Best Answer

1/4" per ft. is the lowest allowed.

1. Allowed by whom? Not many regulatory authorities specify the minimum slope of a 6" sewer pipe.

2. Why state in inches, typically engineers use a 2.0% or 0.02 / 100' form for the answer.

3. Using Manning's of 0.013 (although most PVC could use a 0.009 or 0.011 n factor, you can achieve the 2 ft/sec typical requirement with a slope of 0.005 or 0.5%, although it was stated to me that 0.0067 or 0.67% is the correct minimun slope to use. I am just trying to find that source which is tough as most authorities do not specify the minimum slope of a 6" pipe.

User Avatar

Caroline Cronin

Lvl 10
2y ago
This answer is:
User Avatar
More answers
User Avatar

Wiki User

15y ago

Depends on how many fixture units are being served .... Normally 1/8 in per ft

This answer is:
User Avatar

User Avatar

Wiki User

13y ago

1/8" per ft.

This answer is:
User Avatar

User Avatar

Wiki User

11y ago

1/8 to 1/4 inch drop per foot of length.

This answer is:
User Avatar

Add your answer:

Earn +20 pts
Q: What is the minimum slope for 6 inch underground sewer pipe?
Write your answer...
Submit
Still have questions?
magnify glass
imp
Related questions

What is the minimum slope permitted for 2.5 inch underground sewer pipe?

It really depends on your local building code, but 2% should be the minimum so that your pipe will be self-cleaning.


What is the minimum slope permitted for 8 inch underground sewer pipe?

1/16 PER IN PER FT. But the Fixture unit value decreases to only 1440 as opposed to 7300 at 1/2 Pitch.


What is the maximum slope for 4 inch sewer pipe?

1/8th per inch


What is the minimum slope permitted for 4 inch underground sewer pipe?

A slope of 1/4" in 12' is 0.0017 - inadequate for cleansing; it should be at least 0.0084 to produce a reasonable flow velocity of 2 ft/sec. The metric slope I was informed is 18mm in 1000mm Most codes require a 1/4" slope for each 12" of run.


What slope to use on sewer drain lines?

One eighth inch drop per foot of run.


What is the minimum fall for a 4 inch sewer pipe?

1/8" per foot.


How much slope per foot toilet drain?

All drains slope 1/4 inch per foot, minimum. Too much slope,though, can mean pulling water out of the trap or goose neck on a toilet.


What should the slope be for a shower PVC drain pipe in a home?

One-quarter inch per foot is both the standard practice all around the country and the minimum slope (or grade) allowed by most codes. If maintaining that much slope is a problem, an exception can be requested from the administrative authority.


How big is a sewer rod?

A sewer "rod" is normally no larger then 3/8 of an inch diameter BUT a SEWER Cable can be as large as 11\4" even the small sewer rods can have large heads to maintain sewers as large as 36"


What is the correct amount of pitch for 6 inch diameter sewer pipe?

.25 per inch per foot


What is the minimum pitch requirement on a roof?

the pitch of a 7-12 roof slope meaning that for 12" of horizontal measurement (roof run) the vertical measurement (roof rise) is 7". Not totally sure but I believe the minimum to be about a 3-7 inch pitch 3 inch roof rise per 7 feet of horizontal measurement


What is the Level of drop for sewer drain?

1/8 inch per foot