Since this transformer has a ratio of 1:2 the load current on the 480V side just has to be doubled. 85 x 2 = 170A on the primary. 40.8 KVA transformer. To prove this just find the KVA of both sides and they should be equal.
To wire a 15 kW dry type transformer for a 240V to 480V configuration, first ensure that the transformer is rated for this voltage conversion. Connect the primary side to the 240V supply by connecting each of the two primary terminals to the respective phases of the 240V supply. For the secondary side, connect the output terminals to the load requiring 480V, ensuring that the load is compatible with the transformer rating. Always follow local electrical codes and safety standards, and consider consulting a licensed electrician for installation.
Ohms law says that watts are equal to volts times amps. 240v X 13.5a = 3240 va VA / 1000 = Kva So, your load requires 3.24 Kva. The transformer should have a rating greater than this as a safety factor, so you would choose the next larger size, in this case probably a 5 Kva transformer with a 480v primary and a 240v secondary. Your local electrical codes may require a larger safety factor, so you would want to consult them before buying the transformer!
For an 800 kVA transformer, the size of the fuse depends on the primary and secondary voltage levels. A common rule of thumb is to use a fuse rating of about 125% of the transformer's full-load current. For an 800 kVA transformer at a standard voltage of 480V, this typically results in a fuse size of around 1,200 to 1,500 Amps, but it's essential to consult the manufacturer's specifications and consider local regulations for precise sizing. Always ensure that the fuse is selected based on both the transformer and application requirements.
To find the output in amps for a single-phase transformer, you can use the formula ( \text{Amps} = \frac{\text{VA}}{\text{Volts}} ). For a 1000 VA transformer operating at 480 V, the output current would be ( \frac{1000 \text{ VA}}{480 \text{ V}} \approx 2.08 \text{ A} ). This is the output current at 480 V. If you need the output at 240 V, it would be ( \frac{1000 \text{ VA}}{240 \text{ V}} \approx 4.17 \text{ A} ).
208 v. equipment is a little smaller and cheaper, and 208v. is slightly safer to use. However, 480v. runs on half the amperage 208v. equipment does, which means equipment or devices cost almost 50% less to operate. With respect to energy consumption, the answer above is incorrect. It is true that equipment that operates at 480v does operate at roughly half the amperage vs. 208v, however, it operates at over twice the voltage. Your local power company charges you per kilowatt hour (voltage x amperage), not on amperage alone. Example, a 208v motor that draws 10 amps would consume (208v x 10a) 2.080 kilowatts per hour. The same motor on 480v would draw roughly half, 4.3 amps (480v x 4.3a) and would also consume 2.080 kilowatts per hour. So in terms of power consumption, they are virtually the same. The main reasons one would opt for higher is the fact that you can install smaller wire and you can run longer distances. It's a ratio that is directly proportional (at least with electric motors/inductive loads). If you were comparing a 240v motor to a 480v motor the ratio would be exact, if a 480v motor draws 5 amps, the same motor on 240v would draw 10 amps.
3
To wire a 15 kW dry type transformer for a 240V to 480V configuration, first ensure that the transformer is rated for this voltage conversion. Connect the primary side to the 240V supply by connecting each of the two primary terminals to the respective phases of the 240V supply. For the secondary side, connect the output terminals to the load requiring 480V, ensuring that the load is compatible with the transformer rating. Always follow local electrical codes and safety standards, and consider consulting a licensed electrician for installation.
Sounds like the wrong size fuse protection was used. The transformer should be protected to its kva capacity.
Ohms law says that watts are equal to volts times amps. 240v X 13.5a = 3240 va VA / 1000 = Kva So, your load requires 3.24 Kva. The transformer should have a rating greater than this as a safety factor, so you would choose the next larger size, in this case probably a 5 Kva transformer with a 480v primary and a 240v secondary. Your local electrical codes may require a larger safety factor, so you would want to consult them before buying the transformer!
The amps you can get from a 500 kVA transformer would depend on the voltage of the transformer's output. To calculate amperage, you can use the formula: Amps = Power (kVA) / Voltage. For example, if the output voltage is 480V, you would get approximately 1041 amps (500 kVA / 480V).
You can use a step-up transformer. Transformers are rated in primary voltage, secondary voltage, kVA, phases (single and three) and other parameters then equipped with indoor and outdoor enclosures. Be sure to consult a professional engineer or electrician when choosing and installing a step-up transformer. There are several NEC issues involved as well as choosing a transformer that is right for the type of load you have. One without the proper licensing AND knowledge of transformer circuits should never install 480V wiring or transformers.
to derive 120 volts from 480 volts you have to use a transformer, based on your needs. If you needed 100 amps at 120 volt single phase you would need a 12kva transformer. This is just an example.
No, a 1500KVA transformer is not large enough to handle a 1600A load at 480V. The transformer should have a higher kVA rating to support the current demand of 1600A. A transformer with a minimum capacity of 1920KVA would be needed for this application.
The primary feed for a 480V to 208V, 100 amp panel in a three-phase system typically consists of three phases (L1, L2, L3) and a neutral wire, coming from a step-down transformer designed to convert the higher voltage to the lower voltage. The transformer will have a primary side connected to the 480V supply and a secondary side that outputs 208V. Additionally, proper grounding must be ensured for safety and compliance with electrical codes. The panel will distribute the 208V power to various circuits as needed.
An exact breaker size can not be given because the voltage, and hence the calculation for current, is not given. A transformer shall be protected by an over current device that is not rated at more that 150% of the primary current.
Five wires. Two on the primary side, connected to each 120V leg, giving a primary voltage of 240V. Two on the secondary side, one connected to neutral, and the other the new 480V hot. One connecting the frame of the transformer and the box containing it to ground. Note: you will only get one phase power out of this configuration - to get three phase output, you need three phase input, three transformers, and a lot more wires.
Not directly, you would need to transform 480v circuit to 120v with a transformer first.