Restricted earth fault protection is used to protect a specific zone, and should not trip for a fault outside of that zone (usually limited to a transformer, and possibly extending to lowside, highside, and tertiary breakers).
There is such a thing as a three phase to earth fault, so maybe this is what you mean by a "balanced earth fault". I don't believe any earth or ground currents would flow in this case. A restricted earth fault is a typical phase to earth fault, where the zone of protection is restricted to a specific area, such as around a transformer. "Restricted" is referring to the protection method, not what is actually going on with the currents and voltages.
An isolation transformer is a mutual transformer having a voltage ratio of 1:1, so that the secondary circuit is electrically isolated from the primary circuit, yet subject to the same voltage.An earth protection relay is a category of protective relay that responds to an earth fault monitored by a current transformer (CT). In the event of an earth fault being detected by the CT, the relay with activate the trip circuit to a circuit breaker which will then disconnect the fault.
Sensitive Earth Fault protection is required to either to alarm or trip the faulted circuit. It is usually used for resistance grounded or ungrounded systems; where first earth fault doesn't interrupt supply. It is also used on long overhead lines (even solidly grounded systems) where earth fault currents can be significantly low.
To prevent overheating/damage/fire of the electrical components in a circuit.
The purpose of an earthing (protective) conductor in a residential installation is to allow sufficient fault current to flow, in the event of an earth fault, to enable the operation of the circuit's overcurrent protection device (fuse or circuit breaker), so its resistance must be sufficiently low to allow this to happen.
There is such a thing as a three phase to earth fault, so maybe this is what you mean by a "balanced earth fault". I don't believe any earth or ground currents would flow in this case. A restricted earth fault is a typical phase to earth fault, where the zone of protection is restricted to a specific area, such as around a transformer. "Restricted" is referring to the protection method, not what is actually going on with the currents and voltages.
I'm guessing this is in reference to a restricted earth fault, and you want to know what the opposite is? Restricted earth fault protection is designed to operate for earth faults within a specific zone. Unrestricted protection will operate for faults "anywhere", as long as the pickup can be satisfied. For example, REF (restricted earth fault) transformer protection looks for a small amount of neutral current, and if this exists, and the relay identifies this current as being within the zone of protection, the relay will trip. If it were unrestricted, the small amount of neutral current alone would be enough to cause a trip.
Requirement of REF protection for 50KVA 11KV/.4KV transforemr
A Restricted Earth Fault (REF) means an earth fault from a restricted/localized zone of a circuit. The term "REF protection method " means not to sense any earth faults outside this restricted zone. REF is a type of "unit protection" applied to transformers or generators and is more sensitive than the method known as differential protection. An REF relay works by measuring the actual current flowing to earth from the frame of the unit. If that current exceeds a certain preset maximum value of milliAmps (mA) then the relay will trip to cut off the power supply to the unit. Differential protection can also be used to protect the windings of a transformer by comparing the current in the power supply's neutral wire with the current in the phase wire: if the currents are equal then the differential protection relay will not operate; if there is a current imbalance then the differential protection relay operates. However, REF protection is also applied to transformers in order to detect ground faults on a given winding much more sensitively than differential protection can do.
An isolation transformer is a mutual transformer having a voltage ratio of 1:1, so that the secondary circuit is electrically isolated from the primary circuit, yet subject to the same voltage.An earth protection relay is a category of protective relay that responds to an earth fault monitored by a current transformer (CT). In the event of an earth fault being detected by the CT, the relay with activate the trip circuit to a circuit breaker which will then disconnect the fault.
Sensitive Earth Fault protection is required to either to alarm or trip the faulted circuit. It is usually used for resistance grounded or ungrounded systems; where first earth fault doesn't interrupt supply. It is also used on long overhead lines (even solidly grounded systems) where earth fault currents can be significantly low.
No, a circuit protection device must open the circuit on a fault current or overload.
Protective devices - relays, CT,PT, isolators, circuit breakers are used for fault protection. Fault protection means If there is a fault in the circuit, the circuit must be cut off before any damage occurs due to fault.
A Fuse or a circuit breaker can be used to protect an electric circuit from over loads. A surge arrestor / over voltage relay can be provided for voltage protection An ELCB/ Earth fault Relay may be provided for earth fault protection. Electrix Chennai, India.
Short circuit fault.
A Restricted Earth Fault (REF) refers to a method of fault protection that is applied to electrical system units, such as transformers or generators, that is more sensitive than the method known as Differential Protection (DP).An REF relay works by measuring the actual current flowing to earth from the frame of the unit. If that current exceeds a certain preset maximum value of milliamps (mA) then the relay will trip to cut off the power supply to the unit.REF protection is applied on transformers in order to detect ground faults on a given winding more sensitively than when only using differential protection.Differential Protection is commonly used to protect the windings of a transformer by comparing the current in the power supply's neutral wire with the current in the phase wire. If the currents are equal then the DP Relay will not operate. If there is a current imbalance then the DP Relay operates.REF and DP protection devices operate in similar ways to a GFCI or RCD device, which combines both REF and DP functions inside the one single device.For more information about GFCIs and RCDs, please see the answer to the Related Question shown below.
To prevent overheating/damage/fire of the electrical components in a circuit.