Yes, you can reduce the neutral in a three phase system. you must figure the unbalanced current the neutral will carry and also make allowances for any harmonics that may be present.
two wires coming off the secondary of the transformer ex. residential voltage of 120 volts each line, and one neutral wire, L1 to neutral is 120 volts, L2 to neutral is 120 volts, L1 to L2 is 240 volts.AnswerA single-phase, two-wire, system comprises a line conductor and a neutral conductor. In European countries, the line conductor for a residential supply is at a nominal potential of 230 V with respect to the neutral.In North America, a 'split phase' system is used for residential supplies; this is a single-phase, three-wire, system comprising two line conductors which and a neutral conductor. The nominal potential difference between the line conductor is 240 V, while the potential of each line conductor with respect to the neutral is 120 V.
Yes, a 3 wire system can create neutral voltages due to harmonic distortion. Neutral voltages can also be caused by load imbalance between the two hots. It is normal for neutral to have a voltage differential relative to ground. Neutral is, after all, a current carrying conductor. In a well balanced system, however, there is little (theoretically zero) current in neutral.
link is provided in neutral path of ac supply because it should provide a path for unbalanced currents , if we use fuse ,fuse may blow of and damage the entire system and also unbalanced currents may be more than the fuse rating
A brick wall is not a sufficiently good electrical conductor to act as part of an earthing system. There is no substitute for a proper system.
No, in a three phase balance load, there should not be any current through Neutral conductor. If it is a 2 wire, single phase system, the Neutral will carry the same current as live conductor if the system has no Earth fault, leak.
As the neutral point of an electrical supply system is often connected to earth ground, ground and neutral are closely related. Under certain conditions, a conductor used to connect to a system neutral is also used for grounding (earthing) of equipment and structures. Current carried on a grounding conductor can result in objectionable or dangerous voltages appearing on equipment enclosures, so the installation of grounding conductors and neutral conductors is carefully defined in electrical regulations. Where a neutral conductor is used also to connect equipment enclosures to earth, care must be taken that the neutral conductor never rises to a high voltage with respect to local ground.
Conductor combining the functions of both a protective earthing conductor and a neutral conductor
ECC stands for Earth Continuity Conductor. It is a grounding component of the electrical system. An ECC can be a bare conductor, a single conductor or a part of a multi-conductor cable.
The neutral conductor (also referred to as the grounded conductor) is used in order to establish a ground reference in an electrical system. Without this reference, circuit breakers would not reliably trip (most likely, they would not trip at all) in response to an overcurrent condition. This is a dangerous situation which would lead to destruction of equipment and loss of life. The other primary reason to include a neutral conductor is to stabilize the voltage in a single phase or three phase distribution system. Without a neutral conductor the voltage on ungrounded (hot) conductors would raise or lower due to varying load conditions. This erratically fluctuating voltage would cause damage to equipment and potentially harm people as well. The neutral conductor is very important to ensure safety in electrical circuits.
no
all electrical wire but green and white are hot wires in electrical wiring according to the national electrical code NEC in the USA.Answer for UK / European CablesThe correct term is 'line', rather than 'live', with the line conductor having a nominal potential of 230 V with respect to the neutral. As the original answer points out, both line and neutral conductors are defined as 'live' by both the NEC and the equivalent UK regulations.Throughout Europe, brown insulation is used to identify the line conductor of single-phase system. For a three-phase system, the three line conductors are identified as brown, black, and grey.The neutral conductor is identified by blueinsulation, and the protective (earth/ground) conductor is identified by yellow/green striped insulation.
Presumably, you are asking the purpose of a neutral conductor, rather than 'contactor'?A alternating-current supply has two conductors, a lineconductor and a neutral conductor. The line conductor is at system potential (e.g. 230 V in Europe), whereas the neutral conductor is at approximately earth (ground) potential because it is earthed (grounded) at the supply transformer. The neutral conductor acts as the 'return' path to the transformer, carrying the same load current as the line conductor.
The neutral.
In a three phase system, connected wye, neutral is the common return, and it is grounded. In a delta connection, there is no neutral.
A Neutral represents a reference point within an electrical distribution system. Conductors connected to this reference point (Neutral) should, normally, be non current carrying conductors, sized to handle momentary faults (short circuits) occurring in electrical equipment. A Ground represents an electrical path, normally designed to carry fault current when a insulation breakdown occurs within electrical equipment. (Note: Breakdowns can be forced by connecting (dropping) a metal tool or conductive material from a voltage potential to the steel structure within a facility).
On three phase services over 200 amps the electrical code allows the electrical contractor to reduce the size of the neutral wire . This saves the customer money. There are conditions as to how much the neutral can be reduced but it is not as low as half the supply conductors. The reason that the neutral can be reduced is that it only carries the unbalanced current on the three phase four wire system.
The National Electrical Code requires that the neutral wire is to be designated as the "identified" conductor. Method differ, but look for ridges, lines, or writing on one of the wires.