100MVA
It is the rated maximum current that can be taken from the transformer. This is equal to the VA rating divided by the output voltage. So a 6 kVA 240 v transformer would have a maximum current rating of 6000/240 or 25 amps.
100
Divide VA rating with the Voltage and get Amp rating. So say you have a transformer that delivers 26V, 80VA, that means a maximum current of 80/26=3.07A for a resistive load.
the efficiency is maximum in a transformer when no load loss is equal to load loss.
Knowing the power rating of a transformer will help an operator use the transformer within its design limitations with regard to heating of the windings and their insulation.
The maximum efficiency condition in distribution transformer is said to be occurred when iron loss = copper loss
It is the rated maximum current that can be taken from the transformer. This is equal to the VA rating divided by the output voltage. So a 6 kVA 240 v transformer would have a maximum current rating of 6000/240 or 25 amps.
All transformers have a power rating given in kVA which determine the maximum load that can be connected to that transformer.
Transformer rating is based on the maximum temperature a transformer can run at. This temperature is dictated by the amount of current flowing through the transformer windings. This is why transformers are rated in KVA (voltage * current), not kW - it doesn't matter what the phase relationship is between voltage and current, just the magnitude of the current.
A transformer has separate ratings for maximum voltage and maximum current. Both limits must be observed. The maximum voltage is set by the magnetic flux density in the core, while the current limit is set by the size of the wire used in the primary and secondary windings. Multiplying the two together gives the VA or kVA rating.
it is depends on the rating of distribution transformer,e.g if there is 100 kva, then it will take 5.25amp.
No because the current rating of the transformer is a maximum allowable current. If the computer still takes 3.42 amps it will be OK provided the new transformer supplies the correct voltage.
An electricity board will be fixed some amount of load for consumer (industry or commercial) as per consumers requirement.That is maximum load or maximum demandAnswerA 'maximum demand indicator' (also called a 'thermal demand indicator') is a thermally-operated measuring instrument which indicates the maximum current supplied by a distribution transformer, from which that transformer's actual (rather than anticipated) maximum load can be determined. A distribution transformer is sized based on an anticipated load, resulting from an analysis of the loads to be supplied (taking into account after-diversity maximum demand), this instrument allows the actual maximum load to be compared with that calculated load, and this value should be less if the original analysis was performed correctly.
A distribution transformer IS the term used to describe the utility transformer which supplies a residence.
Depends on the kva rating of the devices to be tested using a transformer.
100
Divide VA rating with the Voltage and get Amp rating. So say you have a transformer that delivers 26V, 80VA, that means a maximum current of 80/26=3.07A for a resistive load.