1o amper
The kW rating of a transformer can be calculated by multiplying the kVA rating by the power factor. For example, if the power factor is 0.8, then the kW rating of a 100 kVA transformer would be 80 kW. You can also use the formula: kW = kVA x power factor.
The question isn't correct, you have to define the voltage level not the power rating.
An ELSP is a current limiting fuse used in series with the primary fuse of a transformer.
Sounds like the wrong size fuse protection was used. The transformer should be protected to its kva capacity.
A 100kVA transformer is rated for...100kVA. That is its' power rating, and it is based off the current that is flowing through the transformer (the I^2*R losses are the limiting factor). This can be 80kW and 60 kVARs, or 100kW and 0 kVARs, or 100kVARs, or anywhere inbetween.Another AnswerThe 'power' rating of a transformer is the product of its secondary voltage and its secondary current, expressed in volt amperes or multiples thereof. It's not expressed in watts, because to know the 'true power' of the transformer, the manufacturer will need to know the power factor of the load, and that could vary considerably. Incidentally, the symbol for kilovolt ampere is 'kV.A', not 'kVa'.
In series to every phase winding of transformer.
For an 800 kVA transformer, the size of the fuse depends on the primary and secondary voltage levels. A common rule of thumb is to use a fuse rating of about 125% of the transformer's full-load current. For an 800 kVA transformer at a standard voltage of 480V, this typically results in a fuse size of around 1,200 to 1,500 Amps, but it's essential to consult the manufacturer's specifications and consider local regulations for precise sizing. Always ensure that the fuse is selected based on both the transformer and application requirements.
50 amp
Yes, but it's usual to have fuses on both sides of the transformer.
It's not - I have seen 50kVA, 100kVA,...15000kVA, 36000kV, 180000kVA to name a few examples. Near where I live, I don't believe there are more than a few transformers rated in multiples of 11 as you state.
the INside
Lower the rating of the primary fuse feeding the transformer.