You need to specify the rating , voltage and phases of the motor to answer this question.
The no-load current of a motor, such as a 90 kW motor operating at 440V and 60Hz, can vary based on its design and efficiency. Typically, the no-load current for such motors ranges from 10% to 30% of the full-load current. To estimate the no-load current, you can use the formula: No-load current ≈ Full load current × (no-load current percentage). The full-load current can be calculated using the formula: Full Load Current (A) = Power (W) / (Voltage (V) × √3 × Power Factor).
The ratio is between 30% to 40 %
Ohm's law: voltage is current times resistance 0.03 amperes times 1000 ohms = 30 volts.
To calculate the power of a contactor when you know the current (in this case, 30 amps), you can use the formula: Power (P) = Voltage (V) × Current (I). First, determine the voltage at which the contactor operates (e.g., 120V, 240V, or 480V). Then, multiply the voltage by the current: for example, at 240V, the power would be P = 240V × 30A = 7,200 watts (or 7.2 kW).
To calculate the resistance, you can use Ohm's Law, which states that ( R = \frac{V}{I} ), where ( R ) is resistance, ( V ) is voltage, and ( I ) is current. Given a potential difference of 12 V and a current of 0.4 A, the resistance can be calculated as follows: [ R = \frac{12 , \text{V}}{0.4 , \text{A}} = 30 , \Omega ] Thus, the resistance is 30 ohms.
The no-load current of a motor, such as a 90 kW motor operating at 440V and 60Hz, can vary based on its design and efficiency. Typically, the no-load current for such motors ranges from 10% to 30% of the full-load current. To estimate the no-load current, you can use the formula: No-load current ≈ Full load current × (no-load current percentage). The full-load current can be calculated using the formula: Full Load Current (A) = Power (W) / (Voltage (V) × √3 × Power Factor).
The ratio is between 30% to 40 %
The starting current of any electrical equipment which is 6 times more than that of the full load current. ex: full load current = 5 A the starting current will be 5*6 = 30 A.
The maximum current rating for the circuit breaker should be at least 30 amps to accommodate the continuous current of 25 amps required by the load.
if you know the gauge of the wire you can learn its current carrying capacity
Ohm's law: voltage is current times resistance 0.03 amperes times 1000 ohms = 30 volts.
Minimum current would be 10000 divided by 240 but it might be up to 30% more if the load has a poor power factor.
To calculate three-phase meter reading in kWh with CT coils, you need to first determine the current ratio provided by the CT coils. Multiply the current readings obtained from the CT coils with the current ratio to get the actual current values. Then, multiply the actual current values with the voltage and power factor to get the power in each phase. Finally, sum the power in each phase and multiply by the time in hours to get the kWh reading.
To calculate the power in watts, you will also need to know the current in amperes. The formula to calculate power is P (watts) = V (volts) x I (amperes). If you only have the voltage (30 volts) and not the current, you cannot determine the power in watts.
This is for 30 day accounts... 100% of total debtors ledger less current * 90%
The rates change every day. Use this currency converter to calculate it.
The load current must not exceed 30 amps. That's the safe limit.