This is a voltage drop question. To answer is question the voltage must be stated.

User Avatar

Wiki User

12y ago

What else can I help you with?

Continue Learning about Electrical Engineering

What size conductor is needed to carry 25 amps 120 volt AC over 400 feet?

A #4 copper conductor will limit the voltage drop to 3% or less when supplying 25 amps for 400 feet on a 120 volt system.


What is the cable size for 90 kw motor?

Depends upon the voltage. The formula for amperage or (wire size) is Watts / Voltage. If the voltage is 220 volts, then the amperage would be over 400 amps. This would require a large wire size to run it. If it were 440 volts, the amperage would be 1/2 or 200 amps. That would require a smaller wire size. As the voltage goes up, the amperage goes down. At a thousand volts, the amperage would only be 90 amps. A wire gauge or size of a #2 would carry 90 amps for small distances.


Cable size for 100kw 3phase with 175meter length?

2.5 mm twin and earth should do the trick. A 100 kw @ 400 V, 50 Hz,3 Phase at a power factor approximately 0.8 will draw a current ( 100x1000/root 3x400x0.8 )=180.42 A. Breaker rating to be 200A TP MCCB and cable size to be minimum 4 Core 120 mm2 .


What cable size is needed for 415VAC 3 Phase 400kVA generator to a load 50meters away?

As example, at 380V the generator produces 685A per phase. Therefore you will require 2 x 120mm2 cables per phase. (1 x 120mm2 cable will support 365A per phase). In total you will require approximately 1/2km of cable to cover the 50m run between the generator and the ATS panel/Load. i.e. 5 phases in total - 2 x 50m cables per phase.


How many amps is 400 kcmil good for?

The ampacity of a 400 kcmil (thousand circular mils) conductor depends on factors such as the conductor material (copper or aluminum), insulation type, and installation conditions. For example, a 400 kcmil copper conductor can typically carry around 400 to 600 amps at standard temperature ratings in open air or conduit, while an aluminum conductor of the same size may carry slightly less. Always refer to the National Electrical Code (NEC) and local codes for precise applications and ampacity tables.

Related Questions

What is the cable size required for a 400 amp and 350 amp load?

350mcm


For 100kw which cable size is good and how to find out cable size?

100 kw is the power drawn by the load. to calculate the cable size you need to know the voltage. From that you can calculate the current. this decides the cable size. for example if the voltage is 400Volts then the current flowing in the circuit when the load is 100 KW will be 250 amps. (100,000/400). for 250 amps to flow with out causing excessive heating of the cable the cross sectional area of the copper cable should be 150 sq mm.for a round cross section the diameter will be roughly 15mm.


What has a maximum speed of 400 Mbps?

A Fire Wire 400 cable.


Is Boeing 747 or 777 is bigger?

777-300 can carry 550 passengers; 747-400 can carry 400 passengers


How much current does 300 sq mm cable carry?

A 228 sq mm conductor equates to 450 MCM. A conductor of 450 MCM is not a standard AWG wire size. A standard 400 MCM will carry 380 amps. A standard 500 MCM will carry 430 amps. Difference between 400 and 500 MCM amperage's is 50 amps. Transposing between the two amperage's of 50 amps will be 380 + 25 = 405 or 430 - 25 = 405 amps. This is a very rough calculated answer for the question.


How much kilograms can one camel carry?

they can carry 2200


Where is throttle cable in Lexus sc 400?

The throttle cable is located on top of the throttle body.


What will be the recommended size cable size for 400 KVA transformer?

3r x 300sq.mm Al. ar UG cable <<>> Wiring is sized by the amperage that is used by the load. The formula for amps is I = W/E. Amps = Watts (or VA)/Volts. As you can see an answer can not be given unless a voltage is stated. The lower the primary voltage the larger the amperage will be and likewise the larger the wire size will be.


Does a 4corex630 sq mm cable carry the same current as a single core 630 sq mm cable?

4-core 630 mm-sq cable sounds like 4 cores each of 630 mm-sq as used on 400 kV power lines, in which case it carries 4 times the current.


What is the cable size for 3.7 kw 3 phase motor?

It depends on more than Wattage or horsepower. In your question, you also need to mention line Voltage, power factor, and whether single or three-phase. Cable size is based on current, so we need to know everything to calculate current.


What size conductor is needed to carry 25 amps 120 volt AC over 400 feet?

A #4 copper conductor will limit the voltage drop to 3% or less when supplying 25 amps for 400 feet on a 120 volt system.


What size service cable is required for 120 volt 150 amp direct bury 400 feet single phase?

A 1000 MCM copper conductor will limit the voltage drop to 3% or less when supplying 150 amps for 400 feet on a 120 volt system.

Trending Questions
What is value of current you in adjoining circuit? What are convectional and non convectional methods of speed control of a induction motor? Can indoor Romex wiring be used outdoor as long as it is inside of PVC conduit? What would happen to a series circuit if another bulb was added? Why can some birds land on high voltage lines without getting shocked and and some can't? Can a capacitor be gradually charged by lesser capacitors? What is the numerical value of the Bridge Priority held by Catalyst switches? A step-up transformer has 300 turns on the primary coil and 90000 turns on the secondary coil if the current flowing through the secondary is 5 amps what is the current flowing in the primary? How does a transducer converts any form of energy into electricity? Will decreasing the resistance in a circuit decrease current flow if voltage is kept constant? Why at resonance the voltage drop across inductance and the voltage drop across capacitance is greater than the source voltage? Can branch circuits from a panel be pulled in the same conduit if not exeeding the conduit fill requirements? What is the function of door interlock and defeat interlock in an Air Circuit Breaker for an electrical control panel? How does the variation of excitation of an alternator correct power factor? Why a 5amp. rating ammeter is connected to secondary side of current transformer? Why are transformer used with power tools? How can you cut an energized conductor? What does SMPS stand for? Who is responsible for coordinating EMF surveys and measurement activities with command and supervisory personnel? Meaning of recovery voltage?