It depends on the voltage on line side. KVA is simply thousand volt-amps, so you need to know voltage in order to calculate amperes.
Another Answer
The rated primary current is the rated apparent power of the transformer, divided by the rated primary current. However, the actual primary current is determined by the actualsecondary load current in proportion to the reciprocal of the turns ratio.
Different controllers have different outputs depending on how many valves are on each zone. In the device there is a control transformer. Look for the VA output of the transformer's secondary side. Mine states 20 VA at 24 volts. To find the amperage use the following equation. I = W/V. Amps = Watts or VA/Volts. Mine can output 20 divided by 24 = .83 amps. This amperage will be the maximum output in amps that the controller can produce to operate the zone valves. To find the current draw of the primary side of the transformer divide the transformers VA by 120 volts.
To answer this question a voltage must be given. 25 amps drawn by a bulb seem to be on the high side.
No, you can not plug a 240 volt amplifier into a 120 volt outlet. That said there are a number of step-up transformers available that will convert 110V to 220V - that's the simplest way to do it. You should make sure the transformer is rated at many times the power of your amplifier, because of inefficiencies in the amplifier. Look on your amplifier to see how many amps it uses at 220V. Double that number for going to 110 and add 20% more amps as a conversion margin. Take that number and multiply it by 110 to get the watts you need to supply. Size the transformer accordingly. eg. 5 amps @ 220V 5 amps * 2 = 10 amps 10*20% = 2 amps Total amps = 12 amps 12 amps*110 = 1320 watts In this example a transformer rated at or above the calculated wattage is recommended.
to derive 120 volts from 480 volts you have to use a transformer, based on your needs. If you needed 100 amps at 120 volt single phase you would need a 12kva transformer. This is just an example.
Enough to make your mother’s panties drop on the floor.
The maximum power output of the transformer is measured in VA or KVA, (volt-amps) or thousand (volt-amps). That will will marked or stamped on the transformer. If you want to measure the amount of power being used by the Xformer, measure the Line side current in amps with an amprobe and multiply by the line voltage to it. The result in watts is the power consumption.
For single phase, KVA = (line to ground) * (phase current). A 75kVA 480 to 208Y/120 volt transformer is a fairly common transformer. I assume this is the type of transformer you are referring to. 75k / 120 = 625 Amps. As an FYI, the 208Y voltage is the line to line voltage, which is equal to (phase 1) - (phase 2), where the phases are separated by 120 degrees, thus (phase 1) * 1.732 For three phase, kVA = (line to line voltage) * (phase current) *(sqrt 3), 75k / 208 / 1.732 = 208 Amps.
On a 1kva you have 1000 watts capacity. To fine the current the formula is I = W/E. The secondary side of the transformer has the capacity of 1000/120 = 8.3 amps. In your question you do not put the amps across the secondary you draw amps from it. Using the transformer to its maximum, without overloading it, the primary will be 4.16 amps at 240 volts and the secondary will be 8.33 at 120 volts. <<>> voltage times amps equals wattage
The primary line side of a 3 phase transformer should be marked H1, H2, H3. The line side is the incoming voltage that you want to step up or step down or isolate.
Rephrase your question, as it doesn't make any sense. If the primary side of the transformer is 480 volts 3 phase, this transformer can be supplied from a breaker as big as 180 amps. If 480 volts 3 phase is your secondary then you can supply up to 180 amps to your loads.
yes,we can change the transformer side in transmission line as use of high current or high voltage in output.
The wattage must remain equal on the primary and secondary sides of a transformer. An example to the above statement with a 1000 watt step down transformer. To fine the watts (load) the formula is W = A x V. The primary side of the transformer has the capacity of 1000 W = 4.16 Amps x 240 Volts. The secondary side of the transformer has the capacity of 1000 W = 8.3 Amps x 120 Volts. Using the transformer to its maximum, without overloading it, the primary will be 4.16 amps at 240 volts and the secondary will be 8.33 at 120 volts. As you can see the wattage (load) remains constant only the voltages and current change.
The load side of a transformer feeds the device, such as a light or motor. It is the output of the transformer. The input, or line side, provides the voltage that is to be transformed, either up or down, to supply the load side.AnswerA transformer's primary winding is connected to the supply voltage, and the secondary winding is connected to the load.
50 VA means about 50 watts. Transformers usually use VA instead of watts because a transformer has very little wasted power, and watts measure power. A 50 va transformer that is 120v. on the primary side will use about .41 amps at 120 volts. On the secondary side, (if it's 24 volts) it will support about 2.08 amps.
You need to specify the phase. I assume it is 3 phase system. Then the HT current is 30.3 amps
The line side of a transformer that is connected to your source or incoming voltage that you are stepping up or down.
Different controllers have different outputs depending on how many valves are on each zone. In the device there is a control transformer. Look for the VA output of the transformer's secondary side. Mine states 20 VA at 24 volts. To find the amperage use the following equation. I = W/V. Amps = Watts or VA/Volts. Mine can output 20 divided by 24 = .83 amps. This amperage will be the maximum output in amps that the controller can produce to operate the zone valves. To find the current draw of the primary side of the transformer divide the transformers VA by 120 volts.