50 sq.mm of aluminium

and 25 to 35 sq.mm of copper

User Avatar

Wiki User

13y ago

What else can I help you with?

Related Questions

What cable size of wire if the machine is 50hp?

If it is a 480v 3 pH machine, #4 wire will be fine.


What is the cable size for 55kw motor on 3 phase?

Without knowing the nominal voltage rating, who can tell? <<>> The sizing of cables or conductors is based on the amperage that the conductor can safely carry. The formula for amperage is I = W/E. Amps = 12000/Volts. With out a voltage stated an answer to this question can not be answered. When you calculate the amperage, re-ask your question for a conductor size for a given amperage.


In 3 hp 415vOLT what are the size of cable in mm?

6mm cable


What is the cable size for 1.5KW 3 phase induction motor?

Sir, what is the cable size for 1.5kw 3phase induction motor 400v?


What size cable for 50 amps 3 phase for 650 meters length?

70mm 4core copper cable


What is the recommended gauge size for a 100 amp cable?

The recommended gauge size for a 100 amp cable is typically 3 AWG (American Wire Gauge) for copper wire.


What is the recommended cable size for a 100 amp electrical circuit?

The recommended cable size for a 100 amp electrical circuit is typically 3 AWG copper or 1/0 AWG aluminum.


Low voltage cable size calculation formula?

1) determine load /design current. eg 13kw oven Ib=13000W/230V if 3 phase- 13000w/1.73*400V =56.52A In(circuit breaker size)=60A 2) In/ C1+C2+C3 (c is coefficient of ambience temperature of type of cable referred to BS tables) 3) value of above refer to BS tables for appropiate cale size. eg. based on 60A cable size is 16mm2 pvc/pvc cable size


Could you Calculate cable size for 100 kw load?

To calculate the cable size for a 100 kW load, you would need to consider factors such as the voltage of the system, the type of cable insulation, the ambient temperature, and the installation method. The cable size is typically determined by the maximum current the cable will carry without overheating. Using the formula: Cable size (mm²) = (2 x L x I x R) / (√3 x V x cosΦ), where L is the cable length, I is the load current, R is the resistance of the cable, V is the voltage, and cosΦ is the power factor, you can calculate the appropriate cable size for the 100 kW load.


What size of cable will you need for a 3 phase panel running 3 3kw motors?

To answer this question a voltage must be stated.


What size snake in a 3inch drain cleanout?

The cable is 3/4 to 1 inch diameter with a head that expands with the rotation. For a 3 inch drain you use a powered auger that turns the cable.


What size cable should be used for a 3phase 10kw Air Heater?

To answer this question the voltage of the unit must be given.