Related Questions

Where is the bulb of the TXV mounted on?

end of the evaporator on the suction line


Effect of moisture on thermostatic expansion valve?

None, a TXV operates by it's sensing bulb sensing superheat of the suction line as it exits the evaporator coil.


Equalizing lines should be located in multiple condenser and compressor applications where Between condenser and evaporator coils or Near the TXV or Between compressors and condensers or None of them?

oppisite side of txv sensing bulb on outlet of evaporator (suction line)


Will the Evaporator Pressor Regulating valve close if the Thermostatic Expansion Valve is in the evaporator air stream?

The EPR valve should work reguardless of if the TXV is in the air stream. The TXV in the airflow shouldn't make it act any different since it is sensing the temperature at the bulb instead of at the valve it's self.


How can you install an txv?

To install a thermal expansion valve (TXV), first, ensure the system is off and properly evacuated. Remove the old valve and clean the mounting surfaces before installing the new TXV, ensuring it aligns with the refrigerant lines. Secure it in place with the appropriate hardware and connect the sensing bulb to the suction line as specified by the manufacturer. Finally, check for leaks, recharge the system, and test the operation.


What is the purpose of the external equalizer on a TXV?

The purpose of the External equalizer on the TXV is to compensate for the pressure drop in the evaporator coil , This is done since the superheat calculation is based on the difference in the Saturation temperature corresponding to the Suction pressure (Measured after the coil) and the actual suction line temperature. Now, in a TXV measurement of actual line temperature is accomplished by using the Sensing Bulb and the Measurement of the Suction pressure by the External Equalizer of the TXV. The opening/Closing of the Expansion valve is controlled by the setting of the superheat which is governed by the setting of the Spring.


What is the function of equalising line in Thermostatic expansion valve?

The equalizing line in a thermostatic expansion valve (TXV) serves to balance the pressure between the sensing bulb and the valve body. This pressure equalization allows the TXV to respond accurately to changes in evaporator temperature, ensuring optimal refrigerant flow. By maintaining this balance, the equalizing line helps regulate the superheat level, enhancing the system's efficiency and preventing issues like flooding or starvation of the evaporator.


What is a heat sensing bulb?

A heat sensing bulb is a specialized light bulb that includes a sensor to detect temperature changes. These bulbs are often used in devices such as heat lamps and incubators to help regulate temperature and prevent overheating. The sensor in the bulb triggers the light to turn on or off based on the surrounding temperature.


What is the different between exv and txv?

Difference between txv and exv.


What causes the low side pressure in commercial air conditioner to hunt?

The metering device is sensing and adjusting /throttling in many case, it depends on in what part of the operation /cycle this happens? is it at the beginning? or the end? or the whole time? TXV sensing bulbs can lose their charge, the power head too, the position of the sensing bulb should be at 3 or 9 o'clock not at 12 or 6 due to liquid refrigerant being in the bottom of the suction line at times. During a hot pull down suction line pressures will hunt in times of pulling down a hot room or box . A restriction can do this as well.


Which type of remote-sensing system records electromagnetic radiation using a satellite-mounted sensor?

a compass


Don't burn bulb base up?

Unavoidable in certain situations. Light fixtures are sometimes mounted in the ceiling - the bulb must then be mounted base up or base horizontal.