Depends on the three phase voltage. 54 Kilowatts = 54,000 Watts. 54,000 Watts / square root of 3 / voltage. So a three phase, 54KW, 480 Volt load equals 64.95 Amps (54,000/1.732/480 = 64.95)
AnswerThe equation for power of a balanced three-phase load is as follows: P = 1.732 EL IL x power factor
...where EL and IL are line values.
So, to find the current drawn by the (balanced) load: IL = P / (1.732 EL x power factor)
Unfortunately, as you have not supplied a value for power factor, your question cannot be answered.
If I have 1 KW In 3 Phase it will give 1.54 A and In single phase it will give 4.6 AFor cosF 0.9V 415 3 phV 240 1 phIt seems the reason is because the current is carried on more wires. Also, remember that if wattage stays constant, then as voltage increases, current decreases.AnswerIt really depends on the load. Are you assumining the three-phase load to be the same as the single-phase load or, as it is likely to be in practice, three times the value of the single-phase load?But, in either case, the single-phase current will not be double the the three-phase (line) current!The equation for the load current supplying a single-phase is: I = P / (E x power factor)The equation for the line current supplying a balanced three-phase system is: IL = P / (1.732 x E x power factor)If you insert real figures into these equations, (240 V for the single-phase voltage and 415 V for the three-phase line voltage) then you will find that, when the three-phase load is threetimes that of the single-phase load, the supply currents will be exactly the same. On the other hand, if you assume that the three-phase load is exactly the same as the single-phase load, then you will find that the three-phase line current will be one-third that of the single-phase current.
A 7.5 kW three phase load will be balanced by the manufacturer. When connected to a three phase source the line current on each phase will be equal.
In a three-phase system, the total load is the sum of the currents in each of the three phases. This is due to the balanced nature of three-phase systems, where the currents in each phase are equal in magnitude but shifted by 120 degrees. The full load of X Amps is the total current drawn by the load across all three phases.
A phase current is the current passing through a phase, whereas a line current is the current flowing through a line.In the case of a balanced delta-connected load, IL = 1.732 IP. In the case of a balanced star-connected load, IL = IP.For unbalanced loads, these relationships don't hold true, and must be individually calculated.
You will need to determine the power per phase, and add them up to give the total power of the three-phase load. To do this, you will need to multiply the phase-voltage by the phase current by the power factor -for each phase.
All transformers, single phase or three phase have a "no-load current" rating. That is simply the nameplate rating of the Xformer in VA, (volt-amps) or KVA (1000Volt-amps) for larger Xformers. Simply divide the nameplate rating in VA or KVA by the supply voltage and you'll get the Xformers potential maximum output in ampheres.
A balanced three phase system is where the currents into the loads placed on all three phases of the service are reasonably close to each other in amperage.Another opinionA 'balanced' three-phase system describes a three-phase load in which each phase current is identical in both magnitude and phase. If the phase currents are only 'reasonably close', then the load is not balanced.
The limit or range of the neutral current in an unbalanced three phase system is the third harmonic in single phase non-linear load current is the major contributor to neutral current.
If the load is connected in wye (star) and it has a neutral, then the vectorial-difference of the phase currents will flow in the neutral and there will be no problem. On the other hand, if there is no neutral, then an unbalanced load would cause unbalanced phase voltages.
Maximum load current on a 140KVA, three phase transformer when the output voltage is 115 v phase to phase is: 140kva / sqrt (3) / 115 = 703 Amps. frequency does not matter here.
A balanced three phase load is where the current flowing in all three phases of the load are reasonably close to each other.Another answerWhen the voltage and measured current draw do not deviate by more than 2 percent under load.AnswerA balanced three-phase load is one in which each of the three loads is identical in all respects (magnitude and phase). Further to the first answer, the three line currents must not all be 'reasonably close', they must be identical -i.e. the same value and phase relationship.
A three-phase load reactor is an inductive device used to limit the inrush current and improve the power factor in three-phase systems. It consists of three coils, each connected in series with one of the phases of the load. When current flows through the reactor, it creates a magnetic field that opposes changes in current, thereby smoothing out current fluctuations and reducing harmonic distortion. This helps protect equipment from voltage spikes and enhances overall system stability.