A voltage level of 480 volts is the working three phase service voltage of commercial and industrial sites in the United States. The service is usually a wye connection so that the star point voltage of 277 can be used for building lighting.
In Canada the three phase system voltage for commercial and industrial is 347/600 volts
220 volt single phase from 480 volt 3 phase that one wire taken one phase and second wire connected in earth point. we get 220 v The above answer is incorrect, one phase from a three phase 480 volt system will give you 277 volts to ground. You must use a transformer to get the voltage you need.
You Don't. 440volt 3-phase is actually 480 volts, taking a single phase gives 277Volts single phase. To get single phase 440 you would use one leg of three phase 440/760 three phase power.
Across a 480 volt three phase system, 480 volts should appear across L1 and L2, L2 and L3 and L3 and L1.
No, you will not obtain 230 volts. From a wye connected three phase 480 volt supply, 277 volts can be obtained from one phase leg and the neutral on the wye connection. 480 volts/1.73 (sq. root of 3) = 277 volts.
Current in 200kw at 480 volts = 200,000/480 = 416.667 amps
220 volt single phase from 480 volt 3 phase that one wire taken one phase and second wire connected in earth point. we get 220 v The above answer is incorrect, one phase from a three phase 480 volt system will give you 277 volts to ground. You must use a transformer to get the voltage you need.
You Don't. 440volt 3-phase is actually 480 volts, taking a single phase gives 277Volts single phase. To get single phase 440 you would use one leg of three phase 440/760 three phase power.
Across a 480 volt three phase system, 480 volts should appear across L1 and L2, L2 and L3 and L3 and L1.
No, you will not obtain 230 volts. From a wye connected three phase 480 volt supply, 277 volts can be obtained from one phase leg and the neutral on the wye connection. 480 volts/1.73 (sq. root of 3) = 277 volts.
240/220 480 volts 3 phase
Current in 200kw at 480 volts = 200,000/480 = 416.667 amps
If the heater is rated as a 3 phase 480 volt heater then a neutral is not needed. If the voltage stated is 277 volts three phase then a neutral is needed.
You should not need a wiring diagram. If the generator has a star point (wye) connection then the phase voltage to ground (star point) is 277 volts. 480/1.73 = 277.
These voltages are both wye connection three phase voltages. The voltage difference comes from the primary three phase voltage supplies. 277 volts is obtained from 277 x 1.73 = 480 and 240 volts is obtained from 240 x 1.73 = 415. 480/277 volts is a common three phase American voltage. 415/240 volts is a European voltage. In Canada a common three phase voltage is 347/600. The 240 volts could also be a single phase voltage in North America derived from a split phase secondary on a distribution transformer that supplies 120/240 volts to homes.
Usually yes. A typical 480 volt panel is a 3 phase panel with 480 volts line-to-line and 277 volts line-to-neutral. However, I did once see a panel that was 480 volts, 3 phase, but because it served only motors it did not have a neutral. (a 3 phase motor doesn't use a neutral.) Similarly, if a panel uses only 2 legs of a 3 phase 480 volt system, which would be called single phase, it would not require a neutral if it only feeds 480 volt single phase loads. But I find the idea of no neutral to be extremely unusual and in my one personal experience, I blamed it on the age of the system. In 16 years of commercial and industrial construction I have never installed a 3 phase panel without a neutral and all my work is designed by engineers.
From a three phase four wire distribution system the voltages would be as follows. From L1 to N - 277 volts. From L2 to N - 277 volts. From L3 to N - 277 volts. From L1 to L2 - 480 volts. From L2 to L3 - 480 volts. From L3 to L1 -480 volts.
The star point or wye voltage of a 480 volt three phase four wire system is 277 volts. The 480 voltage is divided by the sq root of 3 (for 3 phases). The sq root of 3 is 1.73. 480 volts/1.73 = 277 volts. The same formula is used on all three phase four wire systems. 208 volts /1.73 = 120 volts, 416 volts /1.73 = 240 volts, 600 volts / 1.73 = 347 volts.