208 v. equipment is a little smaller and cheaper, and 208v. is slightly safer to use. However, 480v. runs on half the amperage 208v. equipment does, which means equipment or devices cost almost 50% less to operate.
With respect to energy consumption, the answer above is incorrect. It is true that equipment that operates at 480v does operate at roughly half the amperage vs. 208v, however, it operates at over twice the voltage. Your local power company charges you per kilowatt hour (voltage x amperage), not on amperage alone.
Example, a 208v motor that draws 10 amps would consume (208v x 10a) 2.080 kilowatts per hour.
The same motor on 480v would draw roughly half, 4.3 amps (480v x 4.3a) and would also consume 2.080 kilowatts per hour.
So in terms of power consumption, they are virtually the same. The main reasons one would opt for higher is the fact that you can install smaller wire and you can run longer distances.
It's a ratio that is directly proportional (at least with electric motors/inductive loads). If you were comparing a 240v motor to a 480v motor the ratio would be exact, if a 480v motor draws 5 amps, the same motor on 240v would draw 10 amps.
It is the line to line voltage divided by 1.73. 600V / 1.73 = 347V 480V / 1.73 = 277V 380V / 1.73 = 220V 208V / 1.73 = 120V
1kw=1.25kvaby this relation 75kva=60kwp=1.732*380*I*1I=60000/1.732*380*1I=91AmpsCommentPower factor is irrelevant to this question. You don't need to convert the kV.A rating to kilowatts, simply divide 75 000 V.A by (1.732 x 380). The answer is 114 A.This, of course, assumes that the question refers to a three-phase generator and that 380 V is the line voltage.
yes,
Only one neutral conductor is typically in a 3 phase panel.
for three phase the calculation is 30,000 = 1.73*V*I - simple as that. For single Phase the calculation is 30,000 = V*I - simple as that It is important to note the voltage in the first line is Line to Line (typically how it is specified in three phase power systems), and the second line it is Line to neutral. A 30KVA transformer is the same as 30,000VA to find out the Amps you need to divide the voltage if the transformer is single phase for example: 30,000VA / 480V = 62.5 Amps The calculation for a 3 phase transformer is the VA / voltage / 1.73 for example: 30,000VA /480V / 1.73 = 36.12 Amps
The primary feed for a 480V to 208V, 100 amp panel in a three-phase system typically consists of three phases (L1, L2, L3) and a neutral wire, coming from a step-down transformer designed to convert the higher voltage to the lower voltage. The transformer will have a primary side connected to the 480V supply and a secondary side that outputs 208V. Additionally, proper grounding must be ensured for safety and compliance with electrical codes. The panel will distribute the 208V power to various circuits as needed.
Not directly, you would need to transform 480v circuit to 120v with a transformer first.
Mathematically, just divide 480 by the square root of three. Electrically, 480V refers to the line-to-line value of a three phase system. For example, measure the voltage across A-phase and B-phase and you'll get 480V. 277V is the line-to-neutral value. Measure the voltage across A-phase and the neutral conductor and you should get 277V.
Standard household and business power in the entire US is 120V single phase and 240V double phase. Light industry will likely use 208V three phase, 240V three phase, 400V three phase, 415V three phase, or 480V three phase. Heavy industry and subway systems use higher AC voltages and sometimes DC.
there isnt a high leg in a three phase 480v panel only on 240v panels
It is the line to line voltage divided by 1.73. 600V / 1.73 = 347V 480V / 1.73 = 277V 380V / 1.73 = 220V 208V / 1.73 = 120V
Line voltage equals phase voltage multiplied by the square root of three. a.k.a. E l = E p X 1.73 In a 3 phase 480v system the phase voltage is 277v. Therefore E l = 277 X 1.73 = 480v
In a star configuration, often called "Y", the voltage across one winding is from a phase to ground. Phase to phase you have voltage across 2 windings. And at the risk of confusing you, the phase to phase voltage is not double the other because the windings are only 120 degrees out of phase and not 180 degrees. To calculate this you take the voltage of one winding, 120v for example, and multiply by the square root of 3, or about 1.732, and get 208v. Or you take 277v and get 480v.
That's 277 volts of alternating current. This is typically one phase of a 480v 3 phase system. Don't worry that 3 x 277 adds up to more than 480v. A 277v line is typically one phase of a 480v 3 phase system.
To calculate the current in amps for a 470 kW load on a 480V three-phase circuit, you can use the formula: [ I = \frac{P}{\sqrt{3} \times V \times PF} ] Assuming a power factor (PF) of 1 for simplicity, the current would be: [ I = \frac{470,000}{\sqrt{3} \times 480} \approx 564.5 \text{ amps} ] This means a 470 kW load would require approximately 564.5 amps on a 480V three-phase circuit, assuming a power factor of 1.
At 240v single phase it's 70.8 amps. If it runs on 2 wires plus ground, take the voltage rating of the equipment and divide that into the watts to get amps. At 480v 3 phase it's 25.8 amps. At 208v 3 phase it's 47.2 amps. <<>> There are zero amps in 14 kW. A voltage needs to be stated. I = W/E, Amps = Watts/Volts.
1kw=1.25kvaby this relation 75kva=60kwp=1.732*380*I*1I=60000/1.732*380*1I=91AmpsCommentPower factor is irrelevant to this question. You don't need to convert the kV.A rating to kilowatts, simply divide 75 000 V.A by (1.732 x 380). The answer is 114 A.This, of course, assumes that the question refers to a three-phase generator and that 380 V is the line voltage.