answersLogoWhite

0

short circuit and fault current are not related or comparable practically or mathematically. a short circuit is a break down in insulation causing contact between live/line conductors. fault current is different. it is measured in the value kA and is the benchmark as to whether your overcurrent device is adequate. this is determined by measurement or enquiry to the local provider.ohms law applies- I=V divided by R.

User Avatar

Wiki User

12y ago

What else can I help you with?

Continue Learning about Natural Sciences

What is the difference between trench and fault?

putapete


How is restricted earth fault called so how is it restricted?

A Restricted Earth Fault (REF) refers to a method of fault protection that is applied to electrical system units, such as transformers or generators, that is more sensitive than the method known as Differential Protection (DP).An REF relay works by measuring the actual current flowing to earth from the frame of the unit. If that current exceeds a certain preset maximum value of milliamps (mA) then the relay will trip to cut off the power supply to the unit.REF protection is applied on transformers in order to detect ground faults on a given winding more sensitively than when only using differential protection.Differential Protection is commonly used to protect the windings of a transformer by comparing the current in the power supply's neutral wire with the current in the phase wire. If the currents are equal then the DP Relay will not operate. If there is a current imbalance then the DP Relay operates.REF and DP protection devices operate in similar ways to a GFCI or RCD device, which combines both REF and DP functions inside the one single device.For more information about GFCIs and RCDs, please see the answer to the Related Question shown below.


Difference between thrust and reverse fault?

There is a slight difference. A thrust fault is a variety of reverse fault with a dip angle of less than 45 degrees.


What is the difference between fault lines and plate boundaries?

Fault lines are fractures in Earth's crust where movement has occurred, while plate boundaries are the regions where tectonic plates meet and interact. Fault lines can be found within a single plate or at plate boundaries, where they are associated with seismic activity due to the movement of tectonic plates.


What is the difference between earthquauke and fault?

An earthquake is the shaking of the ground caused by a sudden release of energy in the Earth's lithosphere. A fault is a fracture in the Earth's crust where movement has occurred, resulting in the displacement of rocks on either side of the fracture. Faults are often associated with earthquakes as they are the zones where seismic energy is released.

Related Questions

What is the difference between balanced earth fault and restricted earth fault?

There is such a thing as a three phase to earth fault, so maybe this is what you mean by a "balanced earth fault". I don't believe any earth or ground currents would flow in this case. A restricted earth fault is a typical phase to earth fault, where the zone of protection is restricted to a specific area, such as around a transformer. "Restricted" is referring to the protection method, not what is actually going on with the currents and voltages.


What is the difference between a fault and a fold?

a fault is a large crack in the earth. a fold is when the ground gets bent.


Restricted earth fault protection circuit?

Restricted earth fault protection is used to protect a specific zone, and should not trip for a fault outside of that zone (usually limited to a transformer, and possibly extending to lowside, highside, and tertiary breakers).


What is a restricted earth neutral system?

appropriate resistance is to be inserted between the neutral point of the transformer and the earthing mat to restricted earth fault current. for this purpose a sensitive earth leakage relay is used. in the event of a fault, fault current returning to the system neutral trips an earth leakage relay and disconnects the supply. anand r. ambekar


What is the difference between a crack in the earths crust and a fault?

A crack in the Earth's crust is a fracture where rocks have pulled apart, whereas a fault is a fracture where there has been movement along the fracture plane. In other words, a fault is a type of crack in the Earth's crust that has undergone displacement.


What is an Unrestricted Earth Fault?

I'm guessing this is in reference to a restricted earth fault, and you want to know what the opposite is? Restricted earth fault protection is designed to operate for earth faults within a specific zone. Unrestricted protection will operate for faults "anywhere", as long as the pickup can be satisfied. For example, REF (restricted earth fault) transformer protection looks for a small amount of neutral current, and if this exists, and the relay identifies this current as being within the zone of protection, the relay will trip. If it were unrestricted, the small amount of neutral current alone would be enough to cause a trip.


What is the difference between trench and fault?

putapete


What the difference between an earthquake and a fault?

n


What is the difference between Earth Fault Relay and Earth Leakage Relay?

Earth leakage relays are instantaneous tripping relays where as earth fault relays have the option of time and ampere setting i.e. for a setted ampere the circuit breaker will be tripped off after the setted time (in second).


How is restricted earth fault called so how is it restricted?

A Restricted Earth Fault (REF) refers to a method of fault protection that is applied to electrical system units, such as transformers or generators, that is more sensitive than the method known as Differential Protection (DP).An REF relay works by measuring the actual current flowing to earth from the frame of the unit. If that current exceeds a certain preset maximum value of milliamps (mA) then the relay will trip to cut off the power supply to the unit.REF protection is applied on transformers in order to detect ground faults on a given winding more sensitively than when only using differential protection.Differential Protection is commonly used to protect the windings of a transformer by comparing the current in the power supply's neutral wire with the current in the phase wire. If the currents are equal then the DP Relay will not operate. If there is a current imbalance then the DP Relay operates.REF and DP protection devices operate in similar ways to a GFCI or RCD device, which combines both REF and DP functions inside the one single device.For more information about GFCIs and RCDs, please see the answer to the Related Question shown below.


What is the difference between an earthtquake and a fault?

The same as between running and legs.


Calculation of restricted earth fault relay stabilizing resistor?

Requirement of REF protection for 50KVA 11KV/.4KV transforemr