The emf induced in the rotor depends upon the rotor frequency which further depends on relative speed between rotor and synchronous speed of rotating magnetic field. The relative speed at the time of starting or standstill is maximum and hence large emf in induced in rotor conductors or winding due to which very high current flows in rotor which is generally 5 to 7 times of the full load or running current of an indication motor.
The starting current, sometimes called inrush current will be 8-10 times higher than the motor's rated current because the motor is at rest.
When at rest, the motor appears to be a transformer, with it's secondary winding short circuited, i.e. the rotor winding or squirrel cage is a closed circuit. This results in a low impedance to the system voltage and the motor has a "locked rotor" current of typically 6 times full load current, but also up to 8 and sometimes 10 times current.
This starting value is independent of any load attached, however, the inertia of the motor and load has to be overcome. This is especially true when the motor is connected to a load, like a conveyor belt with product on it. The larger the inertia, the longer the motor takes to reach full speed.
As the motor accelerates, part of the starting current power overcomes this inertia and is conveted to kinetic energy. The remaining power of the starting current heats the rotor, up to possibly 250 deg C for a "long" start (20 seconds!!).
During the first couple of cycles of AC current, transient currents make some of the phases have higher assymetrical values, which can cause nuisance tripping of the supply breakers to the motor, when protection settings are too low!
Equation for current: I = P / cos phi / ( 1.732 * V), (cos phi can be 0.3 during starting).
V (voltage) stays pretty much constant, therefore I (current) must rise (but is limited to the locked rotor value for the specific motor) as P (power) is required to start the motor and to keep it running.
Some voltage drop will occur for most power systems during a motor start, thus with a constant locked rotor impedance, the starting current will reduce proportionally.
I start = V / 1.732 / Z (locked rotor) for a three phase motor. (Z is fixed)
When nearly full running speed is reached, the current drops rapidly to full load current or less, depending on the actual load attached.
-Don't forget to recommend Kevlarster if you like this answer!
yes
There is no fixed limit on the number of start and stop operations for an induction motor. However, frequent start and stop operations can lead to increased wear and tear on the motor, affecting its lifespan. It is advisable to minimize frequent start and stop operations to prolong the motor's longevity.
A CSIR motor stands for Capacitor Start-Induction Run motor, which is a type of single-phase induction motor commonly used in household appliances like refrigerators and air conditioners. It uses a capacitor to provide the starting torque needed to initiate rotation, then operates as a standard induction motor once up to speed.
Open ended induction motor - i assume you are talking about split phase induction motor. With these motors old style speed controlling method using external resistors can be used. However this is now obsolete.
A star-delta starter is a method used to reduce the starting current drawn by a 3-phase induction motor. It involves initially connecting the motor windings in a star configuration for starting, and then switching to a delta configuration for running. This helps to minimize voltage drops and prevents excessive current flow during start-up.
capacitive start motors start by themselves however a normal single phase induction motor requires a starter motor to 'kick-start' the motor into action.
yes
A single phase induction motor is mainly used in fans.It is capacitor start capacitor run induction motor.In three phase induction motor squirrel cage induction motor is mainly used in elevators,lifts,cranes.slip ring induction motor is mainly used in electrically driven ships.
Three Phase Induction Motor is self starting motor so you can start it by conneting to power lines directly if the power line capacity is sufficient.
The single phase induction motors are made self starting by providing an additional flux by some additional means. Now depending upon these additional means the single phase induction motors are classified as: 1.Split phase induction motor. 2.Capacitor start inductor motor. 3.Capacitor start capacitor run induction motor. 4. Shaded pole induction motor.
To start an induction motor we have to excite field. The excitation is done by connecting the DC supply to the field winding's.
A single phase induction motor has two sets of coils and a centrifugal start switch. The start winding is in series with the start switch. The start winding provides a rotating magnetic field in one direction enabling the motor to start. The motor can be reversed by reversing the connections of either the start winding or the run winding but not both.
to start the motor and give more current to motor to run
Yes the Induction motor works on Electromagnetic induction principle.
Single phase induction motor ( usually capacitor- start type)
capacitor start induction run motor
There is no fixed limit on the number of start and stop operations for an induction motor. However, frequent start and stop operations can lead to increased wear and tear on the motor, affecting its lifespan. It is advisable to minimize frequent start and stop operations to prolong the motor's longevity.