A Buchholz relay is situated in an inclined pipe between the transformer itself and its expansion tank. It (a) provides an alarm should there be an oil leak or if excessive gas accumulation within the relay and, (b) will disconnect the transformer in the event of a major oil loss or a surge within the oil (caused by a fault within the transformer).
resistic earth fault relay install on transformer nutral .
OSR meance oil surge relay & it is used in x'mer OLTC . it is measured if any surge produce in oil then the give the signsl to relay panel for tripping of transformer
I am going to assume that you are asking about a differential relay. It is basically just that- it compare two different sources and will trip at a set value value of the difference. These can be directional as well. A couple of examples are transformer protective relays and bus differential. A transformer relay will measure the amount of current coming into the transformer and the amount of current going out. If there is a disparity due to an internal fault the relay will trip the supply source and deenergize the transformer. Same for the Bus differential.
A differential relay for a transformer is designed to detect faults by comparing the current entering and exiting the transformer. Under normal operating conditions, the incoming and outgoing currents should be equal; any significant difference indicates a fault, such as a short circuit or ground fault within the transformer. When a discrepancy is detected, the relay triggers an alarm or disconnects the transformer from the power system to prevent damage and ensure safety. This protective mechanism helps maintain the reliability and integrity of electrical systems.
It depends what you mean by an '11-kV transformer'; do you mean a primary transformer (33/11-kV transformer) or a distribution transformer (11-kV/400-230-V transformer). Differential protection IS offered on primary transformers.
A Buchholz relay is designed to detect a failing oil-filled power transformer. It will automatically disconnect the transformer and produce an alarm signal.
Physicially it has transformer tank, conservator, bucholz relay , windings, oil
The indicates the direction for correct installation. Bucholz relay operates when gas bubbles in the transformer oil pass through the relay in its pathway. The relay has to be installed arrow indicating upwards.
Power Transformer
an REF relay (restricted earth fault) is used to provide ground fault protection for a transformer. Its' operation is limited by CTs starred towards the transformer (usually on the transformer bushings or in breakers used to isolate the transformer), so it will only operate for transformer related faults. Because of this, it can be set to operate very quickly.
resistic earth fault relay install on transformer nutral .
OSR meance oil surge relay & it is used in x'mer OLTC . it is measured if any surge produce in oil then the give the signsl to relay panel for tripping of transformer
I am going to assume that you are asking about a differential relay. It is basically just that- it compare two different sources and will trip at a set value value of the difference. These can be directional as well. A couple of examples are transformer protective relays and bus differential. A transformer relay will measure the amount of current coming into the transformer and the amount of current going out. If there is a disparity due to an internal fault the relay will trip the supply source and deenergize the transformer. Same for the Bus differential.
In power transformer, a differential relay is a relay that verifies the balance of current between the primary and the secondary face of a transformer. It is also employed in other components of the power system like in protecting cables. Differential relay is also called a unit protection.
CT (Current Transformer ) is essential whether is electronic relay or electromagnetic relay. A relay requires the CT to sense the line current.
An isolation transformer is a mutual transformer having a voltage ratio of 1:1, so that the secondary circuit is electrically isolated from the primary circuit, yet subject to the same voltage.An earth protection relay is a category of protective relay that responds to an earth fault monitored by a current transformer (CT). In the event of an earth fault being detected by the CT, the relay with activate the trip circuit to a circuit breaker which will then disconnect the fault.
A 'voltage transformer' (called a 'potential transformer' in North America) is classified as an 'instrument transformer', and is used to reduce the voltage of an electrical system to a lower, safe, level for the purposes of either operating a voltmeter or supplying a protection relay. At the same time, it electrically-isolates the meter or relay from the high-voltage system.