12 Lead, Single Voltage, Wye Start - Delta Run. Wye start; L1 to 1 and 7. L2 to 2 and 8. L3 to 3 and 9. All joined together 6,12,4,10,5 and 11.
Delta run; L1 to 1, 6, 7, and 12. L2 to 2, 4, 8, and 10. L3 to 3, 5, 9, and 11.
To reverse the direction of the motor interchange L1 and L2 of the supply voltage.
It is not advisable to run lower voltage motor on a higher voltage.
DC motor: Switch your leads. AC single phase motor: Direction cannot be changed. The motor will run the same direction regardless of how your leads are terminated. AC 3 phase motor: Switch any two leads.
no load means the motor is acting like a coil
Any two legs of a three phase system are classed as single phase. So yes a single phase motor will operate when connected. Be sure to use the proper motor protection devices to control the motor.
To see if the motor is three phase or single phase look at the motor's nameplate. There it will tell you what the voltage needs to be and what system phase the motor needs to be connected to operate properly.
It is not advisable to run lower voltage motor on a higher voltage.
Generator coils generate the voltage, motor coils use the generated voltage.
It is possible to run a DC motor on a 3-phase supply using a full-wave rectifier if the voltage is right.
Its a servo.
Yes. If voltage leads the current, the impedance is inductive (this would be the case if the load is a motor). If current leads the voltage, the impedance is capacitive (this would be the case for a CFL light bulb).
Ac voltage
the three phase dc motor never seen yet motor eaither 3phase m/r or dc motor.
Which starter is best for 7.5 hp 3phase motor?Read more: Which_starter_is_best_for_7.5_hp_3phase_motor
depending on 1phase or 3phase voltage motor , the amphere requirement is found outfor 3phase AC motor use this formula: (HP x 746)/(1.73 x E x Eff x PF)for 1phase AC motor : (HP x 746) / (E x Eff x PF)
If switching the leads on a 3-phase motor did not result in a reversal of direction, it could be due to incorrect lead identification or a faulty switching mechanism. Double-check the connection diagram for the motor and ensure that you are switching the correct leads. If the issue persists, there may be a problem with the motor itself that requires further investigation or professional assistance.
Into units of what?
Yes it can run when single phasing in a delta configuration but the motor will not start from a dead stop. There will be quite a bit of degradation in its operation from its nameplate data.