national electrical code NEC in the USA.Answer for UK / European CablesThe correct term is 'line', rather than 'live', with the line conductor having a nominal potential of 230 V with respect to the neutral. As the original answer points out, both line and neutral conductors are defined as 'live' by both the NEC and the equivalent UK regulations.Throughout Europe, brown insulation is used to identify the line conductor of single-phase system. For a three-phase system, the three line conductors are identified as brown, black, and grey.The neutral conductor is identified by blueinsulation, and the protective (earth/ground) conductor is identified by yellow/green striped insulation.


What is the purpose of neutral contactor?

Presumably, you are asking the purpose of a neutral conductor, rather than 'contactor'?A alternating-current supply has two conductors, a lineconductor and a neutral conductor. The line conductor is at system potential (e.g. 230 V in Europe), whereas the neutral conductor is at approximately earth (ground) potential because it is earthed (grounded) at the supply transformer. The neutral conductor acts as the 'return' path to the transformer, carrying the same load current as the line conductor.


What conductor should be grounded in a four wire three phase system?

The neutral.


What is role of neutral in three phase system?

In a three phase system, connected wye, neutral is the common return, and it is grounded. In a delta connection, there is no neutral.


Difference between neutral conductor and grounding conductor is that?

A Neutral represents a reference point within an electrical distribution system. Conductors connected to this reference point (Neutral) should, normally, be non current carrying conductors, sized to handle momentary faults (short circuits) occurring in electrical equipment. A Ground represents an electrical path, normally designed to carry fault current when a insulation breakdown occurs within electrical equipment. (Note: Breakdowns can be forced by connecting (dropping) a metal tool or conductive material from a voltage potential to the steel structure within a facility).


Why you take radius or size of neutral wire half wrt phase conductor?

On three phase services over 200 amps the electrical code allows the electrical contractor to reduce the size of the neutral wire . This saves the customer money. There are conditions as to how much the neutral can be reduced but it is not as low as half the supply conductors. The reason that the neutral can be reduced is that it only carries the unbalanced current on the three phase four wire system.


How do you know which wire is hot on a cord with no color system?

The National Electrical Code requires that the neutral wire is to be designated as the "identified" conductor. Method differ, but look for ridges, lines, or writing on one of the wires.