answersLogoWhite

0

Yes, a 60 kVA generator can power a load of 28,000 BTUs, provided it has sufficient capacity. To determine if the generator can handle the load, you need to convert BTUs to watts: 28,000 BTUs is approximately 8,225 watts (using the conversion of 1 BTU/hr = 0.293 watts). Since 60 kVA translates to about 48 kW (assuming a power factor of 0.8), the generator can accommodate the 28,000 BTU load with ample capacity to spare.

User Avatar

AnswerBot

1mo ago

What else can I help you with?

Continue Learning about Engineering
Related Questions

What is 63 Kva generator power to watts?

It could be as much as 63 kW (63,000 Watts) into a load with a power factor of 1.0. For other loads, multiply the kVA by the power factor.


Which is to consider in sizing generator kva or kw ratins?

the unit of generators power is KVA becoze the kva is the power that contain the active power (KW) and the reactive power mean that the name plate of any generator must contain the rated kva of it (like the transformer P (KW) = P (kva) * cos fi P (KW) = V I cos fi for single phase P (KVA) = V I when cos fi closed to 1 this will increase the useful power that exit from the generator or transformer with my pleasure


What is4o kva for generator?

A 40 kVA generator refers to a generator with a power output capacity of 40 kilovolt-amperes. This measurement indicates the apparent power, which is a combination of real power (measured in kilowatts, kW) and reactive power. The actual usable power will depend on the power factor of the generator, typically ranging from 0.8 to 1.0 for most applications. Therefore, a 40 kVA generator can provide between 32 kW to 40 kW of real power, depending on the load and its power factor.


Why kva written on generator?

because the generator generate apparent power in kilos and it is written as ( kilo volt ampere OR KVA) it is the combination of active and reactive powers where active will be used by the consumers and the reactive will come back to the generator.


What is the power of AC generators measured in kW or kVA?

Yes, you can use both, but watts is more useful; it provides the total amount of power the generator can output.


What is size of power cable of 1137 kva generator?

It depends totally on the voltage used.


If generator is 635 KVA what is alternator KVA rating?

635kva


What is the oil perisher for 1500 kva generator?

The oil perisher for 1500 KVA generator is used for the lubrication purposes.


What will happen if you use 50 KVA generator when your requirement is 90 KVA?

If you take out too much power, the generator will probably get damaged. In the best of cases, it has a built-in protection, and shuts down before it gets damaged. In any case, you should avoid taking out more power than the generator can handle; also, you should get a more powerful generator. Or reduce your use.


Can we improve generator power factor for increasing active power?

The 0.8 Power Factor provided by generator manufacturers is not the load power factor, but it is the nominal power factor used to calculate the kW output of an engine to supply the power for a particular alternator kVA output. Alternators are therefore designed to supply their rated kVA at 0.8 lagging power factor.


Is the kva rating of a three phase generator per phase or a total of the three phases example is a 3 phase 75 kva generator 25 kva per phase or 75 per phase?

The kV.A (not 'kva') rating is the total apparent power of the machine. So a 75 kV.A machine is 25 kV.A per phase.


How many KVA Generator requeired for 1 ton window ac?

A 1-ton AC can melt a ton of ice in 24 hours. The power needed is theoretically 3517 Watts so allowing for power factor and efficiency you would need a 7 kVA generator.